The above values are optimally set for the actuator as default settings. They can be changed if required for
the following conditions:
The P band is to be increased in case the PV (process value/ valve position) increases the SV (set valve)
and the actuators goes into hunting between Open and close and settles at the SV (set value).
Duty Cycle will depend on the P band. P band & Duty cycle are proportional i.e. larger the P band larger
will be Duty Cycle.
H band (Hysteresis band) is to be increased in case there is continuous hunting and the actuator does
not stop.
PROCEDURE TO PROGRAMMING SOLID STATE RELAY CONTROLS
The programming instructions for SSR are as given in PROGRAM MODE – Remote Settings Flowchart
above in section 4.1.1. The same instructions are also given below.
Manual for entering into settings:
Step 1: Put Selector switch in OFF Position
Step 2: Press OPEN and CLOSE Key Together for Approximately 6 Seconds
Step 3: After entering into program mode follow the flow chart as shown
If hunting persist in the specified H-Band