Ethernet Communications Modules, 3rd Edition, Rev. D
5-13
Chapter 5: MODBUS TCP for H0/H2/H4-ECOM100
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Word Data Types*
Registers (Word)
(V-Memory)
Qty
(Dec.)
PLC Range
(Octal)
Modbus 40001
Address Range
Modbus 30001
Address Range
Access
Timers
256
V0 – V377
40001 – 40256
30001 – 30256
Read/Write
Counters
256
V1000 – V1377
40513 – 40768
30513 – 30768
Data Words
256
V400 – V777
40257 – 40512
30257 – 30512
3072
V1400 – V7377
40769 – 43840
30769 – 33840
5906
V10000 – V23416
44097 – 49999
34097 – 39999
5361
V23417 – V35777
410000 – 415360
310000 – 315360
System Parameters
128
1024
V7600 – V7777
V36000 – V37777
43969 – 44096
415361 – 416384
33969 – 34096
315361 – 316384
Remote Inputs
128
V40000 – V40177
416385 – 416512
316385 – 316512
Read Only
Remote Outputs
128
V40200 – V40377
416513 – 416640
316513 – 316640
Read/Write
Input Points
64
V40400 – V40477
416641 – 416704
316641 – 316704
Read Only
Output Points
64
V40500 – V40577
416705 – 416768
316705 – 316768
Read/Write
Control Relays
128
V40600 – V40777
416769 – 416896
316769 – 316896
Timer Status Bits
16
V41100 – V41117
416961 – 416976
316961 – 316976
Counter Status Bits
16
V41140 – V41157
416993 – 417008
316993 – 317008
Special Relays
32
V41200 – V41237
417025 – 417056
317025 – 317056
Read Only
* Refer to your PLC user manual for the correct memory mapping size of your PLC. Some of the addresses shown above might not pertain to your particular CPU.