Sanitation Procedure

continue to run pump if water doesn’t flow.
B. The high level of chlorine required to sanitize 

a water system is corrosive to most metals and 

 

chlorine solution must not be allowed to remain in water 

system more than 36 hours before being completely flushed 

from system.
8.  After  system  has  been  completely  flushed,  perform  a 

bacteriological analysis on the water following all applicable 

procedures.
NOTE:  Always follow the sanitizing procedure required by 

applicable state or local laws.
EPA Registered:  Well sanitizer pellets are EPA Registered 
for sanitizing potable water.  EPA Registration No. 50510-1
LARGE DIAMETER WELLS:  Dug or bored wells 

should be disinfected in the same way as a drilled one.  Lower 

the water level as much as possible, remove the sand, silt 

and debris, and then treat with the chlorine solution.  Mix 

thoroughly by circulating the water back into the well  and 

use the hose to rinse the interior lining of the well. Do not 

try to disinfect an unprotected, unlined well because new 

seepage or surface contamination will flow into the water 

about as fast as you can disinfect it.  Disinfect the pipeline 

distribution system as indicated for drilled wells.
SPRINGS AND CISTERNS:  Mix about ½ cup of 

household bleach in 5 gallons of water and use this to 

scrub the walls of the spring box or holding tank.  With 

a  constant  flow  of  fresh  water  from  the  spring,  there  is  

probably no way of detaining the chlorine solution in the 

reservoir for more than a few minutes.  However, the 

chlorinated  water  should  flow  through  the  pipeline  to 

disinfect the distribution system.  Cisterns can be disinfected 

in the same way but a source of clean water will be needed to 

flush the dirty waste out of the system.
For additional information about how to protect wells and 

springs and keep them from becoming contaminated, call or 

visit your local Cooperative Extension office, or your nearest 

certified water treatment specialist.
TABLE 1 **  Quantity of solution mixed - 5.25% 

available chlorine (laundry bleach) for disinfecting  

 

 

 

wells, or 52,500 P.P.M..

WQA recommends 50mg/l or ppm chlorine 

concentration.

Formula: C2 X V2 / C1 = V1

C1= Household Bleach (52,500 P.P.M.) 

V1= Chlorine Amount Needed

C2= 50 mg/L 

V2= 80 gallons holding time

I.E.  50-ml/g X 80 gal= 4000/52,500= .08 gallons of chlorine (5.25%)

        .08 gal chlorine (5.35%) X 128 (oz/gal) = 10.24 oz (5.25%)

Dug Wells - 3 to 4 feet diameter - 4 cups per foot of water

Drilled Wells - 3 to 8 inch diameter - 1 cup per foot of water

HOW TO DISINFECT A WATER SYSTEM:
Every  new  well,  or  existing  water  supply  system  that 

has been disrupted for service or repair, should be 

disinfected before it is returned to use. Water in the 

well and storage tank should be treated with a strong  

chlorine solution to destroy disease organisms.  All pipelines 

and  fixtures  in  the  distribution  system  should  be  rinsed 

and flushed with chlorinated water.  Upon installation of 

a U.V. disinfection unit or yearly bulb replacement service, 

disinfection  with  chlorine  to  initially  flush  the  system  is 

recommended to assure line sanitation prior to U.V. start up.
The source of chlorine can be ordinary household liquid 

laundry bleach (about 5.25% available chlorine).  The 

quantity required depends on the volume of water to be 

treated.  The United States Environment Protection Agency 

(EPA) indicated that about 100 parts of chlorine, by weight, 

mixed in a million parts of water help destroy essentially all 

water-borne disease organisms.  Table 1 shows the quantity 

of liquid bleach required to disinfect wells of various 

diameters and depths.  
DISINFECTION PROCEDURE:
1. Remove the cap or seal from the casing and measure 

the depth of the water in the well, then refer to Table 2 to 

determine how many chlorine pellets should be used.  In 

some instances removing the seal to measure the water can 

be a difficult task, and it is easier to estimate well and water 

depth from well  log or other records.
2. Remove well cap and determine if there is an unobstructed 

path from the top of the well to the water level.  If it is not 

possible to remove the well cap, remove vent or sanitation 

access plug.
3. Drop one pellet into the well and listen to hear if it hits the 

water.  If the pellet hits the water, drop one-half the number 

of pellets determined to be needed into the well.  These will 

sink to the bottom and sanitize the lower part of the well.
4. Mix the remaining pellets in a few gallons of water in a 

CLEAN plastic container and pour the solution into the well.
5. In order to mix the chlorine thoroughly throughout the 

entire water system, it is necessary to re-circulate the water in 

the well.  This can be accomplished by connection a hose to 

an out side faucet that is located after the pressure tank.  Use 

hose to run water back down the well (this also rinses upper 

portion of well).  After about 15 minutes of recirculation the 

water, a strong chlorine odor should be apparent.  Turn off 

hose.
6. Bypass water softener and filters and open each water 

outlet in the water system until chlorine is present in water.  

This procedure assures that all the water in the system is 

chlorinated.
7. Allow the chlorinated water to stand in the system for 

at least one (1) hour, and preferable overnight. After this, 

open an outside faucet system until water runs chlorine free.  

Repeat flush operation on each faucet in system.
NOTE:
A
. Chlorine may break loose iron deposits, slime and organic 

material.  This material will make the water discolored.  The 

material broken loose may plug pump screens.  Do not 

GDS ©2019 • www.aquat.com

Содержание GDS-12

Страница 1: ... Info Installation Operation and Maintenance Manual CAUTION Read and Follow all safety rules and operating instructions before first use of product Ultraviolet Disinfection Systems Models GDS 8 GDS 12 GDS 20 ...

Страница 2: ...GDS 2016 2 ...

Страница 3: ...6 Installation Diagram 7 Electronic Controls Startup Procedures 8 Sanitation Procedures 10 Maintenance 12 Unit Parts Breakdown 13 Circuit Board Layout 16 Wiring Diagram 17 Troubleshooting 18 Sterile Water Sample Precedures 19 Specifications 20 Notes 21 Warranty 23 Table of Contents GDS 2019 www aquat com ...

Страница 4: ...ause an unsafe condition 7 Intended for indoor use Do not install this disinfection system where it will be exposed to the weather Do not store this disinfection system where it will be exposed to temperatures below freezing unless all the water has been drained from it and the water supply has been disconnected 8 Read and observe all the important notices and warnings on the water disinfection sy...

Страница 5: ...tion equipment may be required if these parameters cannot be maintained Flow rate must not The GDS series has an unique design with an ultraviolet germicidal lamp housed within a single quartz sleeve surrounded by a stainless steel pressure chamber The chamber is fabricated out of 304 Stainless Steel These units come with an ultraviolet lamp designed with four pins at one end The quartz sleeve is ...

Страница 6: ...proper wall support Use anchores with screws for sufficient support not included A lock nut secures the mounting bracket to the U V chamber If your piping system is subject to impulse pressure resulting in a water hammer condition a surge tank or other means must be provided to remove this condition otherwise this extreme shock pressure condition may rupture or fracture the quartz sleeve Make all ...

Страница 7: ...GDS 2016 7 Installation Diagram GDS 2019 www aquat com ...

Страница 8: ... This is also equipped with an internal and external fused surge protection system This solid state electronic circuit board provides the latest in U V lamp monitoring technology U V LAMP CONTROL START UP PROCEDURE 1 Make sure the U V lamp is inserted per instructions into the quartz sleeve and U V chamber Then plug the U V lamp into the end lamp connectors 2 Plug the unit into a 120V wall plug ou...

Страница 9: ...GDS 2016 9 Sample Screen Shots GDS 2019 www aquat com MONTH DAY ALARM Fig 1 MONTH DAY ALARM Fig 2 MONTH DAY ALARM Fig 3 MONTH DAY ALARM Fig 4 ...

Страница 10: ...er in the well and storage tank should be treated with a strong chlorine solution to destroy disease organisms All pipelines and fixtures in the distribution system should be rinsed and flushed with chlorinated water Upon installation of a U V disinfection unit or yearly bulb replacement service disinfection with chlorine to initially flush the system is recommended to assure line sanitation prior...

Страница 11: ... disinfect the water if necessary Plumbing Line Sanitation Only When installing an ultraviolet disinfection system a pre filter with sump may serve as a source to sanitize the water lines only For whole system disinfection follow procedure as outlined above Source The Pennsylvania State University College of Agriculture Cooperative Extension How to Sanitize a Water System Using Well Sanitizer Pell...

Страница 12: ...trical connection Then remove brass end nut Install the quartz sleeve through the stainless steel threaded nipple until it is centered in the quartz spring Use a small amount of plumber s grease and install the O ring around the quartz sleeve Avoid riding the O Ring on any threaded part of the nipple Hand tighten the brass end nut to form a compression seal around the quartz sleeve Avoid over tigh...

Страница 13: ...LACE DECIMAL 010 THREE PLACE DECIMAL 002 UNLESS OTHERWISE SPECIFIED 3 29 2017 ATS GDS CUSTOMER 3 5 2 6 7 ITEM NO PART NUMBER DESCRIPTION QTY 1 ATS GDSF GDS Control Box Front Cover 1 2 ATS 281P ATS 281P Circuit Board 1 3 ATS PBBP Plastic Control Box Back Plate 1 4 ATS 4003 Power Cord 1 5 03 SA 015 Molded Lamp Cord 1 6 07 00017 Fuse 1 7 ATS1 421P GDS Ballast 1 DO NOT SCALE DRAWING SHEET 1 OF 1 SCALE...

Страница 14: ...H CHECKED ENG APPR MFG APPR DATE NAME TITLE SIZE DWG NO REV WEIGHT SCALE SHEET 1 OF 1 DO NOT SCALE DRAWING 12 6 3 5 2 1 10 7 4 8 11 13 9 ITEM NO PART NUMBER DESCRIPTION QTY 1 ATS 476D Domed Quartz 1 2 ATS4 450 UV Lamp 1 3 ATS 5172 Sightport Lens 1 4 ATS 5173 Orange 7 OD Viewport O Ring 1 5 ATS 5171 Sightport Nut 1 6 ATS5 410 Lock Nut 1 7 ATS GDS GDS Control Box 1 8 STS 8GPM 8 Gallon Per Minute Bot...

Страница 15: ... 25 TWO PLACE DECIMAL 010 THREE PLACE DECIMAL 002 UNLESS OTHERWISE SPECIFIED 3 27 17 B GDS 12 CUSTOMER BOM 10 11 6 4 5 2 1 3 8 9 12 13 7 ITEM NO PART NUMBER DESCRIPTION QTY 1 ATS1 759D Domed Quartz 1 2 ATS4 739 UV Lamp 1 3 ATS 5173 Orange 7 OD Viewport O Ring 1 4 ATS 5172 Sightport Lens 1 5 ATS 5171 Sightport Nut 1 6 ATS5 410 Lock Nut 1 7 ATS 12GPM 12 GPM Flow Control 1 8 STS 12GPM 12 Gallon Per M...

Страница 16: ...EE PLACE DECIMAL 002 UNLESS OTHERWISE SPECIFIED 3 29 2017 GDS 20 CUSTOME 8 6 5 1 12 13 2 7 3 4 10 11 9 ITEM NO PART NUMBER DESCRIPTION QTY 1 ATS 832D Domed Quartz 1 2 ATS4 810 UV Lamp 1 3 ATS 5173 Orange 7 OD Viewport O Ring 1 4 ATS 5172 Sightport Lens 1 5 ATS 5171 Sightport Nut 1 6 ATS5 410 Lock Nut 1 7 ATS8 544 Quartz Sleeve Black 1 2 OD ORing 1 8 ATS5 414 End Nut 1 9 STS 20GPM 20 Gallon Per Min...

Страница 17: ...GDS 2016 17 Circuit Board Layout GDS 2019 www aquat com ...

Страница 18: ... ATS 281P Circuit Bo B DRAWN TDB MATERIAL FINISH CHECKED ENG APPR MFG APPR DATE NAME TITLE SIZE DWG NO WEIGHT SCALE SH DO NOT SCALE DRAWING 4 21 16 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF AQUA TREATMENT SERVICES ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF AQUA TREATMENT SERVICES IS PROHIBITED PROPRIETARY AND CONFIDENTIAL GDS 2019 www aquat com...

Страница 19: ...s Electrical cord disconnected Check replace or outlet defective Defective U V lamp Replace lamp Defective lamp ballast Check output voltage Replace ballast Loose open circuit wire Trace out and repair Leak at quartz nipple Defective or cracked O Ring Replace O Ring O Ring not seated properly Replace O Ring Cracked quartz sleeve Replace quartz sleeve GDS 2019 www aquat com ...

Страница 20: ...inutes 3 Open the sterile bottle or sterile container being used Holding the cap in a down position the operator should then hold his breath while taking the sample so as to avoid oral contamination of the sample The operator must not allow his finger to touch the inside of the cap or the neck of the bottle 4 After the sample has been taken the cap should immediately be tightly placed on the sampl...

Страница 21: ...GDS 2016 21 Specifications GDS 2019 www aquat com ...

Страница 22: ...GDS 2016 22 Notes GDS 2019 www aquat com ...

Страница 23: ...GDS 2016 23 Notes GDS 2019 www aquat com ...

Страница 24: ...GDS 2016 24 Warranty GDS 2019 www aquat com ...

Отзывы: