Table of error messages
Diagnostics
Boiler is equipped with modern system for autodiagnostics. In case of boiler error, display flickers
together with the sign of error and number indicating error code.
There are errors, that cause permanent blockage (marked by „
A
“ letter): to get boiler back to normal
operation, press RESET button for 1 second or use RESET on remote time controller (additional), if
it is installed; if boiler does not come to operation, it is necessary to remove the fault. Errors (marked
by „
F
“ letter) cause often blockages, that are automatically removed, immediately after the value gets
back into the interval of normal boiler operation.
21
Code
Error
Possible cause
Solution
Check, if gas inlet into boiler is balanced and if pipes are deareated
Error of ignition and ionisation electrode
Check cable connection of electrodes, their correct placing and
if there are no sediments on them
Damaged gas valve
Check and change gas valve
Insufficient gas pressure in network
Check gas pressure in distribution network
Blocked syphon
Check and clean syphon, if necessary
Signal of flame presence
by extinguished burner
Error of electrode
Check cable connection of ionisation electrode
Damaged sensor of heating
Check correct placing and operation of central heating sensor
Water in device does not circulate
Check circuiting pump
Areated heating system
Deareate heating system
Intervention of fuse of flue
gas and smoke exhaust
Error F07, that occured 3-times
in last 24 hours
Action of ventilator fuse
protection
Error F15 that remained for 1 hour
period
Error of ionisation electrode
Check position of ionisation electrode or exchange it
No flame in start-up phase
Unstable pressure
Check burner
(6-times within 4 min.)
Error
Check setting of gas valve by min. output
Flue gas outlet clogged
Remove barries from piping of flue gas outlet
Syphon clogged
Check and eventually clean the syphon
Damaged sensor
Sensor failure at the entry
Cabling under shortage
into distribution device 1
Aborted cables
Damaged sensor
Failure of sensor of return flow
Cabling under shortage
Aborted cables
Damaged sensor
Sensor failure at the entry
Cabling under shortage
into distribution device 2
Aborted cables
Supply voltage lower than
170V
Incorrect frequency in
electrical mains
Incorrect water pressure in
Too low pressure
Refill system with water
device
Damaged sensor/ switch of pressure
Change the RZT sensor or RT,RST pressure sensor
F39
External probe error
Damaged sensor or shortage
Change sensor or check connection of cables
Incorrect water pressure in
Check safety valve
device
Check pressure in expanse vessel
A41
Placing of sensors
Sensor disconnected from pipe
Check correct placing of sensor
F42
Error of heating sensor
Damaged sensor
Change sensor
Water in device does not circulate
Check circuit pump
F43
Safety action of exchanger
Areated distribution device
F47
Error of pressure sensor
Aborted cables
Check connection of cables
F50
Error of modulation reel
Aborted cables
Check connection of cables
Check connection of cables or change sensor
F14
Check connection of cables or change sensor
Problems with electricity mains
Check electricity mains
F34
F11
See error F15
A05
A06
F10
Check connection of cables or change sensor
Boiler overheating
A03
A04
See error F07
No gas is supplied
Burner did not ignit
A01
Check electronics
Error of control electronics
A02
Deareate heating system
F40
Too high water pressure
Problems with electricity mains
Check electricity mains
F35
F37