It is important to understand the installa-
tion requirements for your Terminator I/O 
system. This will ensure that the Terminator 
I/O products work within their environmental 
and electrical limits.

Plan for safety

This catalog should never be used as 
a replacement for the technical data 
sheet that comes with the products or the  
T1K-INST-M Installation and 
I/O Manual (available online at 

 

www.automationdirect.com.) The technical 
data sheet contains information that must 
be followed. The system installation should 
comply with all appropriate electrical codes 
and standards.

Unit dimensions and 

mounting orientation

Use the following diagrams to  decide if 
the Terminator I/O system can be installed 
in your application. Terminator I/O units 
should be mounted horizontally. To ensure 
proper airflow for cooling purposes, units 
should not be mounted upside-down. It 
is important to check the Terminator I/O  
dimensions against the conditions required 
for your application. For example, it is 
recommended to leave 2” depth for ease of 
access and cable clearance. However, your 
distance may be greater or less. Also, check 
the installation guidelines for the recom-
mended cabinet clearances.

48mm

(1.89in)

80mm

(3.15in)

80mm

(3.15in)

48mm

(1.89in)

80mm

(3.15in)

48mm

(1.89in)

89mm

(3.5in)

80mm

(3.15in)

83.3mm

(3.28in)

Power Supply

Network Interface Module

Half-size I/O Module 

with Base

System Depth

Full-size I/O Module 

with Base

Dimensions and Installation

 

See the Enclosures 

section for an enclosure that may 

be suitable for your application

Terminator I/O Environmental Specifications

Ambient Operating 

Temperature

32°F to 131°F (0°C to 55°C)

Storage 

Temperature

-4°F to 158°F (-20°C to 70°C)

Ambient Humidity

5% to 95% (Non-condensing)

Atmosphere

No corrosive gases. The level of environmental  

pollution = 2   (UL 840)

Vibration 

Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand 

(Dielectric)

1500VAC, 1 minute

Insulation 

Resistance

500 VDC, 10 M

q

Noise Immunity

NEMA  ICS3-304 

Impulse noise 1µs, 1000V 

FCC class A 

RFI (144MHz, 430MHz  10W, 10cm)

Agency Approvals

UL, CE, FCC class A, NEC Class 1 Division 2

w w w . a u t o m a t i o n d i r e c t . c o m

Universal Field I/O

tFED-53

For the latest prices, please check AutomationDirect.com.

1 - 8 0 0 - 6 3 3 - 0 4 0 5

Содержание T1K-08ND3

Страница 1: ...r Module 8 sink source Commons Non isolated Ext power 2 isolated 4 pts com Int power 2 all 8 pts internally connected Operating Voltage Range 12 24 VDC Input Voltage Range 10 8 26 4 VDC min max Peak Range 30VDC Input Current Typical 4mA 12VDC 8 5 mA 24VDC Input Impedance 2 8 kq ON Voltage Level 10 0 VDC OFF Voltage Level 2 0 VDC Min ON Current 4mA Max OFF Current 0 5 mA OFF to ON Response 2 8 ms T...

Страница 2: ... Per Module 16 sink source Commons Non isolated Ext power 4 isolated 4 pts com Int power 4 all 16 pts internally connected Operating Voltage Range 12 24 VDC Input Voltage Range 10 8 26 4 VDC Peak Range 30VDC Input Current Typical 4 mA 12VDC 8 5 mA 24VDC Input Impedance 2 8 Kq ON Voltage Level 10 0 VDC OFF Voltage Level 2 0 VDC Min ON Current 4 mA Max OFF Current 0 5 mA OFF to ON Response 2 8 ms Ty...

Страница 3: ... isolated Input Voltage Range 80 132 VAC 47 63 Hz Operating Voltage Range 90 120 VAC 47 63 Hz Input Current 8mA 100VAC 50Hz 10mA 100VAC 60Hz 12mA 132VAC 50Hz 15mA 132VAC 60Hz 8mA 100VAC 50Hz 10mA 100VAC 60Hz 12mA 132VAC 50Hz 15mA 132VAC 60Hz Input Impedance 14kq 50Hz 12kq 60Hz ON Current Voltage 6mA 75VAC OFF Current Voltage 2mA 20VAC OFF to ON Response 40ms ON to OFF Response 40ms Base Power Requ...

Страница 4: ...access and cable clearance However your distance may be greater or less Also check the installation guidelines for the recom mended cabinet clearances 48mm 1 89in 80mm 3 15in 80mm 3 15in 48mm 1 89in 80mm 3 15in 48mm 1 89in 89mm 3 5in 80mm 3 15in 83 3mm 3 28in Power Supply Network Interface Module Half size I O Module with Base System Depth Full size I O Module with Base Dimensions and Installation...

Страница 5: ...parate terminal bases for easy installation To install I O modules 1 Slide the module into its terminal base until it clicks into position 2 Hook upper DIN rail tabs over the top of DIN rail and press the assembly firmly onto the DIN rail 3 Slide the module along the DIN rail until it engages with the adjacent module DN ASB 1 angled mounting bracket Optional angled support bracket raises and tilts...

Страница 6: ... MVSTBW 2 5 6 ST 5 08 BK Note 500mA 24VDC can be achieved by lowering the 5VDC from 2000mA to 1500mA Power Budget Example Module 5VDC 24VDC T1K 01AC 2000mA 300mA T1H EBC100 300mA 0mA T1K 16ND3 70mA 0mA T1K 16TD2 200mA 0mA T1F 08AD 1 75mA 50mA Remaining 1355mA 250mA Module 5VDC 24VDC Analog Input Modules T1F 08AD 1 75 50 T1F 08AD 2 75 50 T1F 16AD 1 75 50 T1F 16AD 2 75 50 T1F 16RTD 150 0 T1F 16TMST ...

Страница 7: ...s pass 24VDC through on an isolated wire All cables pass the 5VDC base power Any local expansion DC input module configured for internal power current sourcing must either have a power supply preceding it on the same base or have a 1 version cable pass 24VDC from a power supply on the preceding base In the system below power supplies can be used anywhere T1K 10CBL 1 I O Addressing T1K 10CBL 1 Cabl...

Страница 8: ...ean wiring with only one wire per termination External user supplied 24VDC power or auxil iary 24VDC terminals from T1K 01AC can be easily applied directly to one end of the terminal rows and jumpered across each base in the system This is a convenient solution for powering analog I O and discrete DC output devices whose modules do not have direct access to the internal bussed 24VDC If current con...

Отзывы: