Compressor type
Voltage
V
Frequency
Hz
Approval
Water-
Cooled
Air-Cooled
Type
GA 160 VSD
460
60
CSA/UL
3x400 A
3x400 A
Class T
fuse; very
fast acting
fuse
4.4
Electric connections
General instruction for the electrical installation of VSD compressors
• Electrical equipment from Atlas Copco Compressor is designed in accordance with the safety regulations
described in IEC60204-1 and CENELEC EN60204.
• It is the responsibility of the customer to install the compressor unit according to the safety regulations in
order to protect people from electric shocks from direct or indirect contact.
• In drives with frequency converters, leakage currents occur along the RFI filter and the cable capacities,
especially during the motor start. Class A leakage detection protections would switch off the machine.
Therefore it is not recommended to use class A detection systems on frequency converters.
Installation instructions for TN, TT, IT
In each network system (TN, TT or IT), the customer has to protect the installation using overcurrent protection
by means of fuses or automatic circuit breaker protection.
With respect to the power distribution system, additional installation instructions are given.
Network type TN (TN-S, TN-C and TN-C-S)
No additional protections need to be installed. If the customer wishes to or needs to install a leakage detection
device, it should be of type B and should comply with IEC755 Amendment 2 "General requirements for
residual current-operated protective devices". Atlas Copco advises customers to install the following earth
leakage detection device: BENDER RCMA 470LY with external current transformer: http://www.bender.org/
prod.html
Network type TT
In the case of TT-systems, safety regulations mostly stipulate the use of an earth leakage circuit breaker
(e.l.c.b). In combination with frequency converters, type B residual current-operated protective devices should
be used. Atlas Copco advises customers to install the following earth leakage detection device: BENDER
RCMA 470LY with external current transformer: http://www.bender.org/prod.html
Network type IT
In IT-network systems, it is permissible for the power supply to continue in the event of an initial earth leakage
fault of a motor phase. However, the customer must detect the initial earth leakage fault. The fault must be
indicated as an alarm. If this is not the case, the initial earth leakage fault must trigger automatic disconnection
of the power supply (EN 60204-1 par.: 6.3). However, the high frequency capacitive leakage currents caused
by frequency converters cannot be detected by standard earth leakage detection systems. Atlas Copco
recommends that customers install: BENDER IRDH 275/435 http://www.bender.org/prod.html.
Instruction book
APF192090
55
Содержание GA 160 VSD
Страница 1: ...GA 160 VSD APF192090 Instruction book ...
Страница 2: ......
Страница 61: ...Electric cabinet Cabinet with VSD Variable Speed Drive unit of GA 132 160 VSD Instruction book APF192090 59 ...
Страница 64: ...Instruction book 62 APF192090 ...
Страница 66: ...Figure A Instruction book 64 APF192090 ...
Страница 67: ...Figure B Instruction book APF192090 65 ...
Страница 70: ...Text on figure Instruction book 68 APF192090 ...
Страница 77: ...Ref Designation 29 Do not mix oil brands Instruction book APF192090 75 ...
Страница 92: ...See Oil specifications Instruction book 90 APF192090 ...
Страница 111: ......