Environment for Operation, Storage, and Transportation
DO NOT expose the GS20 drive to environments that contain dust, direct sunlight, corrosive/inflammable
gases, high humidity, liquids, or high vibration. The salt in the air must be less than 0.01 mg/cm
2
throughout
the year.
Envir
onment
Installation Location IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only
Surrounding
Temperature
Storage: -40°C to +85°C
Transportation: -20°C to +70°C
No condensation, non-frozen
Rated Humidity
Operation: Max. 90%
Storage/Transportation: Max. 95%
No condensed water
Air Pressure
Operation/Storage: 86 to 106 kPa
Transportation: 70 to 106 kPa
Pollution Level
IEC60721-3
Operation:
Class 3C2; Class 3S2
Storage:
Class 2C2; Class 2S2
Transportation:
Class 1C2; Class 1S2
No concentrate
Altitude
Operation
If the GS20 drive is installed at altitudes of 0~1000m, follow normal
operation restriction. If installed at altitudes of 1000~2000m, decrease
1% of rated current or lower 0.5°C of temperature for every 100m
increase in altitude. Maximum altitude for Corner Grounded is 2000m.
Contact ADC for more information if you need to use this motor drive at
an altitude of 2000m or higher.
Package
Drop
Storage
ISTA procedure 1A (according to weight) IEC60068-2-31
Transportation
Vibration
Operating
1.0mm, peak-to-peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from
13.2Hz to 55Hz; 2.0G range from 55Hz to 512 Hz. Comply with IEC 60068-2-6.
Non-operating
2.5 G peak, 5Hz~2kHz: 0.015” maximum displacement.
Impact
Operating
IEC/EN60068-2-27: 15G, 11ms
Non-operating
30G
Protection Level
IP40 - main unit
IP20 - wiring area (main circuit terminals and control terminals (all frame types),
and the vent near the capacitor on frame C, D, E, and F types).
To prevent personal injury, please make sure that the case and wiring are installed
according to these instructions. The figures in these instructions are only for reference.
They may be slightly different from the one you have, but it will not affect your
customer rights.
These installation instructions may be revised without prior notice. The most recent
edition can be downloaded from the AutomationDirect web site at any time:
http://www.automationdirect.com/static/manuals/index.html.
Minimum Mounting Clearances
When installing your GS20 drive, please keep the following in mind:
• Prevent fiber particles, scraps of paper, shredded wood, saw dust, metal particles, etc., from adhering to the
heat sink.
• Install the AC motor drive in a metal cabinet. When installing one drive below another one, use a metal
separation between the AC motor drives to prevent mutual heating and to prevent the risk of accidental fire.
• Install the AC motor drive in Pollution Degree 2 environments only: normally only nonconductive pollution
occurs and temporary conductivity caused by condensation is expected.
←
(Blue Arrow) Inflow
←
(Red Arrow) Outflow
Single drive Independent installation.
Side-by-side horizontal installation:
Installation Method
A
(mm)
B
(mm)
C
(mm)
Operation Temperature
Max
(w/out derating)
Max
(Derating)
Single drive installation
50
30
–
50
60
Side-by-side horizontal installation
50
30
30
50
60
Zero stack installation
50
30
0
40
50