VG OSG
Version 3
17
Once the control box is in place, cable runs can commence. See Drg. Circuit Diagram
Overview (sheet 1) for help to plan the cable runs.
We would strongly suggest that the power is fed from the main lift panel
protected by a circuit breaker Type C rated at 4 Amps.
The cable run should be as short as possible. If the length does not exceed 2metres
the size should be at least 1.5mm
2
. Stranded tri-rated PVC insulated. It should also
comply with local regulations.
The control box base will need holes drilling in either the side or bottom face to
allow for cable entry and it is recommended that Conduit Glands are used. Care
should be taken when deciding on the cable entry points to avoid the internal
battery and power supply unit both of which are mounted in the base.
During wiring great care must be taken to ensure that there is no risk of short
circuits from stray strands, cross connection, loose terminals or strain on cable
joins. All terminations should be made using boot lace ferrules or similar and each
wire appropriately identified with its corresponding wire number at each end of the
cable. Wiring of power and internal main lift connections must be carried out by a
competent electrician, and checked prior to applying power.
SAFETY NOTE:
Once connected to the main lift control panel there will be
potentially live connections within the VGOSG-CB01 enclosure even when the fuses
for the enclosure have been withdrawn. Within the VGOSG-CB01 enclosure the
internal connecting cables are coloured red (input wiring from the main controller
may be different colour) and warning symbols are displayed, this is so that you can
easily identify them as potentially live, check them and beware of them.
Wiring