T1K–MODBUS
Specificaions
Installation and
Safety Guidelines
2–5
T1K–MODBUS Specifications
The Communications Setting mode, DIP Switch 4, enables some of the MODBUS
port communication parameters to be user set using the T1K–MODBUS Set Up
Tool. The following tables describe the default and option modes.
SW 4 Communication Setting Mode
OFF
Default Mode
ON
Option Mode
Default Mode:
The following table lists the MODBUS port default settings when DIP Switch 4 is in
the OFF position.
SW 4 OFF
MODBUS Port / Default
Mode
Item
Default Setting
Communication Data
8 Bit
Start Bit
1 Bit
Stop Bit
1 Bit
Parity Bit
ODD
Communication Timeout
1s
RTS ON Delay Time
0ms
RTS OFF Delay Time
0ms
Option Mode:
The following items are user selectable using the T1K–MODBUS Set Up Tool* when
DIP Switch 4 is in the ON position.
SW 4 ON
MODBUS Port / Option Mode
Item
Default Setting
Communication Data
8 Bit (Fixed)
Start Bit
1 Bit (Fixed)
Stop Bit*
1 Bit / 2 Bit
Parity Bit*
ODD / EVEN / NONE
Communication Timeout*
500ms, 1s, 2.5s, 5s, 10s, 25s, 60s
RTS ON Delay Time*
0ms, 2ms, 5ms, 10ms, 20ms, 50ms, 100ms, 500ms
RTS OFF Delay Time*
0ms, 2ms, 5ms, 10ms, 20ms, 50ms, 100ms, 500ms
Содержание T1K-MODBUS-M
Страница 1: ...Terminator I O MODBUS Base Controller User Manual Manual Number T1K MODBUS M...
Страница 25: ...1 Using the T1K MODBUS Setup Tool 4 In This Chapter Configuring the T1K MODBUS Port...
Страница 28: ...1A Appendix A I O Module Hot Swap In This Appendix T1K MODBUS I O Module Hot Swap Feature...
Страница 31: ...1B Appendix B Analog Output Module Configuration In This Appendix Analog Output Module Control Byte...