background image

 

SE6166 Controller • Rev. 4/13/2011 

© 2011 Automated Logic Corporation 

 

Analog outputs 

6 analog outputs, 0–10 Vdc or 0–20 mA selectable 

Output resolution 

8 bit D/A 

Microprocessor 

High speed 16-bit microprocessor with ARCNET 

communication co-processor 

Memory 

1 MB non-volatile battery-backed RAM, 1 MB Flash memory, 

16-bit memory bus 

Real-time clock 

Battery-backed real-time clock keeps track of time in event 

of power failure 

Battery 

10-year Lithium CR2032 battery provides a minimum of 

10,000 hours of data retention during power outages 

Protection 

Incoming power and network connections are protected by 

non-replaceable internal solid-state polyswitches that reset 

themselves when the condition that causes a fault returns to 

normal. The power, network, input, and output connections 

are also protected against voltage transient and surge 

events. 

BT485 connector 

You attach a BT485 (not included) to a controller at the 

beginning and end of a network segment to add bias and to 

terminate a network segment. 

Status indicators 

LED's indicate status of communications, running, errors, 

power, and digital outputs 

Environmental operating 

range 

-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-

condensing 

NOTE

  The controllers should be mounted in a protective 

enclosure. 

Physical 

Rugged aluminum cover, removable, screw-type terminal 

blocks 

Overall dimensions 

Width: 

Height: 

8 5/16 in. (21.1 cm) 

7 in. (17.8 cm) 

Mounting dimensions 

Width: 

Height: 

7 7/8 in. (19.9 cm) 

5 in. (12.7 cm) 

Recommended panel 

depth 

1 1/2 in. (3.8 cm) 

Weight 

1.2 lbs (0.5 kg) 

BACnet support 

Conforms to the Advanced Application Controller (B-AAC) 

Standard Device Profile as defined in ANSI/ASHRAE 

Standard 135-2004 (BACnet) Annex L  

Listed by 

UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-

Class A, CE EN50082-1997 

  
 
 
 
 

 

Содержание SE6166

Страница 1: ...hat you have the most current version of this document Go to http accounts automatedlogic com then select Support Download Documents Technical Instructions SE6166 Controller Technical Instructions Rev 4 13 2011 ...

Страница 2: ...puts 7 Wiring specifications 7 To wire inputs and outputs 8 Wiring a room sensor to the SE6166 10 Rnet wiring specifications 10 To wire an RS sensor 11 LogiStat wiring specifications 11 To wire a LogiStat sensor 11 Downloading the SE6166 12 To download in WebCTRL 12 To assign inputs or outputs to points 13 Input values 13 Output values 14 Resolution values 15 Offset Polarity values 15 To use the A...

Страница 3: ...al inputs NOTE The SE6166 does not support the LogiStat Pro Use an RS Pro on the Rnet port instead Rnet port Supports up to four RS Standard sensors and one RS Plus RS Pro or RS Pro F sensor for averaging or high low select control The sensors can share the Rnet port with a BACview5 or BACview6 NOTE If you use the Rnet port you cannot connect a LogiStat sensor to the LogiStat port Inputs 16 inputs...

Страница 4: ...tions are also protected against voltage transient and surge events BT485 connector You attach a BT485 not included to a controller at the beginning and end of a network segment to add bias and to terminate a network segment Status indicators LED s indicate status of communications running errors power and digital outputs Environmental operating range 20 to 140 F 29 to 60 C 10 90 relative humidity...

Страница 5: ...nput voltages should be from 0 6 1 2 V NOTE ALC recommends use of an external current transducer between an RTD and the SE6166 IN 1 IN 2 Pulse counter2 Pulse counting up to 40 pulses per second Minimum pulse width on or off time required for each pulse is 12 5 msec IN 1 IN 2 Timed local override A momentary contact switch that overrides a schedule and turns equipment on for a defined period of tim...

Страница 6: ...l access If you use the Rnet port you cannot connect a LogiStat sensor to the LogiStat port You can wire a BACview5 or BACview6 keypad display unit to the Rnet port of the SE6166 to view or edit some of its property values or its real time clock See Room sensors above for Rnet configurations See the BACview5 Hardware Setup Guide http accounts automatedlogic com or BACview6 Hardware Setup Guide htt...

Страница 7: ...Vac 4 Connect the transformer wires to the screw terminal connector 5 Apply power to the transformer 6 Measure the voltage at the SE6166 s power input terminals to verify that the voltage is within the operating range of 21 6 26 4 Vac 7 Insert the screw terminal connector into the SE6166 s power terminals 8 Turn on the SE6166 s power 9 Verify that the Power LED is on and the Run LED is blinking Yo...

Страница 8: ...sted stranded shielded copper wire 2000 feet 610 meters 1 See the ARC156 Wiring Technical Instructions http accounts automatedlogic com download 2 See the MS TP Networking and Wiring Technical Instructions http accounts automatedlogic com download 1 Turn off the SE6166 s power 2 Check the communications wiring for shorts and grounds 3 Connect the communications wiring to the controller s screw ter...

Страница 9: ...2 AWG Shielded RTD 100 feet 30 meters 22 AWG Shielded RS sensor LogiStat sensor See Wiring a room sensor to the SE6166 page 10 NOTE ALC recommends use of an external current transducer between an RTD and the SE6166 Output wiring To size output wiring consider the following Total loop distance from the power supply to the controller and then to the controlled device NOTE Include the total distance ...

Страница 10: ...V Any input Volts Volts Volts Volts Volts Volts mA mA mA mA mA mA 10 kOhm thermistor 1 kOhm RTD n c 4 wire 2 wire 3 wire 4 wire Out Out Gnd V Gnd Any input Out V Gnd Out V n c Out Out V Gnd 0 5 Vdc 0 10 Vdc or 4 20 mA 0 5 Vdc 0 10 Vdc or 4 20 mA 0 5 Vdc 0 10 Vdc or 4 20 mA 0 5 Vdc 0 10 Vdc or 4 20 mA 0 5 Vdc 0 10 Vdc or 4 20 mA 0 5 Vdc 0 10 Vdc or 4 20 mA or or or or or or NOTES Connect the shield...

Страница 11: ...input s Universal Input Mode Select jumper to the type of signal the input will receive Jumpers for inputs 1 3 5 7 9 11 13 15 2 4 6 8 10 12 14 16 Aux Power Out connector Loop powered 4 20 mA Set the Select jumper to 5V or 24V as required by the sensor 5 Connect the digital output wiring to the screw terminals on the SE6166 and to the controlled device 24 Vac dc Motor Valve Any DO Any DO Any DO ...

Страница 12: ... can wire An RS Standard RS Plus RS Pro or RS Pro F to the SE6166 s Rnet port A LogiStat or LogiStat Plus to the SE6166 s Lstat port See the following sections for wiring instructions For other details see the RS Room Sensors Technical Instructions or the LogiStat Sensors Technical Instructions NOTE Use the specified type of wire and cable for maximum signal integrity Description 4 conductor shiel...

Страница 13: ...6 cm 4 Strip about 25 inch 6 cm of the inner insulation from each wire 5 Wire each terminal on the SE6166 s Rnet port to the terminal of the same name on the RS room sensor NOTE If using shielded wire connect the shield wire and the ground wire to the Gnd terminal 6 Set the Stat Select jumper to Rnet 7 Turn on the SE6166 s power Use 22 AWG unshielded wire maximum length 100 feet 30 meters 1 Turn o...

Страница 14: ...d data when you download Equipment controlled by the SE6166 will shut down and restart when you download You download the controller from WebCTRL If your network is complete you can download from any network browser If not complete connect a laptop with a local copy of the system database to the SE6166 s local access port See To communicate through the local access port page 20 1 On WebCTRL s NET ...

Страница 15: ...to the SE6166 you must download now so you can verify inputs and outputs 6 To verify each input s operation force each sensor to a known value then compare it to the Value shown on the Properties page on the I O Points tab 7 To verify each output s operation lock each output to a known condition on the I O Points tab then verify that the equipment operates correctly Input I O Type Sensor Actuator ...

Страница 16: ...he control program must have one Pulse to Analog Input microblock for each pulse counting input Output I O Type Sensor Actuator Type Min Max Analog BAO 0 10 Vdc Electrical 0 10 Volt Linear Full Range Engineering values associated with 0 Vdc Min and 10 Vdc Max 1 2 10 Vdc Electrical 0 10 Volt Linear w Offset 2 10 Volts Engineering values associated with 2 Vdc Min and 10 Vdc Max 1 0 20 mA Electrical ...

Страница 17: ...iately you should understand how the driver uses them Offset Polarity Notes Analog Input BAI Offset value positive or negative adds a fine adjustment to a sensor reading after all scaling for calibration EXAMPLE If a sensor reads 74 9 F when the actual measured value is 73 6 F enter an Offset of 1 3 to calibrate the sensor to the measured value Analog Output BAO You can use the Offset value positi...

Страница 18: ...nt to monitor After you download the driver and control program s to the SE6166 you may want to change the driver s properties to suit your application 1 On WebCTRL s NET tree click to the left of your SE6166 2 Click to the left of Driver to see its children 3 Make changes as needed on the Properties page for Driver and any of its children On the Driver page you can change the following properties...

Страница 19: ...l circumstances COV Throttling should be enabled to prevent excessive network traffic if an object s COV Increment is set too low See EXCEPTION below When enabled if an object generates excessive COV broadcasts 5 updates in 3 seconds the driver automatically throttles the broadcasts to 1 per second Also if the object s value updates excessively for 30 seconds an alarm is sent to WebCTRL listing al...

Страница 20: ... controller acknowledgement for each message type Normally not required TIP To require operator acknowledgement for an Alarm or Return to normal message stored in the WebCTRL database change the acknowledgement settings on WebCTRL s Alarm Enable Disable tab for an alarm source or an alarm category Recipient List Recipients The first row in this list is the WebCTRL Server Do not delete this row Cli...

Страница 21: ...larm is generated Events Alarm Category and Alarm Template See Customizing alarms in WebCTRL Help Enable Clear these checkboxes to disable Alarm or Return to normal messages of this type from this controller Notification Class Do not change this field You can set up a translation table that an analog input will use to translate the raw data from a non linear sensor to the engineering units you wan...

Страница 22: ...erence between the controller s ground and the computer s AC power ground could damage the USB Link Kit and the controller If you are not sure of the wiring polarity use a USB isolator between the computer and the USB Link Kit Purchase a USB isolator online from a third party manufacturer Connect the USB Link Kit to the computer and to the controller s Local Access port Connect to computer s USB p...

Страница 23: ...may be open and is holding the port open 11 On the NET tree select the controller that you are connected to 12 Click the menu button then select Manual Command 13 Type rnet here in the dialog box then click OK 14 On the Properties page click Module Status If WebCTRL displays a Modstat report WebCTRL is communicating with the controller If you have problems mounting wiring or addressing the SE6166 ...

Страница 24: ...ond 3 flashes then off The controller has just been formatted 2 flashes per second 4 flashes then pause Two or more devices on this network have the same ARC156 network address 2 flashes per second 1 flash per second The controller is alone on the network 2 flashes per second On Exec halted after frequent system errors or control programs halted 5 flashes per second On Exec start up aborted Boot i...

Страница 25: ... minimum of 10 000 hours of data retention during power outages If the SE6166 sends a Low Battery alarm to WebCTRL replace the battery 1 Remove the battery from the controller making note of the battery s polarity 2 Insert the new battery into the controller matching the polarity of the battery you removed 3 Download the SE6166 If needed for troubleshooting or start up you can prevent WebCTRL Serv...

Страница 26: ...ly to cause harmful interference in which case the user will be required to correct the interference at his own expense CAUTION Changes or modifications not expressly approved by the responsible party for compliance could void the user s authority to operate the equipment WARNING This is a Class A product In a domestic environment this product may cause radio interference in which case the user ma...

Страница 27: ...cuits Interconnect the Outputs of R TYPE 002104 Volts Run 38 4k 9600 19 2k 88F0 E143900 76 8k Management Equipment Open Energy BACnet Mode ARC156 MSTP 3 DO 1 1 2 DO 2 5 4 24V Max 3A Max To Reduce The Risk of Fire 6166 SE CAUTION Outputs DO 6 DO 4 8 7 6 DO 5 10 11 9 Tx Rx Net BT485 12 BACnet Shield Net Aux Power Out Gnd 24V 5V Select Conductors Only Use Copper 20VA 0 83A 24 Vac 50 60 Hz BACnet Over...

Отзывы: