background image

Terminal base 

specifications

Terminator I/O terminal bases are available in 
screw clamp and spring clamp versions for both 
half-size and full-size modules. Hot stamp silk 
screen labeling is used for numbering I/O points, 
commons, and all power terminals.

Screw clamp, half-size

Screw clamp, full-size

2 and 3-wire DC input devices 

using bussed 24VDC power

Use externally supplied 24VDC 

power or 24VDC auxiliary power 

from T1K-01AC

Spring clamp, full-size

Spring clamp, half-size

T1K-08B   $62.00

T1K-16B   $77.00

T1K-16B-1   $77.00

T1K-08B-1   $62.00

Field Device Wiring and Power Options

Do not jumper modules together 

to create a 24VDC bus when using 

the “hot swap” feature. See Note 

below.

Terminal Base Specifications

Terminal Type

Screw type

Spring clamp

Recommended 

Torque

1.77–3.54 lb·in 

(0.2–0.4 N·m)

N/A

Wire Gauge

Solid: 

25–12 AWG 

Stranded: 

26–12 AWG

Solid: 

25–14 AWG 

Stranded: 

26–14 AWG

Field device wiring options

Power your DC input devices from the 
integrated 24VDC power supply bus. 
T1K-08ND3 and T1K-16ND3 DC input 
modules include jumpers for selecting the 
internal 24VDC power supply available 
for 2- and 3-wire field devices. Clearly 
labeled triple stack terminals make it easy 
to wire 2- and 3-wire devices ensuring 
clean wiring with only one wire per 
termination.
External user supplied 24VDC power, or auxil-
iary 24VDC terminals from T1K-01AC, can 
be easily applied directly to one end of the 
terminal rows and jumpered across each base 
in the system. 
This is a convenient solution for powering 
analog I/O and discrete DC output devices 
whose modules do not have direct access 
to the internal bussed 24VDC. If current 
consumption increases, simply add addi-
tional T1K-01AC power supplies into the 
system.

Hot-swap feature

The hot-swap feature allows Terminator I/O 
modules to be replaced while system power is 
on. Be careful not to touch the terminals with 
your hands or other conductive material to 
avoid the risk of personal injury or equipment 
damage. Always remove power if it is equally 
convenient to do so.

Note

: Before hot-swapping analog or 

DC output modules in a Terminator I/O 
system, make sure that each of the analog 
and DC output module’s 24VDC and 0 
VDC base terminals are wired directly to 
the external power supply individually. If the 
external 24VDC and 0 VDC is jumpered 
from base to base in a daisy chain fashion, 
and an analog or DC output module is 

removed from its base, the risk of discon-
necting the external 24VDC and 0 VDC to 
the subsequent I/O modules exists.

w w w . a u t o m a t i o n d i r e c t . c o m

Universal Field I/O

tFED-57

For the latest prices, please check AutomationDirect.com.

1 - 8 0 0 - 6 3 3 - 0 4 0 5

Содержание T1K-08ND3

Страница 1: ...r Module 8 sink source Commons Non isolated Ext power 2 isolated 4 pts com Int power 2 all 8 pts internally connected Operating Voltage Range 12 24 VDC Input Voltage Range 10 8 26 4 VDC min max Peak Range 30VDC Input Current Typical 4mA 12VDC 8 5 mA 24VDC Input Impedance 2 8 kq ON Voltage Level 10 0 VDC OFF Voltage Level 2 0 VDC Min ON Current 4mA Max OFF Current 0 5 mA OFF to ON Response 2 8 ms T...

Страница 2: ... Per Module 16 sink source Commons Non isolated Ext power 4 isolated 4 pts com Int power 4 all 16 pts internally connected Operating Voltage Range 12 24 VDC Input Voltage Range 10 8 26 4 VDC Peak Range 30VDC Input Current Typical 4 mA 12VDC 8 5 mA 24VDC Input Impedance 2 8 Kq ON Voltage Level 10 0 VDC OFF Voltage Level 2 0 VDC Min ON Current 4 mA Max OFF Current 0 5 mA OFF to ON Response 2 8 ms Ty...

Страница 3: ... isolated Input Voltage Range 80 132 VAC 47 63 Hz Operating Voltage Range 90 120 VAC 47 63 Hz Input Current 8mA 100VAC 50Hz 10mA 100VAC 60Hz 12mA 132VAC 50Hz 15mA 132VAC 60Hz 8mA 100VAC 50Hz 10mA 100VAC 60Hz 12mA 132VAC 50Hz 15mA 132VAC 60Hz Input Impedance 14kq 50Hz 12kq 60Hz ON Current Voltage 6mA 75VAC OFF Current Voltage 2mA 20VAC OFF to ON Response 40ms ON to OFF Response 40ms Base Power Requ...

Страница 4: ...access and cable clearance However your distance may be greater or less Also check the installation guidelines for the recom mended cabinet clearances 48mm 1 89in 80mm 3 15in 80mm 3 15in 48mm 1 89in 80mm 3 15in 48mm 1 89in 89mm 3 5in 80mm 3 15in 83 3mm 3 28in Power Supply Network Interface Module Half size I O Module with Base System Depth Full size I O Module with Base Dimensions and Installation...

Страница 5: ...parate terminal bases for easy installation To install I O modules 1 Slide the module into its terminal base until it clicks into position 2 Hook upper DIN rail tabs over the top of DIN rail and press the assembly firmly onto the DIN rail 3 Slide the module along the DIN rail until it engages with the adjacent module DN ASB 1 angled mounting bracket Optional angled support bracket raises and tilts...

Страница 6: ... MVSTBW 2 5 6 ST 5 08 BK Note 500mA 24VDC can be achieved by lowering the 5VDC from 2000mA to 1500mA Power Budget Example Module 5VDC 24VDC T1K 01AC 2000mA 300mA T1H EBC100 300mA 0mA T1K 16ND3 70mA 0mA T1K 16TD2 200mA 0mA T1F 08AD 1 75mA 50mA Remaining 1355mA 250mA Module 5VDC 24VDC Analog Input Modules T1F 08AD 1 75 50 T1F 08AD 2 75 50 T1F 16AD 1 75 50 T1F 16AD 2 75 50 T1F 16RTD 150 0 T1F 16TMST ...

Страница 7: ...s pass 24VDC through on an isolated wire All cables pass the 5VDC base power Any local expansion DC input module configured for internal power current sourcing must either have a power supply preceding it on the same base or have a 1 version cable pass 24VDC from a power supply on the preceding base In the system below power supplies can be used anywhere T1K 10CBL 1 I O Addressing T1K 10CBL 1 Cabl...

Страница 8: ...ean wiring with only one wire per termination External user supplied 24VDC power or auxil iary 24VDC terminals from T1K 01AC can be easily applied directly to one end of the terminal rows and jumpered across each base in the system This is a convenient solution for powering analog I O and discrete DC output devices whose modules do not have direct access to the internal bussed 24VDC If current con...