II.6.6 SERVICE POSITION:
This is the operating position of the rotative switch.
In this position, the loop terminals are electrically connected to the CCR:
II.6.7 SAFETY POSITION:
This
safety position
will allow the operator to work on the load safely : the
load is in short circuit and grounded. The CCR output is in short-circuit. It can
be energised.
The rotative switch may be locked in the safety position
II.6.8 LOAD MEASUREMENT POSITION:
This
measurement position
will allow any maintenance operation on the
loop. In this position the load terminals are electrically connected to the
measurement points M1 and M2. The CCR cannot be energised.
Load measure