T1K–MODBUS Specifications
Setting the Rotary Address Switches
The T1K–MODBUS unit address is set by the two rotary switches on the front of the
unit. Addresses are in hexadecimal format with valid address from 00 to F7, which is
equivalent to 0 to 247 decimal. The addresses do not have to be sequential, but each
station address must be unique.
The top rotary switch is used to set the most significant digit of the HEX address. The
lower switch is used to set the least significant digit in the HEX address.
.
.
X10
X1
UNIT
ADRS
(HEX)
Eventhough the T1K–MODBUS unit address is set in HEX, it’s not difficult to
calculate the equivalent decimal address used by the MODBUS protocol.
To calculate the equivalent HEX address:
1) Divide the decimal address desired by 16. This provides the X10 HEX digit.
2) The remainder will be a number less than 16, resulting in a HEX number between
0–F. The remainder provides the X1 HEX digit. Two examples are given below.
So 60 decimal = 3C HEX
60
÷
16 = 3
0 1 2 3 4 5 6 7 8 9
with remainder of 12 = C
60 decimal
HEX Format
Decimal format
So 24 decimal = 18 HEX
24
÷
16 = 1
with remainder of 8 = 8
24 decimal
10 11 12 13 14 15
0 1 2 3 4 5 6 7 8 9 A B C D E F
Converting HEX
Addresses to
Decimal
Содержание T1K-MODBUS-M
Страница 1: ...Terminator I O MODBUS Base Controller User Manual Manual Number T1K MODBUS M...
Страница 25: ...1 Using the T1K MODBUS Setup Tool 4 In This Chapter Configuring the T1K MODBUS Port...
Страница 28: ...1A Appendix A I O Module Hot Swap In This Appendix T1K MODBUS I O Module Hot Swap Feature...
Страница 31: ...1B Appendix B Analog Output Module Configuration In This Appendix Analog Output Module Control Byte...