Installation Manual 

 SDU 404 

 

Page 4  

 

Wiring 

Follow these wiring guidelines. 

24VDC Supply 

Connect 24VDC to terminals 1 

(positive) and 2 (0V). Connect a ground 

connection to terminal 3. 

Wire Requirement 

SDU supply wires shall have a minimum 

area of 1.0 mm

2

Switch Channels 

Switch Channels are configurable for 

loop monitoring and short circuit. 

All switch channels use a two-wire 

layout, where both wires from the 

switch are to be routed to the SDU. 

Wire Requirement 

Switch wires shall have a minimum area 

of 0.5 mm

2

Broken Wire Detection 

Requirement for type approved 

installations. Each switch shall have a 

10k resistor connected across.  

Note! The 10k resistors shall be 

connected directly 

at the switch

and not at the SDU 404. 

Switches shall be normally open (NO), 

and shall close to indicate engine 

shutdown.  

Short Circuit Detection 

Each switch shall have a 10k resistor 

connected in series.  

Note! The 10k resistors shall be 

connected directly 

at the switch

and not at the SDU 404. 

Pickup Channel 

The SDU can operate with a magnetic 

or active pickup source.  

Connect the pickup to terminals 4 and 

5, with shield to terminal 3.  

Note! Make sure the cable shield is 

connected at the SDU side and 

not at the pickup side. 

Shutdown Override 

This is to be wired exactly like a Switch 

Input, that is; it shall be a normally 

open switch.  Close the switch to 

activate Shutdown Override.  

Note! Make sure a 10k resistor is 

connected across the switch. 

 

 

 

Содержание SDU 404

Страница 1: ...Manual 1100413 Installation Manual SDU 404 Shutdown Unit...

Страница 2: ...based on former QIG 1 1 21 03 16 Added Appendix A and minor updates 1 2 11 08 17 Added DCU 210E 208E to the DCU Communication terminals table Copyright 2017 by Auto Maskin AS All rights reserved No pa...

Страница 3: ...ine Control Unit 2 RP 410 210E Remote Panel 2 Ethernet Switch 2 Expansion 2 INSTALLATION 3 GENERAL 3 LED Overview 3 WIRING 4 24VDC Supply 4 Switch Channels 4 DCU COMMUNICATION 5 BUTTONS 5 Acknowledge...

Страница 4: ...installation work is carried out in a satisfactorily manner that it is operationally in good order that the approved material and accessories are used and that the installation meet all applicable ru...

Страница 5: ...action is also here RP 410 210E Remote Panel The optional RP remote panel brings the DCU display to a remote location with no need for any configuration Ethernet Switch It s recommended to always us a...

Страница 6: ...has a brief description LED Description Power Lit when power supply is OK Flashing when below the configurable very low threshold Green Running Lit when engine is running Green Overspeed Unacknowledge...

Страница 7: ...tor connected across Note The 10k resistors shall be connected directly at the switch and not at the SDU 404 Switches shall be normally open NO and shall close to indicate engine shutdown Short Circui...

Страница 8: ...meters The Baud rate is 19200 baud 8 data bits 1 stop bit Even parity Configuration Mismatch Warning When the SDU is connected to the DCU the DCU will analyze the configuration in the SDU and compare...

Страница 9: ...ersion This page give the information about the hardware and software version of the SDU 404 Speed Sensor This page has the configuration of the pickup channel Switch This page has the configuration f...

Страница 10: ...met Speed Limit Enabled Set if Speed limit is enabled or not The actual engine speed is set in the Speed limit RPM section Speed Limit RPM If the engine speed is above the set value then the channel...

Страница 11: ...Installation Manual SDU 404 Page 8 Appendix A Wiring The diagram below shows recommended wiring including 3 different types of Switch inputs...

Страница 12: ...Installation Manual SDU 404 Page 9 Appendix B Front Front side and Connectors DCU Link Switch input 1 4 Shutdown Override Acknowledge Power Supply MPU Input Shutdown Relay 1 2 Config...

Отзывы: