                                                       P5/7 

 

disable the AL (Pit) alarm, you can set it to a small number, such as 0° F 
(default). 
 

              Pit
       Low Alarm

 

Figure 11. The LCD display when 

AL (Pit)

 is triggered.  

 
 

Note 3. AH (Food):

 This is the high temperature alarm for the food probe 

(Probe 2). When food probe reading is higher than 

AH (Food)

 value, the 

buzzer on the controller will go off and the LCD display will flash between the 
normal display and the alarm display showing in Figure 12. The alarm has 1°  
hysteresis. The user can mute the buzzer by pressing either the Up key or 
the Down key. For example, if 

AH (Food)

 is set to 130° F, the buzzer will go 

off when Probe 2 reads 131° F, and the buzzer will stop when Probe 2 reads 
129° F or lower. To disable 

AH (Food)

 alarm, you can set it to a large 

number, such as 999° F. 
 
When smoking multiple pieces of meat of different sizes or thickness, you 
can put the probe in the thinnest piece first. Set the 

AH (Food)

 alarm to the 

temperature when meat is ready. It will let you know when it is done. Then, 
you can move the probe to the second thinnest pieces and so on. To use this 
feature, you can set the ending criterion to time. If you prefer to set the 
ending criterion to food temperature, then the Food Temp should be set to 
higher than the 

AH (Food)

.  

 

             Food
       High Alarm

 

Figure 12. The LCD display when 

AH (Food) 

is triggered.  

 
 

Note 4. P:

 Proportional Constant. The unit is 1 degree. This parameter control 

the output of the controller based on the difference between the measured and 
set temperature. Larger the P number means the weaker the action (lower 
gain). If 

P

 = 7, the proportional band is 7 degree. When the sensor 

temperature is 7 degrees below the proportional band (10 degrees below the 
setting), the controller will have 100% output. When the temperature is 5 
degree below the set point, the output is 71%. When the temperature is equal 
to the setting, the controller will have 0% output (assuming integral and 
derivative functions are turned off). This constant also affects both integral and 
derivative action. Smaller 

P

 values will make the both integral and derivative 

action stronger. Please note the value of the 

is temperature unit sensitive. If 

you found an optimized 

P

 value when operating the controller in Fahrenheit, 

you need to divide the 

P

 by 1.8 when changing the temperature unit to 

Celsius.  
 

Note 5. I:

 Integral Time. The unit is in seconds. This parameter controls the 

output of controller based on the difference between the measured and set 
temperature integrated with time. For example, if 

I

 = 1000, it means if the 

temperature difference between the pit temperature and set temperature stays 
constant, the output will be doubled after 1000 seconds.  Integral action is 
used to eliminate temperature offset. Larger number means slower action.  
 

Note 6. d:

 Derivative Time. The unit is in seconds. Derivative action 

contributes the output power based on the rate of temperature change. 
Derivative action can be used to minimize the temperature overshoot by 
responding its rate of change. The larger the number is, the stronger the 

action will be. For example, when the door of oven is opened, the temperature 
will drop at very high rate. The derivative action changes the controller output 
based on the rate of change rather than the net amount of change. This will 
allow the controller to act sooner. It will turn the heater to full power before the 
temperature drops too much. 
 

Note 7. T: 

Control Cycle Time. The unit is second. This unit determines how 

long for the controller to calculate each action. It is only meaningful in the 
PWM mode. e.g. if 

T

 is set to 15 seconds, when controller decide the output 

should be 10%, it will turn on the heater 1.5 second for every 15 seconds. This 
parameter is set to 15 seconds by default. 
 

Note 8. OL Switch: 

Open-Lid Detection Switch. This parameter works as an 

on/off switch to enable or disable the Open-Lid Detection function. When 

OL 

Switch

 is set to 

on

, the Open-Lid Detection function is enabled; otherwise, 

disabled. 

When the lid or dome of a smoker is opened during smoking, the pit 
temperature will drop quickly. The derivative function (

d

) of the PID controller 

will force the blower to run, probably at the maximum speed, in order to stop 
the trend of temperature-dropping. This action would blow up ashes, blow the 
flame stronger, and cause a big temperature overshot after the lid is closed. 
The open-lid detection function is designed to prevent these problems.  

When the smoker

’s

 lid or dome is opened, this function will detect the sudden 

temperature drop and stops the blower. After the lid is closed and the pit 
temperature is recovered by the residual heat stored in the smoker, the blower 
will resume running. However, after 7 minutes, if the temperature 

still hasn’t 

been recovered yet, the controller will resume sending its output to the blower. 
This open-lid detection function is inactive when you starting the fire at the 
beginning. It will be activated after the pit temperature less than 5 degree 
lower than the set temperature. Sometimes the open-lid detection might be 
triggered accidently by a temperature drop not related to lid-opening during 
smoking. In that case, you can cancel this activation by pressing the 
Time/Back key on the controller, or tap t

he “X” 

(Cancel) symbol appeared near 

the “

Open-Lid Detection

” on the SYL

-2615 device info page from the 

AuberSmart app. In situations where the open-lid detection is activated by 
actual lid-opening action, we recommend you not to cancel this function to 
avoid getting a pit temperature overshot. The controller can take care of this 
issue and minimize the disturbance. But if you are cooking at a higher 
temperature range (> 300° F), the pit temperature many not be able to recover 
by itself. In this case, cancel the activation. 

If you want to manually pause the fan output temporarily, you can press and 
hold Up key for 3s. To resume the fan output, press Up key again 
momentarily. (firmware 1.9 or newer).  

Note 9. Save & Recall:

 This controller allows the user to save and recall up to 

6 sets of the P, I, D, and Control Mode settings. The user can tune the settings 
for cooking at different conditions (e.g., different smokers/grills, different 
ambient temperature, or cooking temperature) and save them for future use. 
Three sets of settings for 

18.5’’ Big Green Egg, 22.5” Weber 

Smoky Mountain, 

and 

18.5” Weber 

Smoky Mountain has been pre-saved on the controller as 

BGE

WSM22

, and 

WSM18

 respectively. Another 3 sets of settings 

named as 

4

”, “

5

”, 

and 

6

 are available for custom tuned parameter settings. 

The names for those sets cannot be changed at this moment. Please see 
Table 3 for the name and the values of each group of settings.  

Содержание SYL-2615

Страница 1: ...of which the cooking time is unknown it is better to set a target food temperature to end the step SYL 2615 has a build in Wi Fi module which allows its user to monitor the temperature and control the...

Страница 2: ...ut 99 SET Press and hold Figure 5 Access the menu of parameters using SET key 5 Getting Started Power on the controller by plugging the barrel connector from the 12 VDC adapter to the power input port...

Страница 3: ...N A In this example a user set the pit temperature of Step 1 to 275 F which is higher than normal smoking temperature to speed up the low and slow cooking without compromising the moisture Step 1 wil...

Страница 4: ...2 WSM18 4 5 6 Back 9 Recall Recall PID Settings Back BGE WSM22 WSM18 4 5 6 Back 9 Back Back to main menu Control config System config AH Pit 350 AL Pit 0 AL Pit 0 AH Food 350 Back AH Pit 250 SET SET A...

Страница 5: ...he rate of change rather than the net amount of change This will allow the controller to act sooner It will turn the heater to full power before the temperature drops too much Note 7 T Control Cycle T...

Страница 6: ...manually adjust the fan speed output voltage Note 12 FMRV Fan minimum running voltage This parameter is only used when controller is running under fan speed control mode Due to the variation in the fr...

Страница 7: ...on the probe your probe is bad If this issue remains on the controller your controller is bad For more details please contact customer support 8 2 What if one step is set to end by food temperature w...

Отзывы: