Do-more H2 Series PLC Hardware User Manual, 1st Edition, Rev. F - H2-DM-M
5–14
Chapter 5: Specifications - Discrete I/O Modules
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
D2–08TD2, DC Output
D2-08TD2 DC Output
Outputs per Module
8 (current sourcing)
Commons per Module
1
Output Type
PNP open collector
Operating Voltage
12 to 24 VDC
Output Voltage
10.8 to 26.4 VDC
Peak Voltage
40VDC
ON Voltage Drop
1.5 VDC
AC Frequency
N/A
Minimum Load Current
N/A
Max Load Current
0.3 A per point; 2.4 A per common
Max Leakage Current
1.0 mA @ 40VDC
Max Inrush Current
1A for 10ms
Base Power Required 5VDC
100mA
OFF to ON Response
1ms
ON to OFF Response
1ms
Terminal Type (included)
Removable; D2-8IOCON
Status Indicator
Logic side
Weight
2.1 oz. (60g)
Fuses
1 per common
5A fast blow, non-replaceable
ZIPLink Module
ZL-RTB20 (Feedthrough)
ZIPLink Cable
ZL-D2-CBL10 (0.5 m)
ZL-D2-CBL10-1 (1.0 m)
ZL-D2-CBL10-2 (2.0 m)
4
5
6
7
0
1
2
3
L
C
D2-08TD2
OUT
12-24
VDC
0
1
2
3
V
L
4
5
6
7
10.2-26.4VDC
0.2mA-0.3A
4
5
6
7
0
1
2
3
L
C
D2-08TD2
OUT
12-24
VDC
0
1
2
3
V
L
4
5
6
7
10.2-26.4VDC
0.2mA-0.3A