After  completing  the  programming  of  the  whole  week  of  pump 
operation,  the  user  should  program  the  pump  operation  in
a selected hour (active [lit] rectangle ).

1. Remain in "

Hot water circuit

" (

), mode 

 use controller 

(up  &  down),  to  select  the  pump  operation  in  a  given  hour 
(bottom of the screen).

2. Settings cover two parameters.

-  pump operation time
-  pump stoppage time

[wiat]

[KO]

3. Use controller 

(up & down, left & right) to select "operation time" icon

nd 

confirm it by pressing

button. 

Now it is possible to set the "operation time” of the pump in minutes - use 

 (up 

& down). After this value  is set, confirm it by pressing 

button.

4. Then use  controller 

 (left & right) to set the "stoppage time" 

 and confirm it  by 

pressing 

Now it is possible to set the "stoppage time” of the pump in minutes - use 

controller 

(up & down). After this value is set, confirm it by pressing 

5. Now operation parameters of the circulation pump in the selected hour are set (active 

rectangle).

[KO]

 [KO] 

[KO]

[KO] 

[KO]

[troj]

[KO] 

[KO] 

[KO] 

 

a

[troj]   

b

button. 

utton. 

OK

OK

OK

OK

Hot water circuit
MO
TU
WE
TH
FR
SA
SU

5[min]

10[min]

Setting pump operation time

2. Use controller 

 (up & down), to select a day of the week and 

confirm it by pressing 

button.

.

[ko]

[ko] 

[ko] 

[ko]

[ko] 

[KO]

[KO]

3. To  set  operating  hours  for  the  pump  activate/inactivate 

rectangles  at  the  time  line  –  (activated  rectangle  –  the  pump 
works; inactivated the pump is turned off).
Rectangles are activated (lit) by the controller’s   up arrow 
and inactivated by its down arrow 

 

The hour  (0:00 - 24:00) is selected by the controller’s  

left-

right arrows. After selecting each hour activate/inactivate the 
respective rectangle at the time line .

4. After completing the settings for the whole day, confirm it by 

pressing 

 button and proceed to the next day use controller’s 

 up/down arrows. Proceed similarly to the previous day.

Hot water circuit
MO
TU
WE
TH
FR
SA
SU

5[min]

10[min]

Hot water circuit
MO
TU
WE
TH
FR
SA
SU

5[min]

10[min]

OK

OK

10

11

Copying time line settings from one day to another 

An example of programmed timeline for pump operation from Monday to 
Sunday. 

Day

     Pump operating hours

Monday

6:00 – 8:00; 1

5

:00 – 23:00

T

uesday

6:00 – 8:00;  1

5

:00 – 23:00

6:00 – 8:00;  1

5

:00 – 23:00

6:00 – 8:00;  1

5

:00 – 23:00

F

riday

6:00 – 8:00;  15:00 – 23:00

Saturday

8:00 – 23:00

Sunday

8:00 – 23:00

W

ednesday

Thursday

In order to speed up the programming of the whole week, settings 
of one day of the week may be copied to another. 

(e.g.  the  time  line  form  Monday  bay  be  copied  for  Tuesday, 
Wednesday, Thursday and Friday)

To copy the time line forma day of the week, proceed as follows: 
1.  Use controller

up & down), to select a day of the week  to be 

copied 

(e.g. Monday)

 and confirm it by pressing

button.

 

 (

 

2. After that, changes may be introduced to the time line (but they 

are not necessary). Press again 

button. The time line of the 

selected day is copied to the memory of the device. It is indicated 
by a green frame around the copied day.

3.  To paste the copied time line to another day – use controller 

(up & down) to select the day where the time line is to be pasted 

(e.g.  Tuesday)

  and  confirm  it  by  pressing 

button 

for approx. 

2 sec

. Acoustic signal will confirm pasting the time 

line. 

4. Pasting (sec. 3) may be repeated for the next days of the week.

NOTE: 

Green frame indicates that the selected time line remains 
in the memory of the device.

[ko]

[ko] 

[KO]

[ko] 

[ko]

OK

OK

Hot water circuit
MO
TU
WE
TH
FR
SA
SU

5[min]

10[min]

Hot water circuit
MO
TU
WE
TH
FR
SA
SU

5[min]

10[min]

Hot water circuit
MO
TU
WE
TH
FR
SA
SU

5[min]

10[min]

OK

Содержание AURATON 8000

Страница 1: ...Owner s manual www auraton pl 8000 AURATON 8000 ...

Страница 2: ...ystem It provides information about the window position to the controller The handle recognizes 4 window positions open closed pivotedandtrickle ventposition microventilation The handle transmits information to AURATON 8000 controller which activates the relay e g switching off a heater after opening the window or reducing temperature by 3 C when the window is pivoted inordertosaveenergy AURATON80...

Страница 3: ...ntral heating pump and a potential free outputthatmaybeusedforcontrollingcentralheatingfurnace AURATON 8000 communicates with wireless transmitters using modern transmission protocolLMS Description of AURATON 8000 Button of hot water circulation pump Multi functional controller left right up down OK button OK LCD display ON OFF button Button cover Buttons of heating zones 1 8 LED signalling ON OFF...

Страница 4: ...dbemadewithdisconnectedpower supply Central heating pump Power supply 230V 50HZ Terminal for hot utility water circulation pump Potential free relay contacts Terminals for heating zones head P c A ź ź ź N N N Mounting the controller The controller may be mounted on a wall using two fixing screws rawplugs with screws are providedwiththecontroller Cablesofthecontrollershallbefixedtothewallwithbracke...

Страница 5: ... user adds T 2 thermometer to the paired channel the actual temperature will be read from T 2 thermometer whereas only the set temperature will be read from the thermostat This allows the user to control the temperatureinaroomotherthantheroom wherethermostatisinstalled NOTE In the configuration with thermostat and T 2 thermometer it is important to keep the correct order of pairing the devices Alw...

Страница 6: ...tructions on activating pairing modeinaselecteddeviceisinitsmanual 3 Correct pairing of a LMS device is confirmed by a 1 second acousticsignal 4 When the button of the zone in pairing mode is shortly pressed thenthe pairing modeisturnedoff 5 Whenthe pairing modeisturnedoffinallzones A8000enters themodeofnormaloperation NOTE The pairing mode is automatically switched off 60 seconds after the last z...

Страница 7: ...D forselectedzonestopsblinking itmeansthatallLMSdevicesinthatzonehave beencorrectlydeleted When a LED of any zone continues to blink after deleting process it means that the controllerwaitsfordeletingotherLMSdevices NOTE Deletingprocessinselectedzoneturnsoffautomaticallyafter60s Deleting wireless devices LMS from a zone In order to delete all LMS from AURATON 8000 proceed as follows 1 PressON OFFb...

Страница 8: ...elayturnedoff LEDactiveat10 Central heating pump detected but turned off relayturnedoff LEDactiveat100 Centralheatingactive relayturnedon LEDinactive The heating zone has no LMS device paired no regulation head is connected to the connection witharespectivenumber LEDactiveat10 The heating zone has a LMS device paired and a regulationheadisconnected heatingisturnedoff LEDactiveat100 The heating zon...

Страница 9: ...ensure correct operation weekly programming it is necessary to pair at least one regulator with a clock e g AURATON 2025 RTH or AURATON2030RTH When only 24 h regulators without a clock e g AURATON 200 are paired then the pump operates only in interval mode operating time and break time may be programmed Hot water circuit MO F TU WE TH R SA SU 5 min 10 min Controlling the circulation pump in hot ut...

Страница 10: ... of the whole week settings ofonedayoftheweekmaybecopiedtoanother e g the time line form Monday bay be copied for Tuesday Wednesday ThursdayandFriday Tocopythetimelineformadayoftheweek proceedasfollows 1 Usecontroller up down toselectadayoftheweek tobe copied e g Monday andconfirmitbypressing button 2 After that changes may be introduced to the time line but they are not necessary Press again butt...

Страница 11: ...sing button 4 Then use controller left right to set the stoppage time and confirm it by pressing Now it is possible to set the stoppage time of the pump in minutes use controller up down Afterthisvalueisset confirmitbypressing 5 Now operation parameters of the circulation pump in the selected hour are set active rectangle KO KO KO KO KO troj KO KO KO a troj b button utton OK OK OK OK Hot water cir...

Страница 12: ...H At least one 1 temperature regulator equipped with a clock must be paired with the device If not this information will not be displayed Informs about pump operational status Pump turned on Pump turned off Empty field indicates that no device from this zone is paired with the controller Indicates activated relay heating of the zone 23 0 C 21 0 C Temperature in the zone Set temperature If temperat...

Страница 13: ...tivated relay heating of the zone Temperature in the zone Set temperature If temperature in the zone drops below the set value then heating of the zone will be activated Signal strength received from paired device Battery status of paired device Status of other devices paired with the zone here a wireless window handle AURATON H 1 Hysteresis History of relay operation for the last 24 hours graph 1...

Страница 14: ...central heating pump Thecentralheatingpumpisturnedon whenanyofheatingzonesisactivated Thecentralheatingpumpisturnedoff whennoheatingzoneisactivate A special anti seizing algorithm overrides any other control settings of the heating pump It activatesthepumpfor15secondsinthefollowingcases After the controller detects the pump for the first time or each time after turning on thepowersupplyandtherelay...

Страница 15: ...ionsshallbealwaysmadewithdisconnectedpowersupply It is recommended to commission the installation of the controller to a specialized company 15 Comments RESETTING the controller In order to reset the controller to its default settings proceed as follows 1 Press ON OFF button a single acoustic signal will be emitted Thedisplaywillshowapicklist 2 Use controller up down to select option Delete wirele...

Страница 16: ...and acoustic signal Automatic detection of connected heads central heating pump and circulation pump 8 30 W per zone controlling heads 230V up to 6 AURATON regulators heating pump 230V Disposal The devices are marked with a crossed wheeled bin In accordance with European Directive 2002 96 EC and the Act on Waste Electrical and Electronic Equipment this marking indicates that the device after compl...

Отзывы: