C–5
C–5
Using the D2–DCM with MODBUS
Data Communications Module, 2nd Edition, 2/03
DL250–1 Memory Type
QTY
1
(Dec.)
PLC Range
(Octal)
MODBUS
Address Range
MODBUS
Data Type
For Discrete Data Types ....
Convert PLC Addr. to Dec. + Start of Range + Data Type
Inputs (X)
512
X0
–
X777
2048
–
2560
Input
Special Relays (SP)
512
SP0
–
SP137
SP320
–
SP717
3072
–
3167
3280
–
3535
Input
Outputs (Y)
512
Y0
–
Y777
2048
–
2560
Coil
Control Relays (CR)
1024
C0
–
C1777
3072
–
4095
Coil
Timer Contacts (T)
256
T0
–
T377
6144
–
6399
Coil
Counter Contacts (CT)
128
CT0
–
CT177
6400
–
6527
Coil
Stage Status Bits (S)
1024
S0
–
S1777
5120
–
6143
Coil
For Word Data Types ....
Convert PLC Addr. to Dec. + Data Type
Timer Current Values (V)
256
V0
–
V377
0
–
255
Input Register
Counter Current Values (V)
128
V1000
–
V1177
512
–
639
Input Register
V Memory, user data (V)
3072
4096
V1400
–
V7377
V10000 – V17777
768
–
3839
4096 – 8192
Holding Register
V Memory, system (V)
320
V700
–
V777
V7400
–
V7777
448
–
768
3840 – 3735
Holding Register
Содержание D2-DCM
Страница 4: ...D2 DCM Data Communications Module Manual Number D2 DCM M...
Страница 37: ...1A Cable Diagrams...
Страница 47: ...Data Communications Module 2nd Edition 2 03 B RLL Communications Programs...
Страница 58: ...Data Communications Module 2nd Edition 2 03 C Using the D2 DCM with MODBUS...
Страница 67: ...Data Communications Module 2nd Edition 2 03 D Using the D2 DCM with Modems...