5.10.  FAULT DIAGNOSIS 

Failure description

Possible cause  

Comment 

The Trilane is not powered 
(pictogram not lit, drive 
not lit, free passage in 
both directions, etc

.) 

Remove the cover and check the 230 VAC connection and 
the position of the main circuit breaker. Check the correct 
24 VDC supply voltage. 

In the A5/B5 configuration, the de-
energised TriLane is free in both 
directions of passage. 

A pictogram is not lit

On the AS1635 circuit board, check the connection of 
the CN10 connectors (pictogram direction A) and CN11 
(pictogram direction B). 
Replace the pictograms if necessary. 

CN10(or 11)-1 red
CN10(or 11)-2 green
CN10(or 11)-3 blue 
CN10(or 11)-4 white 
CN10(or 11)-5 0V ref 

The passage 
authorisation is not taken 
into consideration

Using the HMI, check that the TriLane is not in blocked 
mode. 
Check the connection between the reader and the AS1635 
circuit board (24 VDC pulse in CN2-1 for authorisation in 
the A direction and in CN2-2 for authorisation in the B 
direction).  

Default configuration of the inputs, 
can be modified via the PC interface.  

The TriLane does not lock 
itself (in direction A or 
direction B

)

Check the programmed operating mode in direction A and 
B via the HMI (free, controlled, blocked).  
Check that the TriLane is not in Emergency mode 
(connection between CN1.3 and 4 for normal operation). 
Check the supply voltage of the electro-magnet, between 
CN5-1 and CN5-2 (direction A) or CN5-3 and CN5-4 
(direction B).  
If the electro-magnet is functioning correctly, check the 
locking mechanism 

Note: the 24 VDC voltage is only 
applied during the first moments  The 
holding voltage is reduced to prevent 
the electro-magnet from heating up. 

The turret will not re-lock 
during rotation. 

Check the operation of the angular sensor and the 
connecting cable (CN17 on the AS1635 circuit board).  

In the case of an angular sensor 
problem, an error appears on the HMI 
display.  

The TriLane does not 
operate and the LED LD1 
on the AS1635 circuit 
board is off. 

The AS1365 control circuit board is not powered with 
24 VDC. Check the 24 VDC power supply module and the 
connection cable to CN1-1 and CN1-2. 

T

he TriLane does not work 

and the LED LD6 on the 
AS1635 circuit board is off.

The program is not running. Turn off the power to 
reinitialise the program or press the Reset button (see the 
position in the technical manual of the AS1635).  
As a last resort, replace the AS1635 control circuit board.  

If the control circuit board is 
replaced, a new calibration operation 
will be required at power on. Refer to 
the unit test chapter in the AS1635 
manual. 

The horizontal arm does 
not fall in the case of 
a power failure or an 
emergency. (Dropping-arm 
option retained)  

Check the condition of the two actuating springs of the 
arm release mechanism (See the technical manual)

The motor does not 
engage (motorisation 
option retained

)

Check that the CAN bus cable W6 is connected to the CN13 
connector of the AS1635 circuit board.  
Check the connection between the motor circuit board AS 
1636 and the motor. 
If necessary, replace the motor circuit board or the gear 
motor. 

The information contained in this document is the property of Automatic Systems and is confidential. The recipient shall refrain from using this information for any purpose 
other than the use of the products or the execution of the project to which it refers and from communicating it to third parties without prior written agreement of Automatic 
Systems. The document is subject to change without notice

.

Содержание TriLane TL2

Страница 1: ...TriLane TL2 www automatic systems com TRIPOD TURNSTILE TL2 Quick Start Guide QSG Installation Instructions and Getting Started Translated from the original French version Rev 03 ...

Страница 2: ...ns on the equipment must be carried out by qualified personnel Any work on this product that is unauthorized or carried out by an unqualified technician will automatically void the manufacturer s warranty о о Access to the mechanism must be reserved for staff who are aware of the electrical and mechanical risks incurred in case of negligent handling о о For any operation that does not require the ...

Страница 3: ...ation label showing the equipment type the production date the voltage the weight and the serial number and the reference code 4 GENERAL 4 1 GENERAL CONDITIONS OF USE Your TriLane tripod turnstile has been designed to operate in any kind of climatic environment from 10 C to 50 C with up to 90 of relative humidity 4 2 PACKAGING In most cases your turnstile will be delivered in a cardboard box attac...

Страница 4: ... side and in direction B when the tripod is on his left side 4 5 LOCATION OF THE ELECTRICAL COMPONENTS 4 16 4 21 4 15 4 18 4 17 4 19 4 20 4 22 Ref Designation 04 15 Support for electronic devices 04 16 DIN rail 04 17 Power supply 24 VDC 4 A 04 18 Main switch If you open the casing turn off the equipment by switching off the main switch 04 19 Earth terminal 04 20 Terminal block stop 04 21 Protectiv...

Страница 5: ...ools Flat spanner set Set of Allen keys Spirit level Hammer drill concrete drill bit Ø 15 x 100 Standard protective equipment gloves goggles hard hat and safety shoes 5 2 PRELIMINARY WORK The turnstile has been specially packaged for transport Bring the material to the installation site with the help of a forklift truck and remove the packing material Unlock the locks 4 10 and open the cover 4 4 T...

Страница 6: ...h right or left end box EXPANSIBLE ANCHOR B15 30 3413 000 Suggested reference M10 Ø 60 mm PVC SHEATH Concrete Wiring to provide for 230 V single phase power supply ground in 3G2 5 IP CABLE Ethernet STP CAT 5 Dimensions according to standard Automatic Systems anchoring The information contained in this document is the property of Automatic Systems and is confidential The recipient shall refrain fro...

Страница 7: ...ly Ensure that the turnstile remains firmly fixed to the ground by tightening the expandable dowels Ensure that the cables can pass through Make sure that all the housings of the battery are perfectly aligned and horizontal If needed add shims between the housings and the floor to ensure that they are perfectly level 5 6 INSTALLING THE STAINLESS STEEL ARM VERSION WITH FIXED ARMS 5 1 4 6 5 2 L O C ...

Страница 8: ... 2 Install and lock the cover Fig 4 page 5 4 4 Check the functionalities Pictograms locking mechanism fraud detection performing a few passages in both directions The tripod turnstile is now operational All the settings have been made in the factory at the time of the working tests Some additional adjustment could nevertheless be necessary as a result of transport or handling during assembly In su...

Страница 9: ...retain the surface appearance and avoid any oxidation deposits or marks it is strongly recommended to regularly treat the stainless steel surface with a product specially designed for this purpose Automatic Systems can provide an approved product under reference 6031 000 Automatic Systems reserves the right to deny warranty coverage in the case of an apparent lack of maintenance The information co...

Страница 10: ...ctro magnet from heating up The turret will not re lock during rotation Check the operation of the angular sensor and the connecting cable CN17 on the AS1635 circuit board In the case of an angular sensor problem an error appears on the HMI display The TriLane does not operate and the LED LD1 on the AS1635 circuit board is off The AS1365 control circuit board is not powered with 24 VDC Check the 2...

Страница 11: ...atic systems com Tel 32 10 23 02 27 Fax 32 10 86 22 90 Belgium Wallonia Brussels Tel 32 70 22 44 66 Fax 32 10 86 22 90 Email helpdesk be automatic systems com Belgium Flanders Tel 32 70 22 44 66 Fax 32 3 88 700 76 Email dnv be automatic systems com Canada Tel 1 450 659 0737 Fax 1 450 659 0966 Email helpdesk nam automatic systems com China Tel 86 512 5383 0561 Email helpdesk cn automatic systems co...

Отзывы: