Table of error messages

Diagnostics

Boiler is equipped with modern system for autodiagnostics. In case of boiler error, display flickers 
together with the sign of error and number indicating error code.
There are errors, that cause permanent blockage (marked by „

A

“ letter): to get boiler back to normal 

operation, press RESET button for 1 second or use RESET on remote time controller (additional), if 
it is installed; if boiler does not come to operation, it is necessary to remove the fault. Errors (marked 
by „

F

“ letter) cause often blockages, that are automatically removed, immediately after the value gets 

back into the interval of normal boiler operation.

21

Code

Error

Possible cause

Solution

Check, if gas inlet into boiler is balanced and if pipes are deareated

Error of ignition and ionisation electrode

Check cable connection of electrodes, their correct placing and
if there are no sediments on them

Damaged gas valve

Check and change gas valve

Insufficient gas pressure in network

Check gas pressure in distribution network

Blocked syphon

Check and clean syphon, if necessary 

Signal of flame presence 
by extinguished burner

Error of electrode 

Check cable connection of ionisation electrode

Damaged sensor of heating

Check correct placing and operation of central heating sensor

Water in device does not circulate

Check circuiting pump

Areated heating system

Deareate heating system

Intervention of fuse of flue 
gas and smoke exhaust

Error F07, that occured 3-times
in last 24 hours

Action of ventilator fuse 
protection

Error F15 that remained for 1 hour
period

Error of ionisation electrode 

Check position of ionisation electrode or exchange it

No flame in start-up phase

Unstable pressure

Check burner

 (6-times within 4 min.)

Error

Check setting of gas valve by min. output

Flue gas outlet clogged

Remove barries from piping of flue  gas outlet

Syphon clogged

Check and eventually clean the syphon

Damaged sensor

Sensor failure at the entry

Cabling under shortage

into distribution device 1

Aborted cables

Damaged sensor

Failure of sensor of return flow

Cabling under shortage
Aborted cables

Damaged sensor

Sensor failure at the entry

Cabling under shortage

into distribution device 2

Aborted cables

Supply voltage lower than 
170V
Incorrect frequency in  
electrical mains
Incorrect water pressure in

Too low pressure

Refill system with water 

device

Damaged sensor/ switch of pressure

Change the  RZT sensor or  RT,RST pressure sensor

F39

External probe error

Damaged sensor or shortage 

Change sensor or check connection of cables

Incorrect water pressure in

Check safety valve

device

Check pressure in expanse vessel

A41

Placing of sensors

Sensor disconnected from pipe

Check correct placing of sensor 

F42

Error of heating sensor

Damaged sensor

Change sensor

Water in device  does not circulate

Check circuit pump

F43

Safety action of exchanger

Areated distribution device

F47

Error of pressure sensor

Aborted cables

Check connection of cables

F50

Error of modulation reel

Aborted cables

Check connection of cables

Check connection of cables or change sensor

F14

Check connection of cables or change sensor

Problems with electricity mains

Check electricity mains

F34

F11

See error F15

A05

A06

F10

Check connection of cables or change sensor

Boiler overheating

A03

A04

See error F07

No gas is supplied

Burner did not ignit

A01

Check electronics

Error of control electronics

A02

Deareate heating system

F40

Too high water pressure

Problems with electricity mains

Check electricity mains

F35

F37

Содержание KST

Страница 1: ...W W W A T T A C K S K GASCONDENSINGBOILER ATTACK KZT KST KT KTSmall KZTSolarPlus INSTRUCTIONS FOR USE...

Страница 2: ...Hydraulic connections Gas connection anti freeze system Electrical coonections and external sensor Placing of external probe and access to el terminal Flue gas outlets Accessories Connection to outle...

Страница 3: ...ed with electronic ignitionandionisationflamecontrol venilatorwithmodulationofrotationsandmodulationgasvalve Control panel of boilers KT Plus KT small Plus KST Plus Pic 1 Control panel Description 1 B...

Страница 4: ...s by symbol of water tap see page 9 pic 1 Water in exchanger is permanently warmed to temperature of 45 C Display see page 11 pic 1 shows actual temperature of water in the boiler Start and stop of bo...

Страница 5: ...ture It is possible to set the temperature from the minimum of 10 C up to the maximum of 65 C by the buttons of DHW see 1 and 2 Pic 1 Setting of the environment temperature with additional room thermo...

Страница 6: ...Setting temperature at the DHW outlet flickers during the Heat exchanger protection operation 15 Indication of Eco Economy mode or Comfort mode 16 Temperature of the external sensor with additional ex...

Страница 7: ...utton for 1 second again see 9 Pic 2 Boiler will be immediately ready for operation by every DHW consumption or by activation through the room thermostat Indication during heating operation of the KZT...

Страница 8: ...de is temperature of the heating device regulated according to the external climatic conditions to ensure higher comfort and energy savings during the whole year Moreover after increasing of the exter...

Страница 9: ...the above mentioned operations are controlled per boiler display and the FH text appears Regulation of the heating temperature Regulation can be performed via menu of the time remote control as well...

Страница 10: ...lose the filling tap See 1 Connection to the DHW tank of the KT Plus KT small Plus boilers Control electronics of the boiler serves to control the external DHW tank Make hydraulic connections followin...

Страница 11: ...e heating system It is recommended to use copper filter with side cleaning and it has to be cleaned in regular intervals depending on system clogging Due to the maintenance and servicing it is recomme...

Страница 12: ...and theymust be equippedwith bipolarswitch with minimumcontactdistanceof 3mm with integratedfuse of 3A max between boiler and mais By electrical connections it is necessary to keep polarity PHASE bro...

Страница 13: ...Access to electrical terminal of the KST Plus KT Plus KT small Plus boilers To access to boiler terminal it is necessary to remove rear cover and then to make necessary electrical connections as it is...

Страница 14: ...of andminimumdistancesfromwindows walls ventilationopenings etc This appliance of C type has to be installed by usage of suction pipes and exhaust outlets supplied by producer in conformity with UNI C...

Страница 15: ...t is necessary to check if the max permitted length was not exceeded concern that every coaxial bow causeslengthreductionas itisgiveninthetable Connection by separatetubes Examplesofconnectionwith sep...

Страница 16: ...tedfromflammablematerials withconnectiontosingleapplianceon 1floor with connection to same appliances or different but all appliances only with forced flue gas outlet or onlywithnatural fluegas exhaus...

Страница 17: ...akethefollowingsteps 1 Removecovering 2 Open hermeticchamber 3 Hang down fixingclipC andpickgaspipeA outof thefanunit Venturi 4 ExchangenozzleBlaidinsidethegaspipefornozzlefromboilertransformationset...

Страница 18: ...sure C Regulation screw min output setting D Regulation screw max output setting By max output is CO2 set by regulation screw D by max output is CO2 set by regulation screw C Co2 test by max output 1...

Страница 19: ...utionsystem checkpressure inheatingsystem cca1bar incoldstate filloutletsyphone andcheckcorrectconnectiontooutletdeviceforcondensewater check ifthereis no waterleakageintheheatingsystem DHWcircuit con...

Страница 20: ...rectly with no sediments Gas and water supply connections must be ensured against leakage Pressure of water in distribution device in cold state must be approximately 1 bar If pressure is different ad...

Страница 21: ...flame in start up phase Unstable pressure Check burner 6 times within 4 min Error Check setting of gas valve by min output Flue gas outlet clogged Remove barries from piping of flue gas outlet Syphon...

Страница 22: ...heating system c h return flow Dimensions and connections of the KT Plus boiler Dimensions and connections 1 Inlet into heating system c h flow connection 3 Gas inlet 5 Return flow from heating system...

Страница 23: ...ing system c h return flow 6 Safety valve release Dimensions and connections of the KT small Plus boiler Dimensions and connections 1 Inlet into heating system c h flow connection 3 Gas inlet 5 Return...

Страница 24: ...lter on cold water inlet 40 Expanse vessel of supply water 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 82 Ionisation electrode 95 Three way valve 130 Pump of supply water 145 Man...

Страница 25: ...tion valve 37 Filter at cold water inlet 39 Regulator of supply water flow 42 Temperature sensor of supply water 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 82 Ionisation electro...

Страница 26: ...valve 56 Expanse vessel 74 Tap to fill distribution device 82 Ionisation electrode 95 Three way valve 114 Sensor of water pressure 161 Heat exchanger 186 Sensor of return connection of heating water...

Страница 27: ...44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 95 Three way valve 97 Magnesium anode 130 Pump of supply water 154 Pipe for condensed water outlet 161 Heat exchanger 186 Sensor of h...

Страница 28: ...reator 37 Filter at cold water inlet 42 Temperature sensor of supply water 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 95 Three way valve 114 Water pressure sensor 136 Sensor of...

Страница 29: ...ting 36 Automatic deareator 44 Gas valve 56 Expanse vessel 74 Tap to fill distribution device 95 Three way valve 114 Water pressure sensor 154 Condensed water outlet 161 Heat exchanger 186 Sensor of h...

Страница 30: ...ve flue gas overflow kg h 30 3 Min substantive flue gas overflow kg h 5 3 Max flue gas temperature C 63 Min flue gas temperature C Class of efficiency by directive 92 42EHS Emissions class Nox Max ope...

Страница 31: ...278 Double sensor Heating Safety A Contact EKO KOMFORT OPENED mode eco comfort enabled by control panel or remote controller CLOSED mode eco comfort disabled comfort mode remains active Electrical sc...

Страница 32: ...e way valve 114 Switch of water pressure 138 External sensor 139 Remote time controller 186 Sensor of return flow of heating water 188 Ignition electrode 191 Flue gas temperature sensor 278 Double sen...

Страница 33: ...00 paint Accessories of double flue gas exhaust and air suction with diameter of 80 mm Code Name PR45 pipe of exhaust and suction 1m D80 Pr46 1 m D80 extension Pr47 0 5 m D80 extension PR48 elbow 90 D...

Страница 34: ...34...

Страница 35: ...of operation Date Stamp signatureofserviceorganization Obligatory service examination after the 3 rd year of operation Date This page serves for confirming service examinations and is kept by a custom...

Страница 36: ...o producer reserves the right to change technical parameters and dimensions of boilers without previous warning Der Hersteller ATTACK s r o beh lt sich das Recht der technischen Ver derungen an Produ...