background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2015.06                                                                     

   

                                                       P2/5 

 

5.

 

Mode Selection 

This controller has 5 different modes: program run, program hold, program 
stop, parameter setting, and programming mode. Before powering on the 
controller, please connect the sensor cable to it. If no sensor is connected, the 

controller will show error code “Err”, indicating no sensor is detected. 

When the 

controller is powered on, it enters the Program Hold mode. It will flash 
measured reading temperature 

value and “hold” alternatively

. The controller 

will start controlling temperature according to the saved setting, but the timer is 
paused.  
 

Program 

Hold

Parameter 

Setting Mode

Program 

Run

Program 

Stop

Programming 

Mode

2 s

4 s

START

START

STOP

SET

PAUSE

Controller 
Power Up

SET

 

Figure 2. Switching between different modes.   

 
 

Program Running

: The controller executes the saved program. The green 

indicator RUN is lit, and the timer is running. The display window should show 
the current temperature reading. The controller will send power to its 
heating/cooling sockets to regulate temperature. When the program is running, 
press PAUSE key will put the controller to Program Hold mode. 

Program Holding

: Controller pauses the time but it still regulates the 

temperature at the current set value. The RUN indicator is off. The display 
window flashes between the reading temperature 

and “Hold”. To resume the 

program, press START key. To completely stop the program, hold the STOP 
key for 4 seconds.  

Program Stop

: The execution of the program is terminated. Controller outputs 

are deactivated and timer is also stopped. The RUN indicator is off. The display 
window flashes between the reading temperature 

and “Stop”. To start the 

program, press the START key. The controller will start regulating the program 
from the first step. 

Programming Mode: 

Review and edit temperature set value and set time for 

each steps. When the controller is in Program Run, Hold, or Stop mode, press 
SET key to enter the Programming mode. Please see Figure 4 for details.

 

Parameter Setting Mode: 

Review and edit system parameters. When the 

controller is in Program Run, Hold, or Stop mode, hold the SET key for 2 
seconds to enter the Parameter Setting mode. Please see Figure 3 for details.

 

 

6.

 

Parameter Setup  

Please see Table 2 for a list of parameters and see Figure 2 for the flow chart of 
how to set the parameters. Please note that parameters will remain unchanged 
unless you press set key to confirm the change. 
 
Table 2. Parameters Description. 

Code 

Description 

Setting 

Range 

Initial  Note 

AH 

AH 

Deviation high alarm 

0.5~999.9 

20.0 

AL 

AL 

Deviation low alarm 

0.5~999.9 

20.0 

Hy 

HY 

Temp. Control Hysteresis 

Band 

0.5~99.9 

1.0 

CdF 

CDF 

Cooling Differential 

0.5~99.9 

5.0 

HdF 

HDF 

Heating Differential 

0.5~99.9 

5.0 

oFS 

Ofs 

Temp. Offset 

-99.9~99.9 

AS 

AS 

Anti-short Cycle Delay (only 

for cooling socket) 

M 0~ M99 

(0~99 min) 

M 0 

A-M 

A-M 

Power Outage/Startup 

Modes 

S,M,C 

PrG 

PrG 

Program Modes 

on, off 

ON 

SFA 

SFA 

Sensor Failure Operation 

0-0, 0-1, 1-0 

0-0 

Time 

time 

Time unit 

H, M 

10 

C-F 

C-F 

Temperature unit 

ºF, ºC 

ºF 

11 

 
Note 1. 

AH, deviation high alarm; AL, deviation low alarm: 

Assuming measured temperature is PV and set temperature is C. When PV - C 
is above AH, the built-in buzzer will turn on (deviation high alarm); when H 

 

PV is above AL, the built-in buzzer will turn on (deviation low alarm). User can 
mute the alarm by momentarily pressing the Mute key. The alarm will remain 
inactive until the process value moves out of the alarm zone. Both alarms are 
deviation alarms, i.e., if AH = 20, AL = 30, and the Set Temperature (C) is 50F, 
the alarm will be activated if the temperature is above 70F or below 20F. The 
alarm function is suppressed at powering up or when the program is jumped 
from one step to another step. It will be activated automatically once the 
measured temperature enters the none-alarm zone (between C - AL and C + 
AH). 
 

Note 2. 

Hy, Temperature Control Hysteresis Band, or Temperature Control 

Dead Band: 
This parameter set up a dead band (between C - Hy and C + Hy) within which 
either the heating device or cooling device will not work. The minimum value 
for Hy is 0.5. The Hy value should not be too small if the system has sluggish 
response. Otherwise, it may result in the heating device and the cooling device 
working against each other, wasting energy and causing oscillation. 
 

Note 3. 

CdF, Cooling Differential: 

This is the differential band between turn on and turn off the cooling device. It 
is set to the higher side of the temperature set point (C + Hy). The cooling 
device will turn on when temperature is above (C + Hy + CdF), and turn off 
when temperature is below (C + Hy). For compressor based cooling device, the 
CdF value should not be set too small to prevent frequent cycling.  
 

Note 4. 

HdF, Heating Differential: 

This is the differential band between turn on and turn off the heating device. It 
is set to the lower side of the temperature set point (C - Hy). The heating 
device will turn on when temperature is below (C - Hy 

 HdF), and turn off 

when temperature is above (C 

 Hy).  

For example, if Set Temperature C = 50, Hy = 5, CdF = 3, HdF = 2, then the 
heating device will turn on when process temperature is lower than 43 (C - Hy - 
HdF) and turn off when process temperature rise above 45 (C - Hy). The 
cooling device will turn on when process temperature is above 58 (C + Hy + 
CdF) and turn off when process temperature drop below 55 (C + Hy). 
 

Note 5. 

oFS, Temperature Offset: 

oFS is used to compensate the error produced by the sensor or input signal 
itself. For example, if the unit displays 37 when the actual temperature is 32. 
Set parameter oFS = - 5 will make the controller display 32.The displayed 
process temperature = actual measured tempe oFS.   

Содержание TD400P

Страница 1: ...Minute Max Programmable Time 799 2 hours or 33 3 days for total 8 steps Audio Alarm High and low limit Sensor Type Silicon Band Gap Sensor Sensor Size 0 25 OD 6 35 mm x 1 25mm long Ambient Temperature 20 50 C 0 120 F Dimension 91 x 140 x 46mm Input Power 85 242 VAC 50 Hz 60 Hz Sensor Cable Length 6 ft 2 m Power Cable Length 3 ft 1 m Warranty One 1 year Either heating or cooling device is limited t...

Страница 2: ...erential 0 5 99 9 5 0 4 oFS Ofs Temp Offset 99 9 99 9 0 5 AS AS Anti short Cycle Delay only for cooling socket M 0 M99 0 99 min M 0 6 A M A M Power Outage Startup Modes S M C S 7 PrG PrG Program Modes on off ON 8 SFA SFA Sensor Failure Operation 0 0 0 1 1 0 0 0 9 Time time Time unit H M H 10 C F C F Temperature unit ºF ºC ºF 11 Note 1 AH deviation high alarm AL deviation low alarm Assuming measure...

Страница 3: ...ess temperature alternatively This mode is suitable for situations where the operator s attention is needed after power interruption occurs Note 8 PrG Program Mode When PrG is set to ON user can program up to 8 steps Section 7 When set it to OFF this multi step function is disabled and controller is in single step mode User can only set C 1 value without timer t 1 when disabled Please be aware tha...

Страница 4: ... part of the program by jumping to a specified program step For example the controller has run 3 minutes in its 2nd step If the user want to skip the rest of the 2nd step and the entire 4th step then the user can jump to step 4 To jump to a specified step 1 Put the controller in either Program Hold or Stop Mode 2 Press STEP key so the controller will flash J PX where J indicates this operation is ...

Страница 5: ...ble To install the sensor to the controller 1 Identify the key on the male sensor connector Figure 5 a and the notch on the female connector Figure 5 b 2 Hold the tail of the female connector align the notch and the key and push the female connector forward To remove the connector hold the spring loaded collar on the female connector and pull it back Please see Figure 6 a b c Figure 5 Install the ...

Отзывы: