background image

PAGE 8

QualityWaterForLess.com

Help: 888-426-5001

3)  Locate the plumbing adaptors and bypass valve 

assembly that was shipped with your system, 
attach the three o-rings to the rear of the valve 
and lubricate them using the included silicone 
lubricant packet as shown in Figure 8-A

4)  Push the bypass valve snugly to the back of the 

Autotrol 255/760 valve and use the screws and 
nuts to secure the bypass valve as shown in 
figure Figure 8-B

F I G u R e   8 - a

F I G u R e   8 - B

F I G u R e   8 - F

7)  Locate the two plumbing adaptors supplied 

with your system. Insert the plumbing adapter 
through the universal nut and then push down 
the gasket over the adaptor flange as shown in 
Figure 8-E below

8)  Secure each plumbing adaptor onto the bypass as 

shown in Figure 8-F. 

i

 

If you are using copper 

connections, first prefabricate and sweat a 

12” tube section onto each adaptor and cool 

BefORe assembly to the bypass.

 This prevents 

overheating the nut and bypass during plumbing

F I G u R e   8 - C

F I G u R e   8 - e

5)  Locate the drain port on the bypass, apply Teflon 

tape in a clockwise fashion, locate the included 
drain barb elbow, and assemble the fitting as 
shown in Figure 8-C

6)  Assemble your ½” I.D. drain line to the drain barb. 

Be 

sure to use rigid wall ½” I.d. tubing that will not 

flatten.

 

Wrap electrical tape over the drain tubing 

to prevent a tube split and clamp the tubing secure-
ly into place with the included clamp as shown in 
Figure 8-D. 

i

 

Connect the other end of this drain 

line tubing securely to a standpipe or drain in 

accordance with all local plumbing codes 

F I G u R e   8 - d

Содержание 255/760

Страница 1: ...v1 0 AUTOTROL 255 760 Metered Water Softener Install ation Guide...

Страница 2: ...ming When you first plug in your unit the control will require you to enter the adjacent values Use the UP DOWN buttons to cycle through the settings use the SQUARE SET button to enter edit mode use t...

Страница 3: ...lve Page 9 Plumbing the System into your Home and Making the Brine Tank Connection Preface Thank you for your purchase of a new water softener with Autotrol 255 760 Meter Control Valve from QualityWat...

Страница 4: ...er by 17 1 to get Grains gpg Ex If your hardness is measured at 300 PPM take 300 17 1 18 gpg before iron 3 Compensated Hardness Your Iron results should also be measured in either PPM or mg L Take you...

Страница 5: ...x33 Grid 18x40 Grid 24x41 Grid 24x50 Grid 24K 0 75 cu ft 8x44 0 10 gpg Low 2 25 lbs NO GRID NO GRID NO GRID NO GRID TOO LARGE TOO LARGE 10 20 gpg Standard 6 75 lbs Grid Grid NO GRID NO GRID 20 gpg Hig...

Страница 6: ...Fig u r e 6 a Fig u r e 6 b pre install ation Before assembly of your new system be sure that the following conditions have been met for the place ment of your system Level firm surface such as concr...

Страница 7: ...r d fi n e m es h 3 Installing the Autotrol 255 760 Valve 1 Remove the filling funnel and tape and while using the included silicone lubricant packet lubri cate the inner and outer o rings on the bot...

Страница 8: ...ow 8 Secure each plumbing adaptor onto the bypass as shown in Figure 8 F i If you are using copper connections first prefabricate and sweat a 12 tube section onto each adaptor and cool BEFORE assembly...

Страница 9: ...ording to all local plumbing codes If using copper pipe please pre fabricate at least a 12 section of pipe for the IN and OUT bound lines and use a wet rag on the lines being soldered to prevent heat...

Страница 10: ...e tube and insert the tube through the small hole drilled through the brine tank and brine well Loosely un screw the hex nut on the 2310 Brine Float Assem bly Insert the tubing end firmly into the hex...

Страница 11: ...UP or DOWN buttons to change to the current time of day i Note that there is a difference between AM and PM Then press the SET button to make this setting active Figure 11 E 6 Next is the Day of the W...

Страница 12: ...ess the SET button to begin editing choose L for 0 10 gpg S for 10 20 gpg and H for 20 gpg Use the UP or DOWN buttons to make the appropriate chang es to the salt setting and press the SET button to m...

Страница 13: ...lons of water the amount of water needed to cover the brine grid into the brine tank Start the regeneration sequence by HOLDING the REGEN button for 5 seconds Once the hourglass symbol disappears let...

Отзывы: