![AUMA PROFOX PF-100 Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/auma/profox-pf-100/profox-pf-100_operation-instructions-manual_3016453020.webp)
6.4.
Close terminal compartment
Figure 16: Terminal compartment: close
[1]
Cover
[2]
Screws
[3]
O-ring
Short-circuit and electric shock due to pinching of cables!
Risk of death or serious injury!
→
Carefully assemble cover to avoid pinching the cables.
1.
Clean sealing faces of cover [1] and housing.
2.
Check whether O-ring [3] is mounted in the provided groove.
3.
Fit cover [1] and fasten screws [2] evenly crosswise at 24 Nm (M8).
6.5.
External earth connection
Standard version: Without earth connection, with plastic plate and screw only.
Option: With earth connection consisting of metal plate and hex. socket cap head
screw with shaft bearing race.
The actuator is equipped with an earth connection consisting of a metal plate and a
hex. socket cap head screw with shaft bearing race.
Insulating impact of the powder coating can lead to hazardous voltage and
electric shock!
Risk of death or serious injury!
→
Strip powder from actuator surface (file down).
→
Connect all protective earth conductors.
→
Connect earth connection to external protective earth conductor of connection
cable.
→
Power the device only once the protective earth conductor has been connected.
20
PF-M25 – PF-M100
Electrical connection
Parallel
Содержание PROFOX PF-100
Страница 45: ...14 Spare parts 14 1 Multi turn actuators PF M25 PF M100 45 PF M25 PF M100 Parallel Spare parts...
Страница 47: ...47 PF M25 PF M100 Parallel...
Страница 48: ...48 PF M25 PF M100 Parallel...
Страница 51: ...51 AUMA worldwide...