Sulphate (ppm)
Type of cooling system
Standard
Energy recovery
Single pass
< 1000
< 200
Recirculating (with tower)
< 1000
not applicable
Closed loop
< 400
< 200
8.
Iron and Manganese
Dissolved iron (ppm)
Dissolved manganese (ppm)
Type of cooling
system
Standard
Energy recovery
Standard
Energy recovery
Single pass
< 1
< 0.2
< 0.2
< 0.05
Recirculating (with
tower)
<
1
not applicable
<
0.2
not applicable
Closed loop
< 1
< 0.2
< 0.2
< 0.05
The values in
bold
are rejection limits.
9.
Copper
Copper (ppm)
Type of cooling system
Standard
Energy recovery
Single pass
< 1
< 0.2
Recirculating (with tower)
< 1
not applicable
Closed loop
< 1
< 0.2
10.
Ammonium
The limit of
0.5 ppm
is a rejection limit.
The limitation only applies for copper containing systems.
11.
Suspended solids
Large particles (size > 10 µm) should not be present as they can be filtered out.
Small particles (< 0.5 µm) are not taken into account.
For particles between 0.5 µm and 10 µm, the following limits apply:
Suspended solids (ppm)
Type of cooling system
Standard
Energy recovery
Single pass
< 10
< 1
Recirculating (with tower)
< 10
not applicable
Closed loop
< 10
< 1
12.
Oil or grease
<
1 ppm
(rejection value)
13.
Biology
If biology is present, it must be aerobic. Anaerobic biology (in closed systems) must be avoided.
Instruction book
2920 7180 30
129
Содержание GA 30+
Страница 1: ...Atlas Copco Oil injected rotary screw compressors GA 30 GA 37 GA 45 Instruction book ...
Страница 2: ......
Страница 15: ...Motor side view GA 30 up to GA 45 Pack Instruction book 2920 7180 30 13 ...
Страница 16: ...Service side view GA 30 up to GA 45 Pack Instruction book 14 2920 7180 30 ...
Страница 17: ...Motor side view GA 30 up to GA 45 Full Feature Instruction book 2920 7180 30 15 ...
Страница 50: ...3 19 Calling up modifying pressure band settings Calling up the settings Instruction book 48 2920 7180 30 ...
Страница 139: ...6 4 Pictographs Description Pictographs 1 2 3 4 5 6 7 8 9 10 11 12 Instruction book 2920 7180 30 137 ...
Страница 188: ......
Страница 189: ......