background image

Revised 4/27/00 • UNI/16

6

© 2000 Automated Logic Corporation

type

 MO  , , module address,15 

and press Enter.

3. Transfer memory to the module.

• In SuperVision v3.0, click Tools-

Troubleshooting-Transfer Memory to 
Module.

• In SuperVision v2.6b, choose Download 

Memory for This Module.

4. When the memory transfer is finished, 

check the module status report again. 
Make sure the FB List on this page shows 
all the FBs you intended to transfer.

Using Flow Sensors

The UNI/16 supports U-Line modules that use 
flow sensors. You must calibrate each sensor 
to ensure accurate readings. Use the 
calibration instructions on the Parameter 
page of each FB that uses a flow sensor. You 
must indicate on the U1M’s Parameter page 
(in the U-Card Flow Control section) how air 
flow is controlled by each U-Line module. 
Refer to the 

U1M Module Driver 

document

 

for 

details.

Troubleshooting Tips

If you are having trouble communicating with 
the UNI/16, check these items before 
contacting Technical Support.

• Make sure the U-Line wiring is correct. 

In more complex systems, make sure 
that all cables involved are attached 
correctly.

• Make sure the UNI/16 and the U-Line 

modules have power and are turned on. 
In more complex systems, make sure all 
equipment has power and is turned on. 
Some devices, especially 
communication devices, receive power 
from a source other than a power cable 
or adapter (for example, some devices 
receive power through communication 

lines). Some panels can be reinitialized 
by resetting the panel.

• Make sure the module driver and all 

GFBs are transferred into the module. 
You can verify this by checking the 
module status page for the UNI/16 
module.

• Make sure the module driver 

parameters and the parameters for each 
GFB are set up properly in SuperVision. 

Communicating with the Workstation

You can connect a workstation or portable 
computer directly to the UNI/16 module using 
an APT and the module’s Access port (see 
Figure 8). This type of connection can be used 
to troubleshoot the module or transfer 
memory.

The baud rate of the Access port is 
determined by the first switch on the eight-
position DIP switch (see Figure 7 on page 5). If 
you need to change the switch’s position, turn 
the UNI/16 module off first. Once you have 
adjusted the switch, turn the module back on.

1. Connect the computer’s serial port to the 

EIA-232 port of the APT using a standard 
straight-through serial cable.

2. Set the APT’s Mode Select switch.

• On an ARC156 CMnet, use the TTL 

setting.

 Figure 8. Using the Access Port

9

Rx

6 1

2- Tx   out
3- Rx i n
5- Gnd
1,6,8- +10V  or floating

Tx

+5V

A P T

5

Exec. 4 relay

Isolate Network

Mode Select

TTL

485

ACCESS

PORT

 

 

   

 

Содержание UNI/16

Страница 1: ...tomated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions UNI 1 6 Using the UNI 16 2 S...

Страница 2: ...7 2VA power consumption single Class 2 source only 100VA or less Communication One EIA 232 port for diagnostics 9600 bps or 38 4 kbps two EIA 485 ports for Unet communication 9600 bps or 38 4 kbps on...

Страница 3: ...connections to U Line modules on the Unet You can connect an optional BACview1 or BACview2 keypad display unit to the keypad display port see Figure 2 NOTE The EIA 232 port labeled Diag Port in Figure...

Страница 4: ...t the UNI 16 is communicating with the subnet by making sure the Unet transmit and receive LEDs are active When adding a new U Line module to an existing subnet you must transfer memory to the UNI 16...

Страница 5: ...t be made using the Zone GFB option in Eikon Refer to the Eikon User s Guide for more information To transfer GFBs to the UNI 16 you must use SuperVision version 2 6b or later software and you must us...

Страница 6: ...ll equipment has power and is turned on Some devices especially communication devices receive power from a source other than a power cable or adapter for example some devices receive power through com...

Страница 7: ...CMnet Tx lights when the module transmits data over the CMnet CMnet Rx lights when the module receives data from the CMnet Unet receive lights when the module receives data from the Unet Unet transmi...

Страница 8: ...port for the module in SuperVision Refer to the SuperVision User s Guide for more information about the module status report A sticker on the back of the module also shows the date the module was manu...

Отзывы: