Appendix A: Accessories
Page A–3
GS1 Series AC Drives User Manual – 3rd Edition – 11/09/2018
L
ine
R
eactoR
S
pecificationS
– LR S
eRieS
Line Reactors – LR Series
Part Number
Rated
Amps
Imped
-ance
Inductance
Watt
Loss
System
Voltage
Phase
– Use *
GS1 Drive
Model
Drive
HP
LR-10P2-1PH **
5�8
3%
1�58 mH
8�0
120
1 – In
GS1-10P2
0�25
LR-10P5-1PH **
9�8
0�93 mH
11�7
GS1-10P5
0�5
LR-20P5-1PH **
4�9
3�74 mH
11�2
240
1 – In
GS1-20P2
0�25
GS1-20P5
0�5
LR-20P5
2�4
4�2 mH
7
208/240
3 – Out
GS1-10P2
0�25
GS1-10P5
0�5
3 – I/O
GS1-20P2
0�25
GS1-20P5
0�5
LR-21P0-1PH **
8
2�29 mH
15�9
240
1 – In
GS1-21P0
1
LR-21P0
4�6
2�46 mH
11
208/240
3 – I/O
LR-22P0-1PH **
12
1�53 mH
24�3
240
1 – In
GS1-22P0
2
LR-22P0
7�5
1�35 mH
21
208/240
3 – I/O
* Use (side of drive): In = input only; Out = output only; I/O = input or output.
** Single phase line reactors should NOT be installed on the output side of the AC drive.
Part Number
(repeated)
Wire Range
Terminal
Torque
Fasteners
Temperature Range
Environment
Operating
Storage
LR-10P2-1PH
#12–#18 AWG
10 lb·in
#6-32x5/16in
flathead screw
-40 – 104 °F
[-40 – 40 °C]
-40 – 149 °F
[-40 – 65 °C]
NEMA: open
IP00
no corrosive
gases
LR-10P5-1PH
#12–#18 AWG
10 lb·in
LR-20P5-1PH
#12–#18 AWG
10 lb·in
#6-32x5/16in
flathead screw
LR-20P5
#12–#18 AWG
10 lb·in
LR-21P0-1PH
#12–#18 AWG
10 lb·in
LR-21P0
#12–#18 AWG
10 lb·in
LR-22P0-1PH
#12–#18 AWG
20 lb·in
LR-22P0
#12–#18 AWG
10 lb·in
L
ine
R
eactoR
S
pecificationS
– L
egacy
gS S
eRieS
(
do
not
uSe
foR
new
inStaLLationS
)
115V Single Phase Input Line Reactors *
Part Number
Rated
Amps Impedance Inductance
Watt
Loss
GS1 Drive Model and
Side / Phase / Volts
Drive
hp
GS-10P2-LR
18
3%
0�80 mH
19
GS1-10P2 (input) / 1ph / 115V
0�25
GS-10P5-LR
25
3%
0�50 mH
23
GS1-10P5 (input) / 1ph / 115V
0�5
*NOTE: Single phase line reactors should NOT be installed on the output side of the AC drive.
230V Single Phase Input Line Reactors *
Part Number
Rated
Amps Impedance Inductance
Watt
Loss
GS1 Drive Model and
Side / Phase / Volts
Drive
hp
GS-20P5-LR-1PH
8
3%
6�50 mH
13
GS1-20P5 (input) / 1ph / 230V
0�5
GS-21P0-LR-1PH
12
3%
6�50 mH
13
GS1-21P0 (input) / 1ph / 230V
1
*NOTE: Single phase line reactors should NOT be installed on the output side of the AC drive.
230V Three Phase Input / Output Line Reactors
Part Number
Rated
Amps Impedance Inductance
Watt
Loss
GS1 Drive Model and
Side / Phase / Volts
Drive
hp
GS-20P5-LR-3PH
4
3%
6�50 mH
13
GS1-10P5 (output) / 3ph /
230V
GS1-20P5 (in/out) / 3ph / 230V
0�5
GS-21P0-LR-3PH
4
3%
3�00 mH
7
GS1-21P0 (in/out) / 3ph / 230V
1
GS-22P0-LR-3PH
8
3%
1�50 mH
11
GS1-22P0 (in/out) / 3ph / 230V
2