The end positions may also be set using the AUMA Assistant App or the AUMA
CDT software.
Valve damage at valve/gearbox due to incorrect setting!
→
When setting with motor operation: Interrupt operation in time prior to reaching
the end stop.
→
Heed overrun when selecting actuator seating via positions.
7.1.1.
Set end position CLOSED
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Electrical connection and commissioning must be carried out exclusively by
suitably qualified personnel if circuit is live.
→
Do not touch any cables.
1.
Remove cover from actuator.
2.
Operate in direction CLOSE via push button until complete valve closing.
Risk of passing set end positions!
→
During operation in directions OPEN/CLOSE, the actuator stops when reaching
the set end position. When pressing again the button, the actuator runs until
reaching a mechanical stop (end stop of the actuator or the valve) or passes
the end position when releasing the button.
➥
The operation in direction CLOSE is signalled by the LED flashing in red.
3.
Once the desired end position CLOSED has been reached, release the push
button .
➥
The LED continues flashing in blue for approx. 10 seconds. This time span al-
lows for end position setting.
25
PF-M25X – PF-M100X
Parallel
Commissioning
Содержание PROFOX PF-M100X
Страница 9: ...3 Name plate Figure 4 Name plate arrangement 9 PF M25X PF M100X Parallel Name plate ...
Страница 49: ...15 Spare parts 15 1 Multi turn actuators PF M25 PF M100 49 PF M25X PF M100X Parallel Spare parts ...
Страница 51: ...51 PF M25X PF M100X Parallel ...
Страница 52: ...52 PF M25X PF M100X Parallel ...
Страница 55: ...55 AUMA worldwide ...