AUBER INSTRUMENTS
WWW.AUBERINS.COM
2019.07
P4/7
Pit: 73 Set:225
Food:71 Out:99
>Step: 1 Pit: 225
1-End: Fd Temp
>1-End: Fd Temp
1-Fd Temp: 170
> 1-Fd Temp: 170
Step: 2 Pit: 225
>Step: 2 Pit: 225
2-End: Time
>2-End: Time
2-Time: 6:00
>2-Time: 6:00
Step 3: Pit: 160
SE T
>Step: 1 Pit: 225
>Step: 1 Pit: 275
1-End: Fd Temp
>1-End: Time
1-Fd Temp: 170
1-Fd Temp: 175
>Step: 2 Pit: 225
>Step: 2 Pit: 230
>2-End: Fd Temp
>2-Time: 6:00
>2-End: Time
>Step 3: Pit: 160
3-End: Time
>3-End: Time
3-Time: 0:00
> 3-Time: 0:00
Back
>Step 3: Pit: 160
>Step 3: Pit: 165
>3-End: Time
> 3-Time: 0:00
>2-Time: 6:10
>3-End: Fd Temp
> 3-Time: 0:10
> Back
Step: 1 Pit: 275
SE T
SE T
SE T
SE T
SE T
SE T
SE T
SE T
SE T
/
/
/
/
/
/
/
/
/
SE T
SE T
SE T
SE T
SE T
SE T
SE T
SE T
SE T
SE T
Figure 8. How to enter a cooking profile on SYL-2615 controller. The program
shown in Example 1 is used in this flow chart as a demo.
6.2 Set Parameters
To access the parameters, press and hold SET key for about 2 seconds.
Parameters
are divided into two groups: “
Control Config
” and “
System
Config
”.
6.2.1 Control Configurations
Parameters related control configurations during the smoking process are
liste
d under “
Control Config
” menu. Details of each parameters are listed in
Table 2. The flow chart in Figure 9 shows the operations of accessing and
adjusting the parameters in “
Control Config
”.
Table 2. Parameters in Control Config menu.
Name
Description
Range
Initial
Note
AH (Pit)
Pit High Alarm
0 ~ 999
80
1
AL (Pit)
Pit Low Alarm
0 ~ 999
0
2
AH (Food)
Food High Alarm
0 ~ 999
350
3
P
Proportional
Constant
1 ~ 999
60
4
I
Integral Time
0 ~ 9999
1200
5
D
Derivative Time
0 ~ 999
60
6
T
Control Cycle Time
2 ~ 200
15
7
OL Switch
Open-Lid Detection
ON, OFF
ON
8
Save
Save PID Settings
(Back), BGE,
WSM22,
WSM18,
4,5,6
Back
9
Recall
Recall PID Settings
(Back), BGE,
WSM22,
WSM18,
4,5,6
Back
9
Back
Back to main
menu
> Control config
System config
> AH(Pit): 350
AL(Pit): 0
> AL(Pit): 0
AH(Food): 350
> Back
AH(Pit): 250
SET
SE T
> AH(Pit): 350
> AH(Pit): 250
SE T
/
SE T
> AL(Pit): 0
> AL(Pit): 180
SE T
SE T
/
Figure 9. Access the parameters in
Control Config
menu.
Note 1. AH (Pit):
This is the high temperature alarm for pit temperature
(Probe 1). When pit probe reading is higher than
AH (Pit)
value, the buzzer
on the controller will go off and the LCD display will flash between the normal
display and the alarm display showing in Figure 10. The alarm has 1°
hysteresis. The user can mute the buzzer by pressing either the Up key or
the Down key. Temperature must move out of the hysteresis zone to activate
the alarm again. For example, if
AH (Pit)
is set to 290° F, the buzzer will go
off when Probe 1 reads higher than 291° F, and the buzzer will stop when
Probe 1 reads lower than 289° F. To disable
AH (Pit)
alarm, you can set it to
a large number, such as 750° F.
Pit
High Alarm
Figure 10. The LCD display when
AH (Pit)
is triggered.
Note 2. AL (Pit):
This is the low temperature alarm for pit temperature
probe (Probe 1). When pit probe reading is lower than
AL (Pit)
value, the
buzzer on the controller will go off and the LCD display will flash between
the normal display and the alarm display showing in Figure 11. The
alarm has 1° hysteresis. The user can mute the buzzer by pressing
either the Up key or the Down key. Temperature must move out of the
hysteresis zone to activate the alarm again. For example, if
AL (Pit)
is
set to 180° F. The buzzer will go off when pit temperature drop to 179° F;
it will stop when temperature rise above 181° F. The
AL (Pit)
alarm is
suppressed when the controller is just powered up. It will be activated
when the pit temperature has reached the target pit temperature. To