3.6.2.
Settable (user definable) signals
Table 2: Description of the parameter settings
Description
Designation
(process representation)
Prm-Text-Def GSD file
–
(0) = "Bit: Reserved"
For limit seating: Limit switch operated in direction CLOSE
For torque seating: Torque switch and limit switch operated in dir-
ection CLOSE
End position CLOSED
(1) = "Bit: End p. CLOSED"
For limit seating: Limit switch operated in direction OPEN
For torque seating: Torque switch and limit switch operated in dir-
ection OPEN
End position OPEN
(2) = "Bit: End p. OPEN"
End position CLOSED reached or intermediate position reached
(die Zwischenstellungsanzeige erfolgt nur, wenn Parameter
Signal
interm. pos. M0167
=
OPEN/CLOSED = On
)
Signal blinking: Actuator runs in direction CLOSE.
End p. CLOSED, blink
(3) = "Bit: End p. CLOSED, blink"
End position OPEN reached or intermediate position reached.
(die Zwischenstellungsanzeige erfolgt nur, wenn Parameter
Signal
interm. pos. M0167
=
OPEN/CLOSED = On
)
Signal blinking: Actuator runs in direction OPEN.
End p. OPEN, blink
(4) = "Bit: End p. OPEN, blink"
The position setpoint is is within max. error variable (outer dead
band). Is only signalled if Profibus DP master has set the
Fieldbus
SETPOINT
bit (process representation output).
Setpoint pos.reached
(5) = "Bit: Setpoint reached"
Es wird ein Fahrbefehl über die Drucktaster der Ortssteuerstelle
oder den Feldbus in Richtung ZU durchgeführt:
Fieldbus CLOSE
oder
Fieldbus SETPOINT
(Prozessabbild Ausgang). Dieses Bit
bleibt auch bei Fahrpausen gesetzt (z.B. aufgrund der Totzeit oder
der Reversiersperrzeit).
Running CLOSE
(6) = "Bit: Running CLOSE"
Es wird ein Fahrbefehl über die Drucktaster der Ortssteuerstelle
oder den Feldbus in Richtung AUF durchgeführt:
Fieldbus OPEN
oder
Fieldbus SETPOINT
(Prozessabbild Ausgang). Dieses Bit
bleibt auch bei Fahrpausen gesetzt (z.B. aufgrund der Totzeit oder
der Reversiersperrzeit).
Running OPEN
(7) = "Bit: Running OPEN"
Selector switch is in position LOCAL.
Selector sw. LOCAL
(8) = "Bit: Selector sw. LOCAL"
Selector switch is in position REMOTE.
Selector sw. REMOTE
(9) = "Bit: Sel. sw. REMOTE"
Selector switch is in position OFF.
Selector sw. OFF
(10) = "Bit: Sel. sw. OFF"
Limit switch operated in end position CLOSED
Limit switch CLOSED
(11) = "Bit: Limit sw. CLOSED"
Limit switch operated in end position OPEN
Limit switch OPEN
(12) = "Bit: Limit sw. OPEN"
Torque switch operated in direction CLOSE
Torque sw. CLOSED
(13) = "Bit: Torque sw. CLOSE"
Torque switch operated in direction OPEN
Torque sw. OPEN
(14) = "Bit: Torque sw. OPEN"
Collective signal 05:
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to NAMUR
are present.
Device ok
(15) = "Bit: Device ok"
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
NAMUR failure
(16) = "Bit: Failure"
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are temporarily in-
valid.
NAMUR funct. check
(17) = "Bit: Function check"
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation conditions.
NAMUR out of spec.
(18) = "Bit: Out of spec."
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
NAMUR mainten. req.
(19) = "Bit: Maintenance requ."
13
Actuator controls
AC(V) 01.2/AC(V)ExC 01.2 Profibus DP
Commissioning
Содержание AC(V) 01.2
Страница 1: ...Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP Device integration Manual...
Страница 22: ...22 Actuator controls Description of the data interface AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 89: ...89 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...
Страница 90: ...90 Actuator controls AC V 01 2 AC V ExC 01 2 Profibus DP...