8

Regulation of the  KZT Plus boiler

Switching Summer/Winter

Hold the button for 1 second (see 6 - Pic.2).
The Summer sign appears on display (see 10 - Pic.1). Boiler will make only DHW. The antifreeze 
system remains active. To cancel the Summer mode, hold the button for 1 second again (see 6 - Pic.2).

Regulation of the heating water temperature

It is possible to set the temperature from the minimum of 20°C up to the maximum of 90°C by the 
buttons of heating (see 3 and 4 - Pic.2).

Regulation of the DHW temperature

It is possible to set the temperature from the minimum of 10°C up to the maximum of 65°C by the 
buttons of DHW (see 1 and 2 - Pic.2).

Setting of the environment temperature (with additional room thermostat)

Set the required temperature in premises by the room thermostat. If the room thermostat is not 
connected, boiler will keep temperature in supply system at value that was set at the inlet into the 
supply system.

Environment temperature setting ( additional time remote control) 

Set the required temperature in premises by the 

. Boiler will treat water in device 

time remote control

adequately to the required temperature of environment. Farther in this manual you will find instructions 
for operation with time remote control.

Equithermic regulation of the  KZT Plus, KST Plus, KT Plus, KT small Plus boilers

After installation of external probe (additional), the external temperature measured by the external 
probe is displayed on the screen of the control panel (See 5 - Pics.1 and 2). 
Boiler regulation system works with the „Controlled temperature“. In this mode is temperature of the 
heating device regulated according to the external climatic conditions to ensure higher comfort and 
energy savings during the whole year. Moreover, after increasing of the external temperature is the 
temperature at the boiler  outlet decreased  according to the concrete „ compensation curve“. By 
regulation of the equithermic regulation of temperature, the temperature set by the buttons of heating 
(See 3 and 4 - Pics.1 and 2) represents maximum temperature at the inlet  into the heating device.
It is recommended to set maximum temperature to enable system operation within the full interval. 
Boiler must be set by specialist during the installation. Necessary adjustment for higher comfort can be 
done by user.

Compensation curve and shift of curves of the condensing boilers Plus

Press button once to display actual compensation curve (See 6 - Pic.1 KST, KT and See 10 - Pic2 KZT). 
It is possible to change it per DHW buttons (See 1 and 2 - Pic.1 and 2). Adjust the required curve from 1 
to 10, adequately to the characteristics. By adjusting curve to 0 is the regulation of the controlled 
temperature cancelled.

Compensation curve of the Plus condensing boilers

 Access to the paralel curves shifting is enabled through heating buttons (See 3 and 4 - Pics. 1 and 2). 
Flickering text (OF) is displayed. It is possible to change it through DHW buttons. (See 1 and 2 - Pics. 1 
and 2). 

Parallel shift of the curves of the condensing boilers Plus 

Repeated pressing of the button (See 6 - Pic.1 KST, KT  ) and (See 10- Pic.2 KZT ) enables to exit 
mode of the parallel curve regulation. If the environment temperature is lower than required 
temperature, it recommended to set more abrupt curve and vice-versa. Decrease or increase for 1 unit 
and check the result in the room.

Содержание KST

Страница 1: ...W W W A T T A C K S K GASCONDENSINGBOILER ATTACK KZT KST KT KTSmall KZTSolarPlus INSTRUCTIONS FOR USE...

Страница 2: ...Hydraulic connections Gas connection anti freeze system Electrical coonections and external sensor Placing of external probe and access to el terminal Flue gas outlets Accessories Connection to outle...

Страница 3: ...ed with electronic ignitionandionisationflamecontrol venilatorwithmodulationofrotationsandmodulationgasvalve Control panel of boilers KT Plus KT small Plus KST Plus Pic 1 Control panel Description 1 B...

Страница 4: ...s by symbol of water tap see page 9 pic 1 Water in exchanger is permanently warmed to temperature of 45 C Display see page 11 pic 1 shows actual temperature of water in the boiler Start and stop of bo...

Страница 5: ...ture It is possible to set the temperature from the minimum of 10 C up to the maximum of 65 C by the buttons of DHW see 1 and 2 Pic 1 Setting of the environment temperature with additional room thermo...

Страница 6: ...Setting temperature at the DHW outlet flickers during the Heat exchanger protection operation 15 Indication of Eco Economy mode or Comfort mode 16 Temperature of the external sensor with additional ex...

Страница 7: ...utton for 1 second again see 9 Pic 2 Boiler will be immediately ready for operation by every DHW consumption or by activation through the room thermostat Indication during heating operation of the KZT...

Страница 8: ...de is temperature of the heating device regulated according to the external climatic conditions to ensure higher comfort and energy savings during the whole year Moreover after increasing of the exter...

Страница 9: ...the above mentioned operations are controlled per boiler display and the FH text appears Regulation of the heating temperature Regulation can be performed via menu of the time remote control as well...

Страница 10: ...lose the filling tap See 1 Connection to the DHW tank of the KT Plus KT small Plus boilers Control electronics of the boiler serves to control the external DHW tank Make hydraulic connections followin...

Страница 11: ...e heating system It is recommended to use copper filter with side cleaning and it has to be cleaned in regular intervals depending on system clogging Due to the maintenance and servicing it is recomme...

Страница 12: ...and theymust be equippedwith bipolarswitch with minimumcontactdistanceof 3mm with integratedfuse of 3A max between boiler and mais By electrical connections it is necessary to keep polarity PHASE bro...

Страница 13: ...Access to electrical terminal of the KST Plus KT Plus KT small Plus boilers To access to boiler terminal it is necessary to remove rear cover and then to make necessary electrical connections as it is...

Страница 14: ...of andminimumdistancesfromwindows walls ventilationopenings etc This appliance of C type has to be installed by usage of suction pipes and exhaust outlets supplied by producer in conformity with UNI C...

Страница 15: ...t is necessary to check if the max permitted length was not exceeded concern that every coaxial bow causeslengthreductionas itisgiveninthetable Connection by separatetubes Examplesofconnectionwith sep...

Страница 16: ...tedfromflammablematerials withconnectiontosingleapplianceon 1floor with connection to same appliances or different but all appliances only with forced flue gas outlet or onlywithnatural fluegas exhaus...

Страница 17: ...akethefollowingsteps 1 Removecovering 2 Open hermeticchamber 3 Hang down fixingclipC andpickgaspipeA outof thefanunit Venturi 4 ExchangenozzleBlaidinsidethegaspipefornozzlefromboilertransformationset...

Страница 18: ...sure C Regulation screw min output setting D Regulation screw max output setting By max output is CO2 set by regulation screw D by max output is CO2 set by regulation screw C Co2 test by max output 1...

Страница 19: ...utionsystem checkpressure inheatingsystem cca1bar incoldstate filloutletsyphone andcheckcorrectconnectiontooutletdeviceforcondensewater check ifthereis no waterleakageintheheatingsystem DHWcircuit con...

Страница 20: ...rectly with no sediments Gas and water supply connections must be ensured against leakage Pressure of water in distribution device in cold state must be approximately 1 bar If pressure is different ad...

Страница 21: ...flame in start up phase Unstable pressure Check burner 6 times within 4 min Error Check setting of gas valve by min output Flue gas outlet clogged Remove barries from piping of flue gas outlet Syphon...

Страница 22: ...heating system c h return flow Dimensions and connections of the KT Plus boiler Dimensions and connections 1 Inlet into heating system c h flow connection 3 Gas inlet 5 Return flow from heating system...

Страница 23: ...ing system c h return flow 6 Safety valve release Dimensions and connections of the KT small Plus boiler Dimensions and connections 1 Inlet into heating system c h flow connection 3 Gas inlet 5 Return...

Страница 24: ...lter on cold water inlet 40 Expanse vessel of supply water 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 82 Ionisation electrode 95 Three way valve 130 Pump of supply water 145 Man...

Страница 25: ...tion valve 37 Filter at cold water inlet 39 Regulator of supply water flow 42 Temperature sensor of supply water 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 82 Ionisation electro...

Страница 26: ...valve 56 Expanse vessel 74 Tap to fill distribution device 82 Ionisation electrode 95 Three way valve 114 Sensor of water pressure 161 Heat exchanger 186 Sensor of return connection of heating water...

Страница 27: ...44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 95 Three way valve 97 Magnesium anode 130 Pump of supply water 154 Pipe for condensed water outlet 161 Heat exchanger 186 Sensor of h...

Страница 28: ...reator 37 Filter at cold water inlet 42 Temperature sensor of supply water 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 95 Three way valve 114 Water pressure sensor 136 Sensor of...

Страница 29: ...ting 36 Automatic deareator 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 95 Three way valve 114 Water pressure sensor 154 Condensed water outlet 161 Heat exchanger 186 Sensor of h...

Страница 30: ...ve flue gas overflow kg h 30 3 Min substantive flue gas overflow kg h 5 3 Max flue gas temperature C 63 Min flue gas temperature C Class of efficiency by directive 92 42EHS Emissions class Nox Max ope...

Страница 31: ...278 Double sensor Heating Safety A Contact EKO KOMFORT OPENED mode eco comfort enabled by control panel or remote controller CLOSED mode eco comfort disabled comfort mode remains active Electrical sc...

Страница 32: ...e way valve 114 Switch of water pressure 138 External sensor 139 Remote time controller 186 Sensor of return flow of heating water 188 Ignition electrode 191 Flue gas temperature sensor 278 Double sen...

Страница 33: ...00 paint Accessories of double flue gas exhaust and air suction with diameter of 80 mm Code Name PR45 pipe of exhaust and suction 1m D80 Pr46 1 m D80 extension Pr47 0 5 m D80 extension PR48 elbow 90 D...

Страница 34: ...34...

Страница 35: ...of operation Date Stamp signatureofserviceorganization Obligatory service examination after the 3 rd year of operation Date This page serves for confirming service examinations and is kept by a custom...

Страница 36: ...o producer reserves the right to change technical parameters and dimensions of boilers without previous warning Der Hersteller ATTACK s r o beh lt sich das Recht der technischen Ver derungen an Produ...

Отзывы: