25
Assembly Instruction
KSA - T
WIN
S12 24V DC
07
Formula to calculate
the required wire cross-section of a infeed line
Calculation example
Available data:
• cut-off current per drive (i. e. 2 x 4.0A) from data sheet
• length to be bridged from the last window to the control unit
(i. e. 10 meters)
Comply with the local regulations and directives for
fi re behaviour of
building materials and building components (E30, E60, E90) and erec-
tion of power installations with rated voltages below 1000V!
Recommendation:
In choosing a cable, select the next higher wire cross section to antici-
pate possible later changes to the system (e.g. replacement of drives
with greater current consumption or extension of the SHEV or venti-
lation line.
UniPC with confi guration interface
Order number:
Application:
Rated voltage.
Parameterizable
drives:
Scope of delivery:
524178
Hard- and softw
are for confi guration of
drives supplied by Aumüller Aumatic GmbH
24V DC +/-20%
24V DC type MP, S3, S12, S12 V.2
230V AC type S12, S12 V.2
software UniPC (Downloadlink*), Interface
“ParInt”, USB cable, connection cable
* http://aumueller-intern.de/UniPC/UniPC_setup.exe
Features /
Equipment:
Power supply 24V DC
is not included in the
scope of delivery!
Any extended settings
require a software
licence.
Any reconfi guration of a drive is entirely at the
user‘s own risk and responsibility.
I
NSTRUCTIONS
ON
CONNECTION
S
AFETY
CHECK
AND
P
ERFORMING
TEST
RUN
I
NSTRUCTIONS
ON
CONNECTION
Connecting drive cable
• Avoid any installation area with large temperature dif-
ferences, risk of water condensation
• Close to the window (shall be easily accessible later on
for repair work)
• Ensure that a later removal of the connection cable is
possible
• Observe maximum cable length of drives (standard
length approx. 5 meters)
S
AFETY
CHECK
AND
P
ERFORMING
TEST
RUN
Check safety of the assembled system and perform test run
and commissioning.
Safety check:
• Connect operating voltage
• Re-check fastenings (casement bracket, frame
bracket) and re-tighten if necessary
Performing test run:
• visual check of casement motion
• stop immediately in case of mulfunction
• make sure there is no collision with facade construction
and, if necessary, correct assembly or re-confi gure
A
I
L
2
2,0
56
mm
2
=
(total)
x
x
x
(length infeed line)
V
A
m
(voltage drop)
m / (Ω*mm
2
)
(2 x 4,0A) x 10m x 2
A =
2,0V x 56m / (Ω*mm
2
)
A = 1,42mm
2
->
1,5mm
2
chosen
Cable junction box (for renewal)
Order number:
Application:
Rated voltage:
Material:
Protection class:
Dimensions:
Equipment:
513344
to extend a drive cable
only for low voltage
to max. 50V DC/AC
stainless steel (V2A)
IP 40
25 x 27 x 150 mm
with cable gland PG9 (grey)
including strain relief,
with loose ceramic terminals.
For multiple operation of
the application is possible
only with the master and
slave.
(without M-COM)
ca
. 1
17
15
0
27
2 1
,5
2 5
40
40
18
Ø5