Appendix B
Appendix B
Analog Output Module
Appendix E
B–2
Analog Output Module Configuration
Analog Output Module Control Byte
The Terminator I/O analog output modules are configured using the Module
Control Byte located in the most significant byte of the most significant word of
channel 1 of the module. The “I/O Memory Map and Analog Module Resolution”
chapter in the Terminator Installation and I/O Manual (T1K–INST–M) covers
memory mapping for the Terminator I/O modules.
Channel 1 Memory Map
of 8&16-Channel Analog Output Module
(T1F–08DA, T1F–016DA)
Decimal Bit
07
06
05
04
03
02
01
00
Size
Octal Bit
07
06
05
04
03
02
01
00
Size
Analog Value Channel 1
Write Byte 1
Analog Value Channel 1
Write Byte 2
not used
Byte3
Module Control Byte
Write Byte 4
Module Control Byte of 8&16-Channel Analog Output Module
(T1F–08DA, T1F–16DA)
Decimal Bit
31
30
29
28
27
26
25
24
Read/Write
Octal Bit
37
36
35
34
33
32
31
30
Read/Write
Bit 24
Outputs Enable
0 = All outputs OFF
1 = All outputs Enabled
Write
Bit 25
Unipolar / Bipolar
0 = Unipolar selected
1 = Bipolar selected
Write
Bit 26
5V / 10V Range
0 = 5V range
1 = 10V range
Write
Bit 27
0 – 20mA / 4–20mA Range
0 = 0 – 20mA range
1 = 4 – 20mA range
Write
Bit 28 – 31
Reserved for system use
–
Содержание T1K-MODBUS-M
Страница 1: ...Terminator I O MODBUS Base Controller User Manual Manual Number T1K MODBUS M...
Страница 25: ...1 Using the T1K MODBUS Setup Tool 4 In This Chapter Configuring the T1K MODBUS Port...
Страница 28: ...1A Appendix A I O Module Hot Swap In This Appendix T1K MODBUS I O Module Hot Swap Feature...
Страница 31: ...1B Appendix B Analog Output Module Configuration In This Appendix Analog Output Module Control Byte...