background image

Revised 4/27/00 • UNI/16

4

© 2000 Automated Logic Corporation

Connecting the UNI/16 to the U-Line 
modules

The UNI/16 supports up to 16 U-Line 
modules. The baud rate of the Unet is set on 
the module driver Parameter page. Refer to 
the 

U1M Module Driver

 document for more 

information.

Automated Logic Corporation recommends a 
specific wire for both power and 
communications on the Unet. This wire, 
which contains a pair of 14AWG wires for 
power and a pair of 22AWG wires for 
communication, is available from:

Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
Product number A3U-LINE

Note that the communication wire is 
unshielded. Shielded cable is not required for 
the Unet.

Use the Unet connection port to connect the 
UNI/16 to the U-Line modules. The Unet 
connection port can make two connections to 
the Unet, as shown in Figure 3. Make sure the 
Unet connection port configuration jumpers 
are set to UNI and EIA-485 (see Figure 4). 

Make sure that all U-Line modules and the 
TNPB use the same polarity throughout the 
subnet. You can verify that the UNI/16 is 
communicating with the subnet by making 

sure the Unet transmit and receive LEDs are 
active.

When adding a new U-Line module to an 
existing subnet, you must transfer memory to 
the UNI/16 before the new card is recognized.

Connecting the UNI/16 to the CMnet

When communicating on an ARC156 CMnet, 
use an A3ARC156 wire available from 
Magnum Cable Corp. Use a dedicated 22AWG 
to 18AWG twisted pair wire for legacy CMnet 
(EIA-485) wiring. For more information about 
CMnet wiring, refer to the 

Technical Handbook

 

or to the 

ARC156 CMnet Wiring Technical 

Instructions.

To set the baud rate at 156 kbps (when using 
an ARC156 CMnet), set the baud rate jumper 
to Arc156 (see Figure 5 on page 5).

To set the baud rate at 38.4 kbps, set the baud 
rate jumper to 9600/38.4K, and set the first 
switch on the eight-position DIP switch to 
38.4K (see Figure 6 on page 5).

To set the baud rate at 9600 bps, set the baud 
rate jumper to 9600/38.4K, and set the first 
switch on the eight-position DIP switch to 
9600 (see Figure 6).

You can verify that the UNI/16 is 
communicating on the CMnet by making sure 
the CMnet transmit and receive LEDs are 
active.

 Figure 3. Communication wiring 

NET+
NET -

NET+

NET-

NET+
NET-

   

   

 Figure 4. Unet configuration jumpers

N /C

E IA-48 5

U N I

N /C

N /C

Содержание UNI/16

Страница 1: ...tomated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions UNI 1 6 Using the UNI 16 2 S...

Страница 2: ...7 2VA power consumption single Class 2 source only 100VA or less Communication One EIA 232 port for diagnostics 9600 bps or 38 4 kbps two EIA 485 ports for Unet communication 9600 bps or 38 4 kbps on...

Страница 3: ...connections to U Line modules on the Unet You can connect an optional BACview1 or BACview2 keypad display unit to the keypad display port see Figure 2 NOTE The EIA 232 port labeled Diag Port in Figure...

Страница 4: ...t the UNI 16 is communicating with the subnet by making sure the Unet transmit and receive LEDs are active When adding a new U Line module to an existing subnet you must transfer memory to the UNI 16...

Страница 5: ...t be made using the Zone GFB option in Eikon Refer to the Eikon User s Guide for more information To transfer GFBs to the UNI 16 you must use SuperVision version 2 6b or later software and you must us...

Страница 6: ...ll equipment has power and is turned on Some devices especially communication devices receive power from a source other than a power cable or adapter for example some devices receive power through com...

Страница 7: ...CMnet Tx lights when the module transmits data over the CMnet CMnet Rx lights when the module receives data from the CMnet Unet receive lights when the module receives data from the Unet Unet transmi...

Страница 8: ...port for the module in SuperVision Refer to the SuperVision User s Guide for more information about the module status report A sticker on the back of the module also shows the date the module was manu...

Отзывы: