Reset to Factory Default Instructions

Mounting Instructions

SOLO temperature controllers can be mounted through a cutout in an enclosure or panel by using the dimen-

sions shown in Section 5. The directions for mounting the controller through a cutout are:
1. Insert the temperature controller through the panel cutout.
2. Slide the M3X0.5 nut into the opening in the top of the mounting bracket and insert the M3X0.5 X 30mm

mounting screw in the mounting bracket.
3. Insert the mounting bracket into the mounting groove at the top and bottom of the controller, and push the

mounting bracket forward until the bracket stops.
4. Tighten top and bottom screws evenly to secure temperature controller in place.

1

4

3

22

4848

PV

SOLO

F

C

SV

OUT1 OUT2

ALM

AT

SET

6

SL4848-LV

SL4848-VV

SL4848-CV

WARNING! Electric shock danger

To prevent electric shock, do not connect AC power to your device until all input and output

connections are completed.

SL4848-RR

SL4848-VR

SL4848-CR

Terminal Identification

SL4848-LR

7

Display, LED and Key Pad

4848

PV

SOLO

F

C

SV

OUT1

OUT2

ALM

AT

SET

PV Display: To display the process value or parameter type.
SV Display: To display the set point, parameter operation read value

manipulated variable or set value of the parameter.

AT: Auto-tuning LED, flashes when the Auto-tuning operation is ON.
OUT1 / OUT2: Output LED, lights when the output is ON.
ALM: Alarm output LED, lights when one of the alarms is on.
°C, °F: Temperature unit LED. °C: Celsius °F: Fahrenheit

Set Button: Press this key to select the desired function mode and

confirm the setting value.
Rotate Button: Press this key to select parameters within the function

mode.
Down Button: Press this key to decrease values displayed on the SV

display. Hold down this key to speed up the decrement.
Up Button: Press this key to increase values displayed on the SV

display. Hold down this key to speed up the increment.

8

10

All of the following set up instructions are for setting up a controller from the factory defaults. If the appli-

cation for a controller needs to be changed, reset the controller to factory default using the following

steps.
1. Press the

'

button until the parameter

loC

appears. Use the

.

button to select

loC1

. Press the

;

button.

2. Press and hold the

,

and

.

buttons simultaneously for one second and release.

3. Press the

'

button repeatedly until the PV display shows

pass

. Use the

,

button to change the value

on the SV display to

1357

. Press the

;

button.

4. Cycle power on the Controller to reset to factory default mode. All user set values are erased.

Key Pad Operation

Operation Mode

SET

Hold for 3 sec.

SET

Initial Setting

Mode

Regulation

Mode

SET

Press for less

than 3 sec.

Initial Setting

Parameters

Operation

Parameters

Regulation
Parameters

SET

The SOLO temperature controller has three function modes: Initial Setting mode, Operation mode and Regulation

mode. When power is first applied to the temperature controller, the module information splash screen appears.

This screen shows the firmware version on the PV display and the two output types for that particular model on

the SV display. After three seconds, the controller will automatically proceed to the Operation mode main screen.

Press and hold the

;

button for three seconds to go into the Initial Setting mode. Press the

;

button for less

than three seconds to access the Regulation mode. Press the

'

button while inside any of the three function

modes to access the individual parameters for each function mode. Use the

.

and

,

buttons to change the

individual parameter values. Pressing the

;

button saves the parameter values. Press the

;

button again

to return the controller to the Operation mode.

1. Access the Initial Setup mode by pressing and holding the

;

button for three seconds. In the parameter

inpt

, use the

,

and

.

buttons to select the value that corresponds to the thermocouple or RTD type

that will be attached to the controller. See the table below for specifications. Press the

;

button to save the

selected value. The controller will display the module information splash screen for three seconds and then return

to the main screen.
2. Press the

;

button for three seconds again. Press the

'

button to access the

tpun

parameter. Use

the

,

and

.

buttons to select either

C

for Centigrade or

f

for Fahrenheit display. Press the

;

button

to save the selected value. The controller will display the module information splash screen for three seconds and

then return to the main screen.
3. Press the

;

button for three seconds again. Press the

'

button repeatedly until the

tp-H

parameter

appears. Use the

,

and

.

buttons to set the maximum value of the operational temperature range. In oper-

ation, if the PV value is higher than the TP-H value, the PV display flashes to indicate an error and the controller

outputs shut off. The SV value cannot exceed the TP-H value. Press the

;

button to save the selected value.

Press the

'

button to access the

tp-l

parameter. Use the

,

and

.

buttons to set the minimum value

of the operational temperature range. In operation, if the PV value is lower than the TP-L value, the PV display

flashes to indicate an error and the controller outputs shut off. The SV value cannot be set lower than the TP-L

value. Press the

;

button twice to save the selected value and return to the controller main screen.

4. Press the

'

button repeatedly until the parameter

sp

appears. Use the

,

and

.

buttons to select

either

0

for a whole degree or

1

for a tenth degree temperature display.* Press the

;

button twice to save

the selected value and return to the controller main screen.
5. If the input temperature from the thermocouple or RTD needs to be adjusted, press the

;

button for less

than 3 seconds. Press the

'

button repeatedly until the parameter

tpof

appears. Use the

,

and

.

buttons to adjust a positive or negative offset to the PV value displayed on the controller. Press the

;

button

twice to save the selected value and return to the controller main screen.

*Note: The decimal point display cannot be adjusted for B, S, and R type thermocouples.

Thermocouple or RTD Input

Thermocouple* Type and Temperature Range

Input Temperature Sensor Type

LED Display

Temperature Range

Thermocouple TXK type

txk

-328 ~ 1472°F (-200 ~ 800°C)

Thermocouple U type

u

-328 ~ 932°F (-200 ~ 500°C)

Thermocouple L type

l

-328 ~ 1562°F (-200 ~ 850°C)

Thermocouple B type

b

-212 ~ 3272°F (100 ~ 1800°C)

Thermocouple S type

s

32 ~ 3092°F (0 ~ 1700°C)

Thermocouple R type

r

32 ~ 3092°F (0 ~ 1700°C)

Thermocouple N type

n

-328 ~ 2372°F (-200 ~ 1300°C)

Thermocouple E type

e

32 ~ 1112°F (0 ~ 600°C)

Thermocouple T type

t

-328 ~ 752°F (-200 ~ 400°C)

Thermocouple J type

j

-148 ~ 2192°F (-100 ~ 1200°C)

Thermocouple K type

k

-328 ~ 2372°F (-200 ~ 1300°C)

RTD Type and Temperature Range

Input Temperature Sensor Type

LED Display

Temperature Range

Platinum Resistance (Pt100)

pt

-328 ~ 1112°F (-200 ~ 600°C)

Platinum Resistance (JPt100)

jpt

-4 ~ 752°F (-20 ~ 400°C)

*Note: Use only ungrounded thermocouples.

11-1

Sensor Input

Power Input

9

0 – 10 VDC

4 – 20 mA

2-wire RTD

Thermocouple

3-wire RTD

AC Powered

Models

DC Powered

Models

24 VDC power for models with
–D suffix only

All manuals and user guides at all-guides.com