6
Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd.
55
6.2.2
MV High/Low-limit Settings
MV high/low-limit values for control output can be configured to the actual MV,
provided the temperature controller's MV calculation exceeds the limits.
During heating and cooling control, cooling MV carries a "-" prefix. Therefore, the
high-limit is expressed as a + value on the heating side and the lower limit as a -
value on the cooling side.
Group
Preceding
Condition
Parameter
Range
Factory
Default
Unit
Control
Operation
Group
Heating
Cooling
MV Low-limit
0.0 to (MV High-limit - 0.1)
0.0
%
MV High-limit
(MV Low-limit + 0.1) to 100.0
100.0
Heating
and
Cooling
MV Low-limit
-100.0 ~ 0.0
-100.0
%
MV High-limit
0.0 ~ 100.0
100.0
Same MV will be applied during Auto-tuning.
MV limits are not applied to manual control, MV upon control
stop, MV upon a sensor error, and initial manual control MV.
MV high/low-limit configuration is not available for ON/OFF
control in standard control mode (heating or cooling control).
Содержание TM Series
Страница 1: ...User Manual ...
Страница 2: ......
Страница 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Страница 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Страница 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Страница 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Страница 34: ...4 Connections and block diagram 34 Copyright Reserved Autonics Co Ltd 3 Example of connection 4 1 TM4 Series ...
Страница 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Страница 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Страница 52: ...6 Parameter Settings and Functions 52 Copyright Reserved Autonics Co Ltd 6 2 1 3 1 1 Using a Deadband ...
Страница 53: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 53 6 2 1 3 1 2 Using an Overlap Band ...
Страница 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Страница 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Страница 96: ......
Страница 97: ......