2 Communication Setting 

© Copyright Reserved Autonics Co., Ltd. 

 

13 

2

 

Communication Setting 

2.1

 

MP5W Setting 

1st

 

Supply power to the MP5W unit. Press the MODE key to enter parameter setting group. 
 

2nd

 

Enter 

PARa3

 and set the communication settings as below. 

Parameter 

Display 

Setting 

Note 

Communication address 

ADDR 

01 

User setting 

Communication speed 

BPS 

38400 

User setting 

Communication parity bit 

PRTY 

NONE 

Fixed 

Communication stop bit 

STP 

Fixed 

Communication response 
waiting time 

RSwT 

20 

User setting 

Communication write 

COmW 

ENA 

Fixed 

* Hold the MODE key over 3 sec while in setting mode to return to RUN mode.   

* Hold the MODE key for 1.5 sec while in setting mode to move to other parameter group.   

* Press the MODE key after the setting and it is saved.   

* If there is no additional key operation within 60 sec after entering into setting mode, it will   

be automatically returned to RUN mode and previous set value will be remained.   

* Check that RS485 communication models are only available communication. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание MP-XGT

Страница 1: ...Copyright Reserved Autonics Co Ltd iii MP XGT RS485 Technical Support Manual...

Страница 2: ...ii Copyright Reserved Autonics Co Ltd...

Страница 3: ...ecting Autonics products Please familiarize yourself with the information contained in the Safety Precautions section before using this product This user manual contains information about the product...

Страница 4: ...e edited or reproduced in either part or whole without permission This manual is not provided as part of the product package Please visit our home page www autonics com to download a copy The manual s...

Страница 5: ...anual Symbols Symbol Description Supplementary information for a particular feature Failure to follow instructions can result in serious injury or death Failure to follow instructions can lead to a mi...

Страница 6: ...disassemble or modify the unit Please contact us if necessary Failure to follow this instruction may result in electric shock or fire Check the terminal numbers before connecting the power source and...

Страница 7: ...td 7 Keep dust and wire residue from flowing into the unit Failure may result in fire or product malfunction Check the polarity of the measurement input contact before wiring the unit Failure to follo...

Страница 8: ...Safety Precautions 8 Copyright Reserved Autonics Co Ltd...

Страница 9: ...Technical Support Manual Guide 4 Technical Support Manual Symbols 5 Safety Precautions 6 Table of Contents 9 1 System 11 1 1 Version 11 1 2 Connections 11 1 3 Communication cable connection 11 2 Commu...

Страница 10: ...Table of Contents 10 Copyright Reserved Autonics Co Ltd...

Страница 11: ...sion Software Version Note Ms Windows Windows 7 XG 5000 V4 07 Release 2016 03 29 1 2 Connections RS 485 RS 485 RS 485 RS 485 XGK CPUE MP5W MP5W MP5W MP5W XGl CH2A 1 3 Communication cable connection MP...

Страница 12: ...1 System 12 Copyright Reserved Autonics Co Ltd...

Страница 13: ...Y NONE Fixed Communication stop bit STP 2 Fixed Communication response waiting time RSwT 20 User setting Communication write COmW ENA Fixed Hold the MODE key over 3 sec while in setting mode to return...

Страница 14: ...2 Communication Setting 14 Copyright Reserved Autonics Co Ltd 2 2 XG5000 Setting 1st Run XG5000 and select Project New Project on menu Enter project name and select CPU Series and type...

Страница 15: ...ation Setting Copyright Reserved Autonics Co Ltd 15 2nd After executing enter the below contents at XG5000 This communication program is only for test Before using it at field review and test the prog...

Страница 16: ...ings to select connection method This test is connected via USB After completing connection select Online Mode Switch Stop 4th At Online Diagnose I O Information click I O Sync After I O synchronize t...

Страница 17: ...etwork Double click the right communication module 6th Standard Settings Cnet dialog box appears At standard settings set as below Item Setting Note Standard Settings Channel 2 Communication type RS 4...

Страница 18: ...ht Reserved Autonics Co Ltd 7th At advanced settings set as below Item Channel 2 Advanced settings Data bit 8 Stop bit 2 Parity bit NONE 8th At Project window select the communication module and Add I...

Страница 19: ...2 Communication Setting Copyright Reserved Autonics Co Ltd 19 9th Double click P2P Channel and select Modbus RTU client of Use P2P Click OK...

Страница 20: ...station number 2 READ PV M00000 to M00003 2 Continuous WORD size 2 Enter destination station 1 to 4 Refer to the below table for variable setting for PV and SV Click Setting to set variable Modbus Ma...

Страница 21: ...21 PV setting Station Read area setting Save area setting Address fixed Station 1 0x303E9 D00000 N00021 Station 2 0x303E9 D00002 N00062 Station 3 0x303E9 D00004 N00103 Station 4 0x303E9 D00006 N00144...

Страница 22: ...2 Communication Setting 22 Copyright Reserved Autonics Co Ltd 11thAt Online Connection Settings select connection type Select Online Write to execute download...

Страница 23: ...3 Operation Check Copyright Reserved Autonics Co Ltd 23 3 Operation Check...

Страница 24: ...3 Operation Check 24 Copyright Reserved Autonics Co Ltd...

Отзывы: