2011-05
©
Audipack
For connecting or activating the system the switch can be used.
When the system must be connected or activated with an external controll system, use
the below listed option:
-use a separate potential free relay or switch with neutral middle position for each
direction
-always use potential free contact closures (dry contacts)
-switching time delay of at least 0.5 seconds for up and down direction.
For use with an external controll system the standard cable can be modified by cutting
of the switch and use below listed / attached colour scheme to activate the system.
Second option is to use a new control cable with an RJ45 connector.
Pos. 8 red (down)
Pos. 5 green (up)
Pos. 4 blue (common)