output if the temperature increased less than 3 °C (5 °F) after the controller was 
powered up for 5 minutes. The alarm buzzer will be turned on at the same time. 
The display will flashing OPEN (oPEn). 

  Hy. Hysteresis band (or dead band). This parameter is used for on/off control only. 

In the on/off heating mode, the heater will be turned off when T = SV, and turned 
on again when T<SV-Hy. e.g. If SV=100 °C. Hy=3.0 °C, the heater will heat until 
temperature reaches 100.0 °C. It will be turned on again when temperature drops 
below 97.0 °C. For the cooling mode, the compressor will be turned off when 
T=SV. It will be on again when T>SV+Hy. 

  CooL. When Cool=0, the controller is set for heating control (reverse action). 

When Cool=1, the controller is set for cooling control (direct action). 

  Out, Output power reduction. It is expressed as a percentage value. This function 

will allow you to control the maximum output power delivered by the heater. For 
example, if you set Out=50 and your heater is 1000 watts, the output will use 50% 
of the 1000 watts as the full output. It treats the 1000W heater as a 500W heater. 
When the PID algorithm determines 50% output value, the actual power output 
will be 250 watts. This function can be used in two situations. 
1) When you have a very powerful heater and are using a very small pot of water 
to cook at very low temperature, for example, a 1400 watts heater with a one litter 
(1 qt) pot of water at 130 °F. The heater is too powerful for the small water volume. 
The moment it is on, it releases too much energy and overshoots the temperature. 
Although it is still possible to stabilize the temperature with proper PID parameters, 
it is much easier to control if you limit the maximum output to 25%.    Ideally, an 
optimized temperature control system should consume about 25 % of the heater 
power at set temperature (steady state), for example, if you found out that only 50 
watts of energy is needed to maintain the temperature at 60 °C (141°F), ideally 
you should use only a 200 watts heater for the job. Too much power will make the 
system over react too quickly. Too little power will make the system too slow in 
response. By using the OUt function, you can make the 1400 watts heater to act 
as a 200 watt heater for stable temperature control. 
2) When the cooker consumes more power than controller can handle, for 
example, if you have a 12A, 120V AC heater and your cooker contains more than 
38 liter (10 gallon) of water. It might take more than 90 minutes of full power 
heating for controller to heat up the pot. Long time of full power operation might 
cause the controller to over heat. You can set the output to 80%. It will prevent the 
controller from over heating from staying at full power too long. For details, please 
see Appendix 1. 

  C-F, Display unit setting. You can set the display either Celsius or Fahrenheit. 

 

This group of parameters is accessed by input code 155. Figure 9 is the flow chart that 
shows how they can be changed. 

Содержание WS-1500EBPM

Страница 1: ...ETY WARNINGS This controller is designed only to be used with devices that have limited power and their own thermal cutoff protection such as a thermostat or thermal fuse in case of controller failure...

Страница 2: ...he controller off unplug the power cord and contact the manufacturer before using it again Clean the controller only when it is cool and unplugged Do not allow children to operate the controller Speci...

Страница 3: ...ht on the cooking device 3 SET Key For showing current temperature settings entering parameters setting mode and confirming various actions taken 4 Key To increment displayed value 5 Key To decrement...

Страница 4: ...Figure 2 Back Panel 2 Connecting the controller Figure 3 Typical connection between the controller and the heating device in this example the cooker The connection of the controller should be done in...

Страница 5: ...heater has a switch put it in the off position Put the sensor inside the container to be controlled Turn on the controller Turn on the heating device Remark The connector of sensor contains a slot fo...

Страница 6: ...erature may not be able to reach the current step temperature setting before it jumps to the next step The time unit is in minutes with 1 minute resolution If the recipe only needs one step you can pr...

Страница 7: ...steps for cooking you can finish programming by pressing the SET continuously until it passed T06 and the LED displays the current temperature You can also leave the controller alone The display will...

Страница 8: ...to use these settings for other cooking device also because they are suitable for a typical slow response and balanced system If you feel the performance is not ideal you can try to use the recommend...

Страница 9: ...66 Symbol Display Description Range Initial P P Proportional band in 0 1 Degree 0 600 180 I I Integral constant second 0 900 700 d d Derivative constant second 0 300 40 AT AC Auto tune 0 off 1 on 0 T...

Страница 10: ...cookers setting I 0 will significantly reduce the temperature overshoot d Derivative time The unit is in seconds Derivative action contributes the output power based on the rate of temperature change...

Страница 11: ...ng environment The duration of auto tuning depends on how fast the system is responding to the heating and cooling cycle If the temperature of the cooker takes a long time to drop when the heater is o...

Страница 12: ...ED displays LCK Then release the SET key The display will show 0 To get into parameters setting mode you need to key in the pass code Use and keys to adjust the display to 166 which is the pass code a...

Страница 13: ...cooling 0 heat 1 cool 0 Out 00t Output power reduction 1 100 100 C F C F Temperature unit C or F C 180 0 AL AL Alarm Setting 58 0 392 0 F 50 0 200 0 C Details about each parameter SC calibration offs...

Страница 14: ...eater with a one litter 1 qt pot of water at 130 F The heater is too powerful for the small water volume The moment it is on it releases too much energy and overshoots the temperature Although it is s...

Страница 15: ...n its value Use and keys to change the setting When finished press the SET again to confirm the change For example if the temperature is 1 C too high during calibration then use to set the value to 1...

Страница 16: ...andling in transit This warranty does not cover damage or defects caused by or resulting from damages from shipping or repairs service or alterations to the product or any of its parts which have been...

Страница 17: ...17 ATTENTION CUSTOMER SERVICE We are constantly striving to improve our products and therefore the specifications contained herein are subject to change without notice...

Страница 18: ...l produce about 1 3 watts of heat When 12 Amp is passing through the controller 16 watt of heat is produced in the controller As more heat is produced the temperature inside the controller will rise I...

Страница 19: ...ive current is much lower making heat not an issue 2 Limit maximum output power If you set output reduction parameter to 80 then a 15A heater will become a 12A heater It will take 25 longer time to he...

Отзывы: