background image

4

Tech Support 770-844-4200

www.productivity1000.com

Port Specifications

 RS-232 Specifications

Port Name

RS-232

Description

Non-isolated RS-232 DTE port connects the CPU as a 

Modbus/ASCII master or slave to a peripheral device. 

Includes ESD and built-in surge protection

Data Rates

Selectable,1200, 2400, 4800, 9600, 19200, 33600, 

38400, 57600, and 115200

+5V Cable Power Source

210mA maximum at 5V, ±5%. Reverse polarity and 

overload protected 

TXD

RS-232 Transmit output

RXD

RS-232 Receive input

RTS 

Handshaking output for modem control

GND

Logic ground 

Maximum Output Load 

(TXD/RTS)

3k

, 1000 pf

Minimum Output Voltage 

Swing

±5 V

Output Short Circuit 

Protection

±15 mA

Port Status LED 

Green LED is illuminated when active for TXD, RXD 

and RTS

Cable Options

EA-MG-PGM-CBL

D2-DSCBL

USB-RS232 with D2-DSCBL

FA-CABKIT

FA-ISOCON for converting RS-232 to isolated RS-485

6-pin RJ12 Female

Modular Connector

1

6

RS-232

TX

RT

SR

X

Pin #

Signal

1

GND

Logic Ground

2

+5V

210mA Maximum

3

RXD

RS-232 Input

4

TXD

RS-232 Output

5

RTS

RS-232 Output

6

GND

Logic Ground

RS-485 Port Specifications

Port Name

RS-485

Description

Non-isolated RS-485 port connects the CPU as a 

Modbus/ASCII master or slave to a peripheral device. 

Includes ESD/EFT protection and automatic echo 

cancellation when transmitter is active

Data Rates

Selectable, 1200, 2400, 4800, 9600, 19200, 33600, 

38400, 57600, and 115200

TXD+/RXD+

RS-485 transceiver high

TXD-/RXD-

RS-485 transceiver low

GND

Logic ground

Input Impedance

19k

Termination Resistance

(TB Jumper wire “T” to “+”)

120

Maximum Load

50 transceivers, 19k

 each, 60

 termination

Output Short Circuit 

Protection

± 250mA, thermal shut-down protection

Electrostatic Discharge  

Protection

± 8KV per IEC1000-4-2

Electrical Fast Transient 

Protection

± 2KV per IEC1000-4-4

Minimum Differential Output 

Voltage

1.5 V with 60

 load

Fail Safe Inputs

Logic high input state if inputs are unconnected 

Maximum Common Mode 

Voltage

-7.5 V to 12.5 V

Port Status LED

Green LED illuminated when active for TXD and RXD

Cable Options

Recommend L19827-XXX from AutomationDirect.com

Pin #

Signal

T

TERMINATION

+

TXD+/RXD+

-

TXD-/RXD-

G

GND

T

+

-

G

RS-485

PCON-KIT

Содержание Productivity 1000 P1-540

Страница 1: ...red 24VDC 2 5W plus 1 25 W per additional I O module See page 6 for Power Supply options Recommended Fuse External Edison S5061 R Time Delay 1A Fuse Communications 4 Integrated Ports USB IN Programmin...

Страница 2: ...H MIN MAX P1 08TD1 Check all latches are secure after modules are connected CPU Front Panel P1 540 RUN STOP PWR RUN CPU REMOTE I O RS 232 RS 485 10 100 ETHERNET ACT LINK G T LINK ACT PGM LINK RX TX TX...

Страница 3: ...compartment located on the top of the CPU Step Two Insert battery and close compartment Squeeze tabs and pull battery holder up to remove battery P1 540 P1 540 Take care to insert battery behind tab...

Страница 4: ...Maximum 3 RXD RS 232 Input 4 TXD RS 232 Output 5 RTS RS 232 Output 6 GND Logic Ground RS 485 Port Specifications Port Name RS 485 Description Non isolated RS 485 port connects the CPU as a Modbus ASC...

Страница 5: ...RD 1 2 3 4 5 6 7 8 TD TD RD RD 1 2 3 4 5 6 7 8 TD TD RD RD 1 2 3 4 5 6 7 8 RJ45 RJ45 RJ45 RJ45 OR WHT OR GRN WHT BLU BLU WHT GRN BRN WHT BRN OR WHT OR GRN WHT BLU BLU WHT GRN BRN WHT BRN OR WHT OR GRN...

Страница 6: ...Conductor 28 16 AWG Stranded Conductor Screw Driver Width 1 8 in 3 175 mm Maximum Screw Size M2 Screw Torque 1 7 lb in 0 4 N m Productivity1000 Power Supplies All Productivity1000 PLC CPUs require 24...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com...

Страница 8: ...al codes that regulate the installation and operation of your equipment These codes vary from area to area and it is your responsibility to determine which codes should be followed and to verify that...

Отзывы: