6021752 DIAMXXXX CUT OUT rev 1-0.doc
II-21
II.5.6
EXTERNAL ROTATIVE CUTOUT VERSION WITH PADLOCK (OPTION) :
The rotative cutout may as well be installed on the front panel of the CCR, with external
access. In such a case, the padlocking device is mandatory.
Measurement points are accessible in direct way on the front panel, without opening the
CCR.
II.5.7
CIMALT MAINTENANCE
1.
Remove the 3 fixing screws, and tilt the support plate forward, to access the back of the switch
2.
Check the condition of the 3 contacts and the pressure roller. Clean them or replace them if
necessary.
The caster must be able to slide freely about 5 mm in its support: Use a conductive grease (Ref LUBRILOG:
CUPROLOG G1, Ref ELECTROLUB: HCG).
Check the tightness of each contact.
Содержание DIAM 3100
Страница 2: ...6021752 DIAMXXXX CUT OUT rev 1 0 doc I 2...
Страница 9: ...6021752 DIAMXXXX CUT OUT rev 1 0 doc I 9...
Страница 22: ...6021752 DIAMXXXX CUT OUT rev 1 0 doc II 22...