Group
Parameter
Range
Factory Default
Unit
Alarm Setting Group
Alarm Type
See above
table.
AL-A
-
You can set alarm output (Alarm 1 Type to Alarm 4 Type)
individually.
If alarm output mode has been selected as LBA, SBA or HBA,
AL-C, AL-D modes are not available.
6.4.4
Alarm SV setting
You can set alarm output activation values. According to the selected alarm output mode,
configuration parameters (AL
□
.H/AL
□
.L) will be activated for each setting.
Group
Parameter
Range
Factory
Default
Unit
Alarm
Setting
Group
Alarm High_CH
Alarm Low_CH
Deviation alarm:
By input type –F.S. to F.S.
Absolute value alarm:
Within display range by input type
1550
℃,℉
Changing the alarm output mode or options resets the settings to the
highest or lowest values that will not trigger output in the new mode.
6.4.5
Alarm Output Hysteresis Settings
“H” shown in the image from 6-4-2. Alarm Output Mode reresents the alarm output
hysteresis. It is used to set an interval between alarm output ON/OFF periods.
Can be set individually by alarm output (Alarm 1 Type to Alarm 2 Type).
Group
Parameter
Range
Factory
Default
Unit
Alarm Setting
Group
Alarm Hysteresis_Ch
1 to 100
(Temperature H),
0.1 to 100.0
(Temperature L)
1
℃,℉
Alarm output hysteresis applies to heater burnout alarm (HBA)
in the same manner.
This parameter does not appear if Loop Break Alarm (LBA) or
Sensor Break Alarm (SBA) is selected.
Содержание TM Series
Страница 1: ...User Manual ...
Страница 2: ......
Страница 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Страница 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Страница 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Страница 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Страница 34: ...4 Connections and block diagram 34 Copyright Reserved Autonics Co Ltd 3 Example of connection 4 1 TM4 Series ...
Страница 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Страница 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Страница 52: ...6 Parameter Settings and Functions 52 Copyright Reserved Autonics Co Ltd 6 2 1 3 1 1 Using a Deadband ...
Страница 53: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 53 6 2 1 3 1 2 Using an Overlap Band ...
Страница 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Страница 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Страница 96: ......
Страница 97: ......