background image

-|Transparent Guide|-

  

I/O port indicator

01. Pin 4 (C/Q)

Indicator

LED color

Status

Description

0

Yellow

OFF

DI/DO: pin 4 OFF

ON

DI/DO: pin 4 ON

Green

ON

Port configuration: IO-Link

Flashing 

(1 Hz)

Port configuration: IO-Link, 

No IO-Link device found

Red

Flashing 

(2 Hz)

IO-Link configuration error 

•  Validation failed, Invalid data length, 

 

Data Storage error

ON

• NPN:  Short circuit occurred on the output of 

pin 4 and pin 1

• PNP:  Short circuit occurred on the output of 

pin 4 and pin 3

02. Pin 2 (I/Q)

Indicator

LED color

Status

Description

1

Yellow

OFF

DI: pin 2 OFF

ON

DI: pin 2 ON

03. The power supply of the I/O port

Indicator

LED color

Status

Description

0,1

Red

Flashing 

(1 Hz)

Short circuit occurred 

in the I/O supply power (pin 1, 3)

  

Status indicator

01. The power supply of sensor

Indicator

LED color

Status

Description

US

Green

ON

Applied voltage: normal

Flashing

(1 Hz)

The settings of the rotary switches is 

changing.

Red

Flashing

(1 Hz)

Applied voltage: low (< 18 VDCᜡ)

02. The power supply of actuator

Indicator

LED color

Status

Description

UA

Green

ON

Applied voltage: normal

Red

Flashing 

(1 Hz)

Applied voltage: low (< 18 VDCᜡ), 

Error in the rotary switches

ON

Applied voltage: none (< 10 VDCᜡ)

03. Product initialization

Indicator

LED color

Status

Description

US, UA

Red

ON

ADIO initialization failure

04. System failure

Indicator

LED color

Status

Description

SF

Red

OFF

No error

ON

Watchdog timeout, system error

Flashing

DCP signal service is initiated via the bus. 

05. 

Bus failure

Indicator

LED color

Status

Description

BF

Red

OFF

No error

ON

Low speed of physical link or no physical link

Flashing

No data transmission or configuration settings

06. Ethernet connection

Indicator

LED color

Status

Description

L/A1

L/A2

Green

OFF

No Ethernet connection

ON

The Ethernet connection is established.

Yellow

Flashing

Data transmission

07. Transmission rate of the Ethernet

Indicator

LED color

Status

Description

100

Green

ON

Transmission rate: 100 Mbps

Indicators

Содержание ADIO-PN

Страница 1: ...dify the unit Failure to follow this instruction may result in fire 06 Do not touch the product during operation or for a certain period of time after stopping Failure to follow this instruction may result in burn Caution Failure to follow instructions may result in injury or product damage 01 Use the unit within the rated specifications Failure to follow this instruction may result in fire or sho...

Страница 2: ...ADIO PN Integrate the ADIO PN to PROFINET project ADIO PN TIA Portal V16Guide 01 Set the ports of ADIO PN Checking the operation Check the indicators ADIO PN Product Manual 01 The project planning software of the upper level communication system may be different depending on the user s environment For more information refer to the manufacturer s manual Operation mode Safe State01 Validation Data S...

Страница 3: ... 4 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data Power supply port OUT 7 8 Socket Female IN 7 8 Plug Male Pin Function Description 1 2 3 4 5 5 4 3 2 1 1 2 0 V Sensor and actuator supply 3 F G Frame ground 4 24 VDCᜡ Sensor supply 5 24 VDCᜡ Actuator supply PDCT port M12 Socket Female A coded Pin Function 1 4 5 3 2 1 Not Connected N C 2 Data 3 0 V 4 Not Connected N C 5 Dat...

Страница 4: ...ide 29 6 4 7 1 3 215 24 26 5 26 5 26 5 35 26 Ø4 5 7 8 X 2EA 203 35 20 38 6 3 1 3 8 35 33 4 30 5 M4 X 0 7 Ø4 5 M12 X 1 X 11EA 66 Dimensions Unit mm For the detailed dimensions of the product follow the Autonics website ...

Страница 5: ... Prepare a flat or metal panel in the enclosure 02 Drill a hole to mount and ground the product on the surface 03 Turn off all power 04 Fix the product using M4 screws in the mounting holes Tightening torque 1 5 N m M4 M4 Installation UnitDescriptions 1 2 3 2 4 4 5 5 6 7 9 10 8 01 Grounding hole 02 Mounting hole 03 Insertion part for the name plate 04 Ethernet port 05 Power supply port 06 PDCT por...

Страница 6: ...y switches Description Value PROFINET Device Name 000 This device name is stored in the ADIO PN s EEPROM Applying the device name configured on the PROFINET Master or DCP tools PROFINET device name 001 to 999 Establish the communication connection after setting the ADIO PN s device name The value of rotary switches is displayed at the last of the device name ADIO PN MA08A ILM 02 Turn on the ADIO P...

Страница 7: ...tor 1 Function Connector 2 Pin no Connector 2 Function 1 N C 1 5 VDCᜡ 2 Data 2 Data 3 0 V 4 0 V 4 N C 5 Data 3 Data 01 Connect to the PROFINET 01 Connect the M12 connector to the Ethernet port See the connections below 1 2 3 4 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data 02 Connect the connector to the PROFINET network Network device PLC or PROFINET device supporting P...

Страница 8: ... 24 VDCᜡ Sensor supply 5 24 VDCᜡ Actuator supply 1 2 3 4 5 5 4 3 2 1 PWR OUT PWR IN PortConnections 03 Connect with the atIOLink Do not use the PDCT port and the Ethernet port at the same time 01 Connect the M12 connector to the PDCT port See the connections below 1 4 5 3 2 1 Not Connected N C 2 Data 3 0 V 4 Not Connected N C 5 Data 02 Connect the connector to the network device Network device PC ...

Страница 9: ...ngs of the rotary switches is changing Red Flashing 1 Hz Applied voltage low 18 VDCᜡ 02 The power supply of actuator Indicator LED color Status Description UA Green ON Applied voltage normal Red Flashing 1 Hz Applied voltage low 18 VDCᜡ Error in the rotary switches ON Applied voltage none 10 VDCᜡ 03 Product initialization Indicator LED color Status Description US UA Red ON ADIO initialization fail...

Страница 10: ... 4 W 216 W Supplying current per port 2 A Port Sensor current US 9 A Dimensions W 66 H 215 D 38 mm Material Zinc Die casting Ethernet port M12 Socket Female 4 pin D coded Push Pull Number of ports 2 IN OUT Supported function daisy chain Power supply port Input 7 8 Plug Male 5 pin Output 7 8 Socket Female 5 pin Number of ports 2 IN OUT Supported function daisy chain PDCT port M12 Socket Female 5 pi...

Отзывы: