Transformer  Instantaneous  Earth  Fault  Relay  (S14S);

 

Relay  SC14S  is  a  self-powered,  single-phase,  non-

directional, Earth fault relay with one measuring element. The relay can be used for  differential protection of generators, REF 
applications of generators and transformers in all low voltage, medium voltage and high voltage sub-stations. The relay’s solid-
state design offers seven fields selectable pick up current settings. There are two time delay options in addition to instantaneous 
trip–100 millisecond and 200 millisecond. The relay has a built in third harmonic filter to avoid spurious tripping in harmonic 
rich power systems.

 

 

 

Features:  

 

Micro-controller based design 

 

Draw out facility. 

 

Built in Third Harmonic Filter (It helps to avoid spurious tripping in harmonic rich power systems) 

 

Instantaneous time delay or delay of 100 ms, 200 ms can be set 

 

Current Input: 1A / 5A. 

Application:  

These  relay  can  be  used  for  differential  protection  of  generators,  REF applications  of  generators  and  transformers  in  all  
low  voltage,  medium  voltage sub-stations. 

 

TRANSFORMER INSTANTANEOUS EARTH FAULT RELAY (SC14S) 

Item 

Transformer Instantaneous Earth Fault Relay 

Make 

L&T 

Model 

SC14S 

Relay Ratings 

Nominal Current (In) : 1A or 5A                                                          

Frequency : 50Hz ± 2.5 Hz 

Auxiliary Power Supply 

Self powered 

Relay Settings 

Current (Is): 

One of the two ranges (factory set) 

10% to 40% of In in steps of 5% or 
20% to 80% of In in steps of 10 %

 

CT Burden 

Less than 1.0 VA at Is min 
Less than 6 VA at Is max 

Operating 
Characteristics 

Front panel programmable, using push buttons. 

                                      

Pick up current : 

Same as set current Is                                              

Operating time: 

Field selectable 

Instantaneous (Typical 25 ms @ 3 Is) or 100 msec, 200 

msec ( at 3 Is) 

Accuracy 

As per Error class 5 of IS 3231: 1987 

Over Load capacity 

20 times set current Is for 3 sec 

Operation Indicators 

LED indication 

Flag indication (manual reset) 

Output Relay Contacts 

2 C/O contacts for trip signal (self reset) 

Output contact rating 

Rated voltage : 250V AC/ 30V DC                             Rated 
current : 5A                                                         Rated 

Breaking Capacity: 2000VA/240W (Resistive) 

Case  

Draw out case;                                                                                          

Front Bezel

 : 158 x 71 mm, 

Panel Cutout

 : 142 x 62 

mm, 

Depth :

 224 mm 

Weight 

1.0 kg approx. 

Содержание MC 12A

Страница 1: ...b stations The relay has a built in high set facility DIP switches are provided on the front panel for pick up and time delay settings User has a choice of 7 trip time characteristics FEEDER PROTECTIO...

Страница 2: ...1987 a Normal Inverse 3s b Normal Inverse 1 3s c Very Inverse d Extremely Inverse Definite time Three curves as follows e Definite Time 1s f Definite time 10s g Definite time 100s Accuracy As per Erro...

Страница 3: ...iliary Supply 24 240 V AC DC Wide TMS Range 0 01 1 60 Draw out execution With automatic CT shorting facility Instantaneous Over current and earth fault element Communication Through Modbus Protocol on...

Страница 4: ...Stator Ground Fault protection MG30 incorporates 5 output relays expandable up to 16 with the additional module REX 8 Features Voltage controlled over current protection Thermal image element with pr...

Страница 5: ...Instantaneous output 30ms 2 Harmonic restraint level 2H 0 1 1 0 Id step 0 01Id First percent bias 0 5 IR In P 1R 2 20 step 1 Second percent bias IR In P 2R 5 50 step 1 Point of slope variation P 1 3 s...

Страница 6: ...0 to 40 of In in steps of 5 or 20 to 80 of In in steps of 10 CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel programmable using push buttons Pick up...

Страница 7: ...se Cts 1 9999 A step 1A On Rated primary current of earth fault detection Cts 1 9999 A step 1A CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel progr...

Страница 8: ...utomatically manage the starting transition Switch over transition current Itr 0 1 1 Ist step 0 1Ist Maximum switch over time delay tTr 0 5 50 s step 0 1s At motor s start counting of tTr begins If du...

Страница 9: ...pick up level A DIP switch is provided for selection of thermal overload trip class and enable disable of Locked rotor protection and under current protection Other settings are prefixed in the relay...

Страница 10: ...3 sec Both factory set Locked rotor protection Locked rotor current 3 Im Trip time delay 1 sec Both factory set Disable feature Available Under Current protection Under current threshold 50 of Im Tri...

Страница 11: ...d applicable time delays are indicated on a label on right hand side of the unit The wiring diagram label is provided on the left hand side of the unit Display Current and Thermal Capacity Display Dur...

Страница 12: ...l through various settings Function LED showing number or alphabet to indicate which setting is being view as shown in Figure 3 Table 1 gives description of each setting APPLICATIONS MPR 300 offers yo...

Страница 13: ...dVB IdVC Maximum Demand and Inrush Recording IdA IdB IdC Ido I1A I1B I1C I2A I2B I2C IdIIA IdIIB IdIIC IdVA IdVB IdVC Programmable Input Quantities Fn System frequency 50 60 Hz 1In Rated primary curre...

Страница 14: ...1In Detection time 6ms t 20ms Peak current detection with DC offset restraint Digital Inputs B1 Operation block input B2 Harmonic restraint s reduction B3 Oscillographic record external trigger Approv...

Страница 15: ...00 ms can be set Current Input 1A 5A Application These relay can be used for differential protection of generators REF applications of generators and transformers in all low voltage medium voltage sub...

Страница 16: ...nt Function enabling Enable Disable Setting range V 0 5 1 50 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV 0 05 60 s step 0 01s F59 V Second OverVoltage Element Function enabling Enable...

Страница 17: ...alanced Overvoltage Element Function enabling Enable Disable Setting range V2 0 1 1 5 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV2 0 05 60 s step 0 01s Characteristics Accuracy at ref...

Страница 18: ...t Characteristics Normal Inverse 3 5 sec in O V mode Normal Inverse 5 7 sec in U V mode Definite Time 1 10 100 Sec Pick up Voltage Same as set Voltage Vs Reset Voltage 90 to 95 of Set Voltage Vs 105 t...

Отзывы: