2 TM4 Communication Settings
© Copyright Reserved Autonics Co., Ltd.
11
2
TM4 Communication Settings
Devices
from the TM series do not have graphic interface; To change the devices’ settings, we need
to use the device management program from Autonics: DAQMaster.
Set the desired Modbus address thanks to the ‘Communication address’ switches, this address
1st
should be unique on the network:
Connect the TM device to DAQMaster
2nd
Please follow the procedure in annex part of this document to connect a TM device to the DAQMaster
program and have access to its parameters.
In the DAQ Master ‘Property’ window, set the parameters of the ‘Communication Setting’ group
3rd
as following:
Parameter
DAQ Master
setting name
Value range
Note
Comm. speed
Baudrate
Multiple choice
User setting, same than the PLC
parameter
Comm. Parity bit
Parity Bit
None
Fixed
Comm. Stop bit
Stop Bit
2
User setting
Comm. Response
waiting time
Response
waiting Time
20
User setting
Comm. writing
Communication
Write
Enable
Fixed
Device address
Not available
1 to 31
User setting by switch dials, should
be unique on the network