©2004 AUGIER SA.
II-34
II.2.1.4 Remote control connections
Connections to the control system is made at the back of
the CCR, on terminal bloc provided on the interface board
(FAA or IEC type). If the cable is screened, connect the
shield only on 1 side, to the frame or at controller’s ground
terminal.
The control cables run from beneath the frame in the right
duct, and have to be connected to interface board laid on
the LV unit.
II.2.1.4.1 CONFIGURATION OF REMOTE CONTROL TYPE
The DIAM CCR can be remotely controlled either by an external voltage (20 to 60 VDC positive or
negative), or by “free potential” contacts (internal power supply 24VDC from the CCR). This choice is made by
positioning jumpers JP11 and JP12 on the motherboard.
Internal power supply: JP11, JP12 on 1-2
External power supply: JP11, JP12 on 2-3
Equivalent B0 and B1 control diagram :
Equivalent B0 and B1 control diagram:
B0 command
C input
B1 command
B0 command
Entrée C
B1 command