If Your Host Software or Client Requires the Data Type and Address
Many Modbus TCP clients allow you to specify the Modbus data type and the Modbus address
that corresponds to the PLC memory location. This is the easiest method, but not all packages
allow you to do it this way.
The actual equation used to calculate the address depends on the type of PLC data you are using.
The PLC memory types are split into two categories for this purpose.
• Discrete – X, SP, Y, C, S, T(contacts), CT (contacts)
• Word – V-Memory, Timer current value, Counter current value
In either case, you basically convert the PLC octal address to decimal and add the appropriate
Modbus starting address (as required). The following tables show the exact range used for each
group of data.
NOTE:
For an automated Modbus/Koyo address conversion utility, download the file
Modbus_conversion.xls
from the
www.automationdirect.com
technical support website.
DL05 Memory Type
Qty
(Dec.)
PLC Range
(Octal)
Modbus
Address Range
Modbus
Data Type
For Discrete Data Types...
Convert PLC Addr. to Dec.
+ Start of Range
+ Data Type
Inputs (X)
256
X0 – X377
2048 – 2303
Input
Special Relays (SP)
512
SP0 – SP777
3072 – 3583
Input
Outputs (Y)
256
Y0 – Y377
2048 – 2303
Coil
Control Relays (C)
512
C0 –C777
3072 – 3583
Coil
Timer Contacts (T)
128
T0 – T177
6144 – 6271
Coil
Counter Contacts (CT)
128
CT0 – CT177
6400 – 6527
Coil
Stage Status Bits (S)
256
S0 – S377
5120 – 5375
Coil
For Word Data Types ...
Convert PLC Addr. to Dec.
+ Data Type
Timer Current Values (V)
128
V0 – V177
0 – 127
Input Register
Counter Current Values (V)
128
V1000 – V1177
512 – 639
Input Register
V-Memory, user data (V)
3072
V1400 – V7377
768 – 3839
Holding Register