ATMOS MULTI version 2002
Page 19
Figure 8: Removing the appliance case
.
7.2. Minimum clearances.
For servicing and maintenance purposes, a minimum
clearance of 600mm to the front, 150mm above,
750mm below and 100mm to either side of the boiler
case is required. (fig. 9 & fig 10)
Figure 9: Dimensions & minimum clearances
Figure 10: Dimensions & minimum clearances
7.3 Boiler location.
The Atmos Multi is not suitable for external
installations.
While the appliance itself is provided with integral
frost protection it must however, be installed in a
room that stays free of frost even in extremely cold
conditions. This is to prevent pipes or the safety
valves from freezing. If the selected room does not