background image

Revised 4/27/00 • UNI/16

5

© 2000 Automated Logic Corporation

Addressing

The UNI/16 has an eight-position DIP switch 
for assigning the module’s CMnet address. 
Before setting or changing the address, make 
sure the UNI/16’s power is off, since the 
UNI/16 only reads the address when the 
module is turned on. After changing the 
address, you must transfer memory to the 
module. Refer to the section “Transferring 
Memory”
.

Switches two through eight of the DIP switch 
are labeled with addressing values. The 
values of the switches in the on position are 
added together to determine the module’s 
address. For example, in Figure 7 switch 
numbers six and seven are both on, giving the 
module an address of six.

Transferring Memory

The UNI/16 module can store the U1M 
module driver and up to 16 Graphic Function 
Blocks (GFBs), depending on the size of the 
GFBs. All GFBs stored in the UNI/16 must be 
made using the Zone GFB option in Eikon. 
Refer to the 

Eikon User’s Guide

 for more 

information.

To transfer GFBs to the UNI/16, you must use 
SuperVision version 2.6b or later software, 
and you must use FBLINK version 2.7a or 
later. For more information about using 
SuperVision, refer to the 

SuperVision User’s 

Guide

.

The first memory transfer to the UNI/16 takes 
longer than subsequent memory transfers.

1. Connect your workstation or portable 

computer to the UNI/16. Refer to 
“Communicating with the Workstation” on 
page 6
.

2. Navigate to the module driver and look at 

the module status report in SuperVision to 
make sure the module type and number 
agree with the module.

• To view the module status report in 

SuperVision v3.0, click Tools-
Troubleshooting-Module Status.

• To view the module status report in 

SuperVision v2.6b, press the Esc key, 

 Figure 5. Setting the CMnet baud rate to 156 

kbps

 Figure 6. Setting the CMnet port baud rate to 

38.4 kbps or 9600 bps

 

 

  





38.4k

 Figure 7. Setting the module’s address

CM ne t B a u d 96 0 0

O FF

O N

32

16

8

4

2

1

On

3 8.4 k

C Mn e t
A dd re ss
(M o d u le )

64

Содержание UNI/16

Страница 1: ...tomated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions UNI 1 6 Using the UNI 16 2 S...

Страница 2: ...7 2VA power consumption single Class 2 source only 100VA or less Communication One EIA 232 port for diagnostics 9600 bps or 38 4 kbps two EIA 485 ports for Unet communication 9600 bps or 38 4 kbps on...

Страница 3: ...connections to U Line modules on the Unet You can connect an optional BACview1 or BACview2 keypad display unit to the keypad display port see Figure 2 NOTE The EIA 232 port labeled Diag Port in Figure...

Страница 4: ...t the UNI 16 is communicating with the subnet by making sure the Unet transmit and receive LEDs are active When adding a new U Line module to an existing subnet you must transfer memory to the UNI 16...

Страница 5: ...t be made using the Zone GFB option in Eikon Refer to the Eikon User s Guide for more information To transfer GFBs to the UNI 16 you must use SuperVision version 2 6b or later software and you must us...

Страница 6: ...ll equipment has power and is turned on Some devices especially communication devices receive power from a source other than a power cable or adapter for example some devices receive power through com...

Страница 7: ...CMnet Tx lights when the module transmits data over the CMnet CMnet Rx lights when the module receives data from the CMnet Unet receive lights when the module receives data from the Unet Unet transmi...

Страница 8: ...port for the module in SuperVision Refer to the SuperVision User s Guide for more information about the module status report A sticker on the back of the module also shows the date the module was manu...

Отзывы: