SUSPENSION BRACKET
FLAT CEILING INSTALLATION
·
The bracket must be structurally secured within the roof as
shown in the diagram
·
The largest cylinder must protrude down from the ceiling by
at least 1͈ unless the ceiling is made from a non-combustible
material such as concrete.
·
You must leave a 1͈ clearance gap between the bracket and the
ceiling. This gap will be covered by the ceiling cover plate.
·
1/2͈ ventilation gap between the plasterboard and the ceiling
cover plate.
·
1/2͈ minimum clearance from the insulated flue to any
combustible material within the roof space.
»
CEILING
CEILING COVER
PLATE
1
̎
MINIMUM
BELOW CEILING
1
̎
MINIMUM
CLEARANCE