Crossbar Xa 

   

 

   

The crossbar is controlled via an USB module within the control computer. 

   

The code from the USB module is transformed into an I²C bus signal. 
This signal controls the individual relays on the relay board. Control is performed in 
series. 
The crossbar may apply 32 different signals to a test pin. 
Up to 64 different pins can be switched, whereas 56 pins have been assigned different 
functions. 

   

The test bench uses the crossbar to communicate with the test specimen. 

 

Assigment list Xa 

 

No.  Function 

No.

 

Function

 

No.

 

Function

 

DSR   NC Contact 

13 

NTC 2.1 

25 

Spare 

DSR   NO Contact 

14 

NTC 2.2 

26 

Spare 

DÖL   NC Contact 

15 

Pot. Wiper(0-5V) 

27 

Spare 

DÖL   NO Contact 

16 

0V analoque 

28 

Spare 

WSR   NC Contact 

17 

DVM +Input 

29 

Spare 

WSR   NO Contact 

18 

DVM - Input 

30 

Spare 

WÖL   NC Contact 

19 

Output 0-20mA + 

31 

Spare 

WÖL   No Contact 

20 

Output 0-20mA - 

32 

Spare 

Blinker      Contact 

21 

Bus A 

 

 

10 

Thermo    Contact 

22 

Bus B 

 

 

11 

NTC 1.1 

23 

+ 24VDC 

 

 

12 

NTC 1.2 

24 

0     VDC 

 

 

   
   

Crossbar Xa is used for simulating the characteristics of any actuator 

For test specimen with MWG, one MWG  for AC .1 and AC .2 each can be connected 
instead of limit and torque switches. 

 
 
 
 

5.1.7 

Connection box Xa 

   

 

   

To facilitate troubleshooting, all 56 signals 

   

(50 from the crossbar and six from the power module) are connected to  
test terminals at connection box Xa. Therefore, the signals can be interrupted manually 
or the current can be measured. 

 

5.1.8 

Measuring and control module, load/ DVM/oscilloscope 

   

 

All signals to be measured are reduced to standardised signals within the hardware of 
the test bench and supplied to Beckhof measuring technology. 

 
   

The signals are 0 – 10 V DC and 0 – 20mA. 

 

The Beckhoff module are connected via Ethernet to the control computer. 
The measured results are evaluated within the software of the overall system. 
 

Содержание PV1644

Страница 1: ...Operation instructions PV1644 Testing device for auma AC control systems Control system...

Страница 2: ...Page 2 Workbench...

Страница 3: ...ons These operation instructions are part of the product Retain operation instructions during product life Pass on instructions to any subsequent user or owner of the product NOTICE Warranty claims Fa...

Страница 4: ...8 3 3 2 Commissioning 9 3 4 Warranty 9 4 Purpose 9 5 System overview refer to attachment 10 5 1 Description of the design 11 5 1 1 The supply module consists of 11 5 1 2 The signal generator comprises...

Страница 5: ...occupational health and safety Commissioning Prior to commissioning it is important to check that all settings meet the requirements of the application Incorrect settings might present a danger to th...

Страница 6: ...n to safety relevant procedures in these operation instructions each marked by the appropriate signal word DANGER WARNING CAUTION NOTICE DANGER Indicates an imminently hazardous situation with a high...

Страница 7: ...from line When the control cabinet is opened live parts may be exposed Before performing a repair or exchanging parts the unit must be separated from the circuit DANGER Dangerous voltage at electrica...

Страница 8: ...d when working in ambient temperatures of 0 40 C Fluctuation of the supply voltage is only permissible within the tolerances TAB VDE 3 3 Assembly and commissioning 3 3 1 Installation electrical connec...

Страница 9: ...he applicable electrical engineering rules For work on systems with hazardous voltages e g EN 50178 as well for correct use of tools the general and regional installation and safety regulations must b...

Страница 10: ...Page 10 5 System overview...

Страница 11: ...uired for the system The system may provide maximum 2 A current of both AC and DC 5 1 2 The signal generator comprises Motor controlled AC transformer with a adjustment range of 0 230 V Rectifier Chan...

Страница 12: ...0VAC 13 Digit Input 9 25 Bus 2A 2 Cont Volt 0 230VAC 14 Digit Input 10 26 Bus 2B 3 Contr Volt24VDC 15 Digit Input 11 27 Burdon1 4 Contr Volt24VDC 16 Digit Input 12 28 Burdon 2 5 Digit Input 1 17 ana N...

Страница 13: ...t 19 Output 0 20mA 31 Spare 8 W L No Contact 20 Output 0 20mA 32 Spare 9 Blinker Contact 21 Bus A 10 Thermo Contact 22 Bus B 11 NTC 1 1 23 24VDC 12 NTC 1 2 24 0 VDC Crossbar Xa is used for simulating...

Страница 14: ...phase AC three resistance strands are switched as star for 1 phase AC and DC test specimens there exist two identical load paths which may be controlled in 3 steps The currents flowing under load are...

Страница 15: ...ght approx 120kg Ambient temperatures 0 C to 40 C Enclosure protection IP 50 Connection voltage 3Ph 400 V 50 Hz N PE Fuse max 10 A Power consumption 3 kVA max Dimensions W H D 1400 x 2400x 800 mm work...

Страница 16: ...r GmbH Co KG P O Box 1362 D 79373 Muellheim Tel 49 7631 809 0 Fax 49 7631 809 1250 riester auma com www auma com Y005 661 003 en 1 12 For detailed information on AUMA products refer to the Internet ww...

Отзывы: