B–3
B–3
RLL Communications Programs
Data Communications Module, 2nd Edition, 2/03
This example writes 3 bytes of data from the Master Station (starting at V40600) to Y0 – Y27
in Slave Station #1.
DCM
Master PLC
Slave Address 1
Slave Address 2
15
8
0
16pt
Output
16pt
Output
Y0
-
Y17
Y20
-
Y37
V40601
V40600
Y50
Set
SP131
SP130
LD
K401
LD
K3
LDA
O40600
WX
Y0
Communication Error
Communication Not Busy
Example RLL Program
Slave
Address
D2–DCM Slot
Transfer 3 bytes
Master Starting Address
Slave Starting Address
Type of
Operation
Slot 0
CPU
Slot 1
Slot 2
Slot 3
Slot 4
The following paragraphs explain each operation and provide some helpful hints to make
your programs simple and easy to follow.